10. Electrical connection │ UK 

 

17 

3.  Transport unit to installation location and 

deposit there. Observe Chapter 7.1. 

4.  Mount pre-fitted fan unit with mounting foot 

to wall, ceiling or bracket. Mounting 
material of the sufficient size should be 
provided by the customer. 

5.  Lay folded spiral-seams ducts flush 

against the fan on the inlet and outlet side. 
Observe spacing for flexible cuffs or 
flexible couplings (types EL../ELA..). 

6.  Securely screw folded spiral-seams ducts 

down to fan flange bores with all screws 
using flexible cuffs or flexible couplings 
(types EL../ELA..). Ensure seal integrity. 

7.  With a free inlet, also fit a protective grille 

(type SG) as protection against accidental 
contact and drawing in. 

8.  Fit suitable insulation and sound-

deadening material. 

 

10. Electrical connection 

 

NOTICE

 

Risk of damage to unit in the event of 
short-circuits.

 

Insulate any unnecessary cable cores. 

 

 

 

Important notes

 

●  Always note the relevant specifications  

for electrical installations and when fitting 
equipment. In Germany, observe DIN  
VDE 0100 and the corresponding parts  
in particular. 

●  The fan has to be connected to an 

external control device with automatic self-
holding switch-off 

 Chapter 4.3 Thermal 

overload protection

. The control device 

must not switch on again automatically 
after being tripped. 

●  Pole-changeable motors with speed ratios 

of 8/4 or 4/2 have a Dahlander pole-
changing circuit. 

●  Reverse in air flow direction for DZR units 

with reverse wiring of external conductor 
L1 and L2. 

●  Operation with 

frequency converters

 is 

only admitted if factory is consulted. 
Feasibility must be checked in each case. 

 

10.1 Fan connection 

Prescribed tightening torques 

Component 

Tightening 
torque 

Terminal box cover M4 
stainless steel cylinder head 
screws 

1.0 Nm

 

Mantle terminal M7 x 0.75 mm 

0.7 Nm

 

Motor terminals TK 

0.7 Nm 

 

1.  Switch off mains fuse and prevent from 

being started up again. Attach warning sign. 

2.  Remove the terminal box cover. 
3.  Pierce cable grommet in terminal box [7] 

with a nozzle pin. Note cable diameter. 

4.  Guide the power cable into the terminal 

box such that the cable grommet fits 
around the cable sheathing completely. 
Have customer seal cable grommet if 
required. 

5.  Wire fan to the terminal block according to 

the wiring diagram (

 Chapter 17). Note 

tightening torques. 

6.  Connect external control device to the two 

motor terminals TK of the terminal block. 
Note tightening torques. 

7.  Install thermal motor protection for pole-

changeable units or DZR 25/4 D. The 
usage temperatures may not be exceeded. 

8.  Fit optional on/off switch. 
9.  Connect optional accessory components 

(speed controller, 5-step transformer)  

 Chapter 10.2 or 10.3. 

10. Fit terminal box cover. Ensure that there 

are no dirt particles in the terminal box and 
that the seal of the terminal box cover has 
close contact all the way around the 
terminal box. Note tightening torques. 
Check seal integrity of terminal box. 

11. With protection class I, check the connec-

tion of the PE conductor. 

i

Содержание EZR B Series

Страница 1: ...ung Axial Rohrventilatoren Mounting and Operating instructions Axial duct fans Instructions de montage et Mode d emploi Ventilateurs de gaines h lico des EZR B DZR B EZR D DZR D www maico ventilatoren...

Страница 2: ...ing diagrams Page 30 Scope of delivery Duct fan EZR B DZR B EZR D or DZR D Cable grommets in terminal box Capacitor for EZR units in terminal box These mounting and operating instructions Instructions...

Страница 3: ...A B...

