WS 75 Powerbox shell kit for surface-mount-
ing and flush-mounting

These 

shell installation instructions

 contain important in-

formation about 

installation during the shell construction

phase

.

The enclosed supplementary sheet 

Safety instructions

contains important information for the 

operator

 and 

spe-

cialist installer

Read it carefully and completely

, before

operating, setting, opening the ventilation unit or making
changes to the ventilation system. Follow the instructions.

The enclosed 

brief instructions

 contain important informa-

tion on the settings options on the 

RLS G1 WS 

such as op-

erating modes, ventilation levels, and filter changes.

Additional instructions, videos and tutorials

• For information on final installation, commissioning and

spare parts → 

WS 75 final installation instructions

.

• For information on operation, setting, registration with

the smartphone app or the web tool, as well as mainten-
ance and fault rectification → 

WS 75 operating instruc-

tions

.

Video – Installation of WS 75 Powerbox S

Video – Electrical connection of WS 75

1 Safety

• Before installing the shell components, read 

these in-

structions

, the enclosed supplementary sheet 

Safety in-

structions

 and the 

Brief instructions

.

• Follow the instructions.

• Pass these instructions on to the owner/operating com-

pany for safekeeping.

Safety devices

 are designed for your protection and must

not be bypassed or tampered with.

 The Powerbox does not have a unit switch.

After switching on the mains fuse, the Powerbox
switches on directly.

 CAUTION Cuts due to sharp edges on sheet metal or

housing cut-outs or in the electronics compartment.

Wear protective gloves if necessary. Carefully guide con-
necting cables into unit. Do not damage cables.

2 Scope of delivery for shell units

WS 75 RSAP:

 AP metal shell sheet, 

WW 90

 thermally insu-

lated wall sleeves (= 2 ducts, 500 mm long, outside
Ø 125 mm/inside Ø 90 mm, 2 plaster protective covers
each), Maico sticker and these shell installation instruc-
tions.

WS 75 RSUP:

 Flush-mounted shell tray, 

WW 90

 thermally

insulated wall sleeves (= 2 ducts, 500 mm long, outside
Ø 125 mm/inside Ø 90 mm, 2 plaster protective covers
each), 2 sheet metal adapters with slide-in module, Maico
sticker and these shell installation instructions. 

NOTICE:

Maximum of 4 sheet metal adapters can be installed, 2 of
which are included in scope of delivery, additional sheet
metal adapters are optional.

3 Intended use

The 

WS 75 Powerbox

 serves as a decentralised ventilation

unit with heat recovery for controlled ventilation of indi-
vidual rooms. The Powerbox is suitable for apartments, de-
tached houses and multiple-family dwellings, offices, new
buildings and also for renovation work. The Powerbox is
only intended for domestic use and similar purposes. Any
other or additional use shall be deemed improper.

4 Installation components

1 RSAP metal shell sheet, surface-mounted

2 RSUP shell tray, flush-mounted

3 Thermally insulated wall sleeve, 500 mm

4 WS 75-A sheet metal adapter

5 Permissible component combinations

• WS 75 RSAP + WS 75 Powerbox H with RLS G1 WS +

WS 75 APA surface-mounted cover

• WS 75 RSUP + WS 75 Powerbox H with RLS G1 WS +

WS 75 UPA or UPGA flush-mounted cover

6 Installation location, operating conditions

• For 

WS 75 RSAP/WS 75 RSUP + WS 75 Powerbox H

, per-

manent installation in dry interior rooms is required. The
ventilation unit is installed directly on the inside of the
exterior wall inside living rooms, bathrooms or in a utility
room.

• 24 hour operation is required.

Permissible installation positions

• The unit front (design or glass cover + housing cover)

must be removable at all times. Free access is important
for cleaning and maintenance work.

7 Technical data

Ambient conditions

Ambient temperature

+ 10 °C to + 40 °C

Working space in front of
the unit (removal of covers
and filter changes)

min. 70 cm

Dimensions (WxHxD)

WS 75 RSAP

538 x 1070 x 25 mm

WS 75 RSUP

534 x 1066 x 152 mm

Air connections

Outside air/outgoing air:

WW 90

, outer-Ø

125 mm

Exhaust air/supply air (flex-
ible duct 
MF-F75): Outer Ø

75 mm

Weight (without packaging)

WS 75 RSAP

4.9 kg

WS 75 RSUP

8.1 kg

For more technical data → rating plate.

8 Transport

Observe safety instructions for transport → supplementary
sheet Safety instructions

9 Installation conditions, installation prepara-
tions

• The ventilation unit is only suitable for indoor use (de-

gree of protection IP 00). Protect ventilation unit from
moisture and wetness.

Surface mounting of WS 75 RSAP:

 Only mount ventila-

tion unit on a level wall with sufficient load-bearing ca-
pacity.

Flush mounting of WS 75 RSUP:

 Only insert the ventila-

tion unit in a wall with sufficient load-bearing capacity.
Take into account the dimensions of the fully finished
wall → Sticker on flush-mounted shell kit.

• The customer should provide appropriate mounting ma-

terial for installation.

• Core hole diameter for outside/outgoing air incl. insula-

tion 160 mm, hole with 1 to 2 % downward slope to the
outside.

NOTICE Damage to the unit and damage to the masonry
due to condensation running down the wall if the unit is
installed incorrectly.

Install the wall sleeve in such a way that the condensation
water can run off in the drainage channel of the wall
sleeve towards the exterior wall (1 to 2 % downward
slope). The wall sleeve must protrude 10 - 20 mm beyond
the exterior wall after the plaster etc. has been applied.

• For rear wall supply air/exhaust air connection, use 

MF-

WL 100

 bracket and 

MF-F75

 flexible ducts from Maico.

• Electrical cables: Power cable, NYM 3x1.5 mm². If the op-

erating unit is placed externally, LIYCY 4 x 0.34 mm² type
control cable.

If the connecting cables are too short, the electronics
slide-in module cannot be fully pulled out and fitted in
the housing. Ensure connection cables of a sufficient
length inside the ventilation unit.

• Select installation position so as to avoid contamination

and draughts.

Содержание Powerbox S WS 75

Страница 1: ...lang au en 125 mm innen 90 mm je 2 Putzschutzdeckel Maico Aufkleber und diese Rohbauanleitung WS 75 RSUP UP Rohbauwanne w rmeged mmte Wand h lsen WW 90 2 Rohre 500 mm lang au en 125 mm innen 90 mm je...

Страница 2: ...rch die Au enwand gef hrt Die Zuluft und Abluft wird im Powerbox H Ger t seitlich durch Zuluft und Abluft ffnungen durch die Aufputzabde ckung APA geleitet F r zus tzliche r ckwandseitige Zu luft Ablu...

Страница 3: ...hten an der Wand rings um den Zuluft und Abluftstutzen einen durchgehenden Silikonstreifen an bringen Silikon bauseitig 6 Weiteren Einbau wie im vorigen Kapitel Schritt 7 bis 12 vornehmen 10 3 WS 75 R...

Страница 4: ...ng durch die Kabel durchf hrung stecken Bei externer Platzierung der Be dieneinheit au erhalb der Abdeckung UPA UPGA zu s tzlich die Steuerungsleitung durch die Kabeldurchf h rung stecken ACHTUNG Leit...

Страница 5: ...und erm glicht eine Wiederverwendung wertvoller Rohstoffe bei m glichst geringer Umweltbelastung Entsorgen Sie folgende Komponenten nicht ber den Hausm ll Altger te Verschlei teile z B Luftfilter de f...

Страница 6: ...e Powerbox is only intended for domestic use and similar purposes Any other or additional use shall be deemed improper 4 Installation components 1 RSAP metal shell sheet surface mounted 2 RSUP shell t...

Страница 7: ...st be pushed in so far that they are flush with the tabs of the stop plate NOTICE On the exterior wall side the ducts are cut to length when mounting the external cover The WW 90 ducts must protrude 1...

Страница 8: ...is correct can the design or glass cover be hooked into the frame and locked in place during final installation Insert the RSUP shell tray into the shell wall in such a way that the frame rests agains...

Страница 9: ...e finished tiled plastered wall Screw down tray at the 4 lateral fastening tabs X Alternat ively the shell tray can be screwed down directly to the wall 4x pos Y If desired the shell tray can be brick...

Страница 10: ...lectrical and elec tronic scrap environmentally hazardous li quids oils etc Dispose of them in an envir onmentally friendly manner and recycle them at the appropriate collection points Waste Disposal...

Страница 11: ...on peut installer 4 adap tateurs en t le au maximum dont 2 sont fournis adapta teurs en t le suppl mentaires en option 3 Utilisation conforme Le WS 75 Powerbox sert d appareil de ventilation d cen tra...

Страница 12: ...via cache de protection WS 75 APA Les gaines d air rejet d air ext rieur sont pass s travers le mur ext rieur du c t de la paroi arri re du RSAP L air entrant et l air sortant sont dirig s dans l app...

Страница 13: ...r galement les milieux des trous d air entrant et sortant Air sortant Air entrant Air ext rieur Air rejet 3 R aliser les chancrures pour les querres MF WL 100 dans le mur Tenir compte galement de la p...

Страница 14: ...e 10 20 mm du mur ext rieur La saillie sert de larmier l int rieur de la protection externe En cas de montage incorrect endommagement du mur ext rieur 7 Enlever s parer l un des passe c bles pr d coup...

Страница 15: ...ontre l encrassement avec les couvercles de protec tion fournis 5 Monter le Powerbox H et le cache de protection montage encastr UPA UPGA et mettre l appareil de ventilation en service vid os tutoriel...

Отзывы: