7 Operating ventilation unit(s)
51
7 Operating ventilation unit(s)
The set operating mode and ventilation
level apply to all connected room air controls
and ventilation units, as does the External OFF
function. Other settings (intermittent ventila-
tion, sleep mode) only apply to ventilation
units on the relevant room air control.
Only use cross-ventilation mode for limited
periods so that the rooms do not cool too
much at a low supply air temperature (outside
temperature < 16 °C)
.
If stationary for long periods, replace the
air filters → Observe the attached safety in-
struction sheet.
7.1 Switching on and off
Once the mains fuse has been switched on, the
LEDs of the selected operating mode and ventila-
tion level light up on the wired room air controls
→
Operating keys, displays, LEDs [
PP 45 RC
/
PPB 30 RC
radio-controlled ventilation
units have 3 LEDs on the inner housing.
Select “ventilation level 0” to switch off the ventila-
tion units.
To save energy, the LEDs are dimmed if not used
for 5 minutes. Set value can be changed with
commissioning software.
7.2 Shutter
The shutter in the internal housing of the
PP 45
serves to prevent unpleasant smells/harmful sub-
stances from being drawn into interior rooms and/
or cold outside air flowing in when the unit is
switched off (level 0).
• On
PP 45 O
units, the shutter is opened or
closed by hand. Shutter open (vertical): Turn
rotary knob all the way to the right. Shutter
closed (horizontal): Turn rotary knob all the way
to the left.
• With
PP 45 K
and
PP 45 RC
units, the shutter
opens and closes automatically (servomotor).
•
PPB 30
units do not have a shutter.
Before switching on PP 45 O units, ensure
that all shutters are fully opened. This is the
only way of ensuring perfect ventilation and
air extraction.
7.3 Heat recovery operating mode
All ventilation units connected to a room air con-
trol run with heat recovery (HR) in alternation.
When the HR function is switched on, the associ-
ated status LED (HR) lights up. Interconnected
PP 45
unit pairs and the two internal
PPB 30
fans
switch between ventilation and air extraction in 60
second intervals. The ventilation level can be indi-
vidually adapted to requirements.
7.4 Cross-ventilation operating mode
Suited to rapidly venting living spaces or for cool-
ing (e.g. on summer nights). The air flows in one
direction: Direction of airflow permanently set to
ventilation or air extraction, no heat recovery.
When the function is switched on, the associated
status LED (cross-ventilation) lights up. The vent-
ilation level can be individually adapted to require-
ments.
7.5 Demand-driven sensor mode
This operating mode ensures that the air is dehu-
midified in response to demand or that the room
air quality is improved depending on the sensors
in the ventilation system. If required, the ventila-
tion is automatically adjusted using the humidity,
CO2 or air quality value (VOC) measured by the
sensor.
Automatic operation controls interconnected vent-
ilation units following the stored sensor character-
istics curve (linear course). Sensor value limits for
comfort units, can be set with the commissioning
software. The value limits for Object or
PP 45 RC
units are stored permanently and cannot be
changed. For
PPB 30 RC
units, the limit values
can be changed via the service mode → Installa-
tion instructions for final installation kit.
The demand-driven sensor mode is switched on
manually with
PP 45
or
PPB 30 O
units.
PPB 30 K
/
PPB 30 RC
units automatically regu-
late demand-driven sensor mode. Operating
modes for
PPB 30 K
units = automatic or system
operation, setting with commissioning software
(
PPB 30 K
) or with service mode (
PPB 30 RC
).
Depending on operating mode, demand-driven
mode is started in a continuously variable manner
(automatic operation) or when the maximum per-
mitted room air humidity is exceeded (system op-
eration).
If a ventilation level is set manually on an
RLS 45
K
or
DS 45 RC
during demand-driven mode, the
ventilation units continue to run for 30 minutes in
Содержание PP 45 O
Страница 2: ...Inhaltsverzeichnis Deutsch 3 English 36 Fran ais 70...
Страница 4: ...bersicht PP 45 4 bersicht PP 45...
Страница 6: ...bersicht PPB 30 6 bersicht PPB 30...
Страница 8: ...Steuerungskonzept PP 45 8 Steuerungskonzept PP 45...
Страница 9: ...Steuerungskonzept PPB 30 9 Steuerungskonzept PPB 30...
Страница 10: ...Steuerungskonzept PP 45 RC PPB 30 RC Funk 10 Steuerungskonzept PP 45 RC PPB 30 RC Funk...
Страница 37: ...Table of contents 37 PP 45 RC 110 PPB 30 O 112...
Страница 38: ...Overview of PP 45 38 Overview of PP 45...
Страница 40: ...Overview of PPB 30 40 Overview of PPB 30...
Страница 42: ...PP 45 control concept 42 PP 45 control concept...
Страница 43: ...PPB 30 control concept 43 PPB 30 control concept...
Страница 44: ...PP 45 RC PPB 30 RC wireless control concept 44 PP 45 RC PPB 30 RC wireless control concept...
Страница 72: ...Vue d ensemble PP 45 72 Vue d ensemble PP 45...
Страница 74: ...Vue d ensemble PPB 30 74 Vue d ensemble PPB 30...
Страница 76: ...Concept de commande PP 45 76 Concept de commande PP 45...
Страница 77: ...Concept de commande PPB 30 77 Concept de commande PPB 30...
Страница 78: ...Concept de commande PP 45 RC PPB 30 RC radio 78 Concept de commande PP 45 RC PPB 30 RC radio...
Страница 105: ...105 PP 45 PPB 30 Volumenstr me PP 45 PPB 30 volumetric flows D bits d air PP 45 PPB 30...
Страница 106: ...106...
Страница 107: ...107...
Страница 108: ...108 PP 45 O PP 45 K PP 45 O PP 45 K PP 45 O PP 45 K...
Страница 109: ...109 PP 45 O PP 45 K mit PP 45 HYI PP 45 O PP 45 K with PP 45 HYI PP 45 O PP 45 K avec PP 45 HYI...
Страница 110: ...110 PP 45 RC PP 45 RC PP 45 RC...
Страница 111: ...111 PP 45 RC mit PP 45 HYI PP 45 RC with PP 45 HYI PP 45 RC avec PP 45 HYI...
Страница 112: ...112 PPB 30 O PPB 30 O PPB 30 O...
Страница 114: ......
Страница 115: ......