Страница 4: ...rofachkraft vorgenommen werden Sie sind eine Elektrofachkraft wenn Sie aufgrund Ihrer fachlichen Ausbildung Schulung und Erfahrung die einschl gigen Normen und Richtlinien kennen die elektrischen Ansc...

Страница 5: ...ung dieser Stoffe verwenden Explosionsf hige Gase und St ube k nnen entz ndet werden und zu schweren Explosionen oder Brand f hren Ventilator auf keinen Fall in explo sionsf higer Atmosph re einsetzen...

Страница 6: ...en die Leiter ggf durch eine 2 Person zu sichern Sorgen Sie daf r dass Sie sicher stehen und sich niemand unterhalb des Ger tes aufh lt Hohe Ger uschemissionen in der N he des Ventilators Verwenden Si...

Страница 7: ...fen Schutzleiterdurchgang am Geh use pr fen Ger t kann auch im Stillstand unter Spannung stehen und durch Sensorik Zeitverz gerung Feuchte etc oder dem Thermoschalter in der Motorwicklung automatisch...

Страница 8: ...nicht geeignet f r EZR 25 4 D EZR 30 6 B und EZR 35 6 B Ger te DZR Die Anschl sse sind potentialfrei auf Klemmen gef hrt und m ssen an einem Motorvollschutzschalter z B MV 25 oder dem Steuerstromkreis...

Страница 9: ...ngen mit zur Ger tetype Nennweite passenden Wickelfalzrohren 250 bis 600 fest verlegter elektrischer Zuleitung einer Installation an Wand Decke oder Konsole mit ausreichender Tragf higkeit Einbau mit...

Страница 10: ...ch nach dem Ausl sen nicht selbstst ndig wieder einschalten Polumschaltbare Motoren mit Drehzahl verh ltnissen von 8 4 oder 4 2 sind im Dahlanderprinzip geschaltet F rderrichtungsumkehr bei DZR Ger te...

Страница 11: ...mtliche Schraubenverbindungen auf festen Sitz pr fen 3 Sicherstellen dass die Luft ungehindert str men kann und sich keine Fremdk rper im Luftkanal befinden 4 Anschlussdaten mit den technische Daten...

Страница 12: ...z trennen ein Wiedereinschalt Verbotsschild anbringen und Fehlerursache von einer Elektrofachkraft ermitteln lassen Bei wiederkehrenden St rungen das Ger t zur Reparatur in unser Werk schicken 14 Ersa...

Страница 13: ...u are deemed a trained electrician if you are familiar with the relevant standards and guidelines can competently and safely connect units to an electrical power supply in line with the attached wirin...

Страница 14: ...s may ignite and cause serious explosions or fire Never use fan unit in an explosive atmos phere risk of explosion Explosive gases and dusts may ignite and cause serious explosions or fire Never use f...

Страница 15: ...ers Stability should be ensured if necessary have the ladders steadied by a 2nd person Ensure that you are standing securely and cannot lose your balance and that there is no one under the unit High n...

Страница 16: ...lass I connect the PE conductor and check the connection Check protective conductor opening on housing Unit may also be energized even when at a standstill and may be switched on automa tically by sen...

Страница 17: ...circuit The MVE 10 is not suitable for EZR 25 4 D EZR 30 6 B and EZR 35 6 B units DZR Potential free terminal connections which must be connected to e g an MV 25 motor protection switch or the control...

Страница 18: ...s 250 to 600 to suit the unit type nominal size permanent electrical supply cable installation on a wall ceiling or bracket of sufficient load bearing capacity installation with flexible cuffs and fle...

Страница 19: ...circuit Reverse in air flow direction for DZR units with reverse wiring of external conductor L1 and L2 Operation with frequency converters is only admitted if factory is consulted Feasibility must be...

Страница 20: ...ns quietly and ensure if necessary 7 Switch off unit 12 Cleaning maintenance Cleaning Before cleaning switch off mains fuse secure against being accidentally switched back on and position a warning si...

Страница 21: ...Only use original spare parts When ordering spare parts