Montage- und Betriebsanleitung EZR ..., DZR ...
Installation and operating instructions for EZR ..., DZR ...
Notice de montage et mode d'emploi EZR ..., DZR ...

EN

5

Maico Elektroapparate-Fabrik GmbH 

I

 Steinbeisstr. 20 

I

 78056 Villingen-Schwenningen 

I

 Germany 

www.maico-ventilatoren.com

 

I

 S49 7720 6940 

I

 [email protected]

0185.0928.0006_RLF.9_05.23_DSW-AS

6 Technical data

Rated voltage

230 V AC or 400 V 3 N PE,
depending on unit variant

Power frequency

50 Hz

Degree of protection

IP 55
IP 54 for EZR/DZR … 

D

Degree of protection only
guaranteed in horizontal in-
stallation position or, in the
case of vertical installation,
with downward air flow.

Air volume, free outlet or
free inlet

500 to 14,800 m³/h, de-
pending on unit variant

Maximum airstream tem-
perature

40 °C or 60 °C, depending on
the unit variant

Weight

5.7 to 41 kg, depending on
unit variant

For more technical data → rating plate.

For dimensions and characteristic curves → 

www.maico-

ventilatoren.com

.

7 Transport, storage

WARNING:

 Observe the attached 

safety instruction sheet

for industrial fans. Do not attach transport equipment
(cables, chains etc.) to sensitive components (impeller, ter-
minal box).

Store fan horizontally only (at -10 °C to +60 °C).

 Avoid

storage periods that are too long. Recommendation: store
for a max. of 1 year. Before installation, check that the
moving parts (impeller) can move freely.

8 Installation instructions

• Observe the air flow and rotational direction according

to the arrows on sticker [S] → 

Unit overview [

}

 4]

.

• Use ducts (folded spiral-seams ducts) that match the

nominal size of the unit variant.

• Observe the roof’s permissible load-bearing capacity

(min. of 200 kg/m², for heavy units a min. of 300 kg/m²).

• Lay connecting cables (ventilation duct, power cable,

control cable) at the installation site.

• The customer must provide suitable mounting material

(strength class 8.8) which is sufficiently dimensioned to
support the basic unit.

• To avoid sound bridges to the building structure, ob-

serve the planning instructions regarding the unit posi-
tion and distances to other façade components. If neces-
sary, use isolating elements.

9 Installation, electrical connection

9.1 Installation

NOTICE Risks of leakages if unit is not sealed tightly
enough.

Firmly screw fan down to the duct system at all flange
holes. Fit suitable insulation, sound-absorbing and installa-
tion materials.

1. Cut the folded spiral-seams duct at the installation site

if the duct system is already installed.

2. Secure appropriate 

FU

 mounting foot to fan housing

with suitable screws provided. Any installation position
can be selected. Make sure that there is free access to
terminal box at the installation site.

3. Transport the fan to installation site and set it down

there. Observe chapter Transport.

4. Mount pre-assembled fan unit (incl. mounting foot) on

the wall, ceiling or bracket. Mounting material of the
sufficient size should be provided by the customer.

5. Lay suitable folded spiral-seams ducts flush against the

fan on the inlet and outlet sides. Observe spacing for
flexible cuffs or 

EL

 or 

ELA

 flexible couplings.

6. Securely screw folded spiral-seams ducts to the fan

flange holes with flexible cuffs or with 

EL

 or 

ELA

 coup-

lings. Screw all flange holes. Ensure seal integrity.

7. With a free inlet, also fit an 

SG

 protective grille as pro-

tection against accidental contact and drawing in.

8. Fit suitable insulation and sound-deadening material.

9.2 Electrical connection

NOTICE Risk of damage to unit in the event of short cir-
cuits.

Insulate any unnecessary cable cores.

 Make sure to connect the fan to an external

control device with automatic latching switch-off.
The control device must not switch on again auto-
matically after being tripped.

 Pole-changeable motors with speed ratios of

8/4 or 4/2 are switched according to the Dahlander
principle.

 For DZR fans, air flow direction is reversed if

you rewire the external conductors L1 and L2.

 Operation with a frequency converter is only

permitted after consultation with the factory.
Feasibility must be checked on a case-by-case
basis.

Prescribed tightening torques

Components

Tightening torque

Terminal box cover: M4
stainless steel cylinder head
screws

1.0 Nm

Sheath terminal M7 x 0.75
mm

0.7 Nm

Motor terminals TK

0.7 Nm

1. Remove the terminal box cover.

2. Pierce a round opening in the cable grommet in the ter-

minal box with a grommet puncher. Note cable dia-
meter.

3. Guide the power cable into the terminal box such that

the cable grommet fits around the cable sheathing
completely. If necessary, seal the cable grommet on
site.

4. Wire fan to the terminal block according to the circuit

diagram Circuit diagrams, wiring diagrams. Observe the
tightening torques.

5. Connect external control device to the two 

TK

 motor

terminals of the terminal block. Observe the tightening
torques.

External control devices

EZR:

 The fan must be connected to a motor protection

switch 

(e.g. MVE 10-1)

 or the control circuit of a contactor

control (connection terminals potential-free). 

NOTICE:

MVE 10-1 not

 

permitted 

for 

EZR 25/4 D

EZR 30/6 B

 or 

EZR

35/6 B

.

DZR (Standard):

 The fan must be connected to a motor

protection switch 

(e.g. MV 25-1)

 or the control circuit of a

contactor control (connection terminals potential-free).

DZR 25/4 D and pole-changeable DZR:

 Install thermal mo-

tor protection for these fans. The usage temperatures may
not be exceeded. On 

pole-changeable DZRs

, use an op-

tional pole-changing switch, e.g. 

P1

 or 

WP1

, to switch the

speeds.

1. Fit optional on/off switch.

2. Connect optional accessory components (speed con-

troller, 5-step transformer).

Speed controller

Use a speed controller for stepless control of 

EZR fans

. For

suitable speed controller → 

www.maico-ventil-

atoren.com

.

The technology used in the phase angle controller may
cause humming noises.

NOTICE The fan will stop and suffer functional problems
if the output voltage on the speed controller is too low.

Observe information in the speed controller operating in-
structions. Always set the minimum speed on the speed
controller such that the fan motor starts up again after
power failure.

5-step transformer

Use a 5-step transformer to adjust the speed of the 

EZR/

DZR

 fans in steps. For matching 

TR

 5-step transformer →

www.maico-ventilatoren.com

.

1. Fit terminal box cover. Ensure that there are no dirt

particles in the terminal box and that the seal of the
terminal box cover has close contact all the way around
the terminal box. Observe the tightening torques.

2. Check seal integrity of terminal box.

3. With protection class I, check the connection of the PE

conductor.

10 Commissioning

1. Check that all screw connections are tight.

2. Ensure that the air can flow unhindered and that there

are no foreign bodies in the air duct.

3. Check that connection data matches the technical data

on the fan (→ rating plate).

4. Run function test. Check and ensure the direction of ro-

tation/air flow direction and smooth running of the im-
peller.

11 Operation

The fan is switched on or off with a switch that is to be
provided by the customer. Ensure sufficient supply air dur-
ing operation.

Содержание EZR Series

Страница 1: ...bsanleitung separates Sicher heitshinweisblatt f r Industrieventilatoren 3 Bestimmungsgem e Verwendung EZR DZR Rohrventilatoren dienen zur Ent oder Bel ftung in h uslichen oder gewerblichen Bereichen...

Страница 2: ...lich ein Schutzgitter SG als Ber hrungs und Einsaugschutz anbringen 8 Geeignetes Isolations und Schalld mmungsmaterial anbringen 9 2 Elektrischer Anschluss ACHTUNG Ger tebesch digung bei Kurzschluss N...

Страница 3: ...e grenzer abgek hlt sind Die Abk hlzeit kann bis zu 30 Minuten betragen Erst dann den Ventilator wieder einschalten Ventilator schaltet nicht ein Fl gelrad dreht sich nicht Fl gelrad pr fen Sicherstel...

Страница 4: ...s separate safety in struction sheet for industrial fans 3 Intended use EZR DZR duct fans are used for air extraction or ventila tion in domestic or commercial areas Example Changing rooms foremen s o...

Страница 5: ...Risk of damage to unit in the event of short cir cuits Insulate any unnecessary cable cores Make sure to connect the fan to an external control device with automatic latching switch off The control de...

Страница 6: ...heck the fan for unusual noises during oper ation Malfunction Cause measures Deposits on the impeller and in the housing caused by dust in the air Operation without air filter Install air filter in du...

Страница 7: ...rit s pa r e pour les ventilateurs industriels 3 Utilisation conforme Les ventilateurs pour gaine ronde EZR DZR sont utilis s pour l vacuation et l insufflation d air dans les zones do mestiques ou co...

Страница 8: ...h it 7 En cas d aspiration libre ajouter une grille de protec tion SG contre les contacts et les risques d aspiration 8 Poser des mat riaux d isolation thermique et phonique adapt s 9 2 Branchement le...

Страница 9: ...e temp rature Le temps de refroidissement peut at teindre jusqu 30 minutes Le ventilateur peut alors tre remis en marche Le ventilateur ne se met pas en marche L h lice ne tourne pas V rifier l h lice...

Страница 10: ...uton Arr t S2 bouton Marche Q1 contacteur US 16 2 EZR 25 2 B Mit Sch tzschaltung selbsthaltend With contactor switching latched Avec circuit de contacteurs auto maintien S1 Aus Taster S2 Ein Taster Q1...

Страница 11: ...B Mit 5 Stufentransformator TRE With TRE 5 step transformer Avec transformateur 5 plots TRE S1 Aus Taster S2 Ein Taster Q1 Sch tz US 16 S1 Off button S2 On button Q1 US 16 contactor S1 bouton Arr t S2...

Страница 12: ...hzahlsteller STX STSX und Motorschutzschalter MVE 10 1 With STX STSX speed controller and MVE 10 1 motor pro tection switch Avec r gulateur de vitesse STX STSX et disjoncteur mo teur MVE 10 1 11 EZR B...

Страница 13: ...ator TR With MV 25 1 motor protection switch and TR 5 step transformer Avec disjoncteur moteur MV 25 1 et transformateur 5 plots TR 3 DZR B polumschaltbar pole changeable in version de polarit Polumsc...

Страница 14: ...mbH I Steinbeisstr 20 I 78056 Villingen Schwenningen I Germany I www maico ventilatoren com I Service 49 7720 6940 I info maico de 0185 0928 0006_RLF 9_05 23_DSW AS 5 DZR 25 4 D Mit 5 Stufentransforma...

Отзывы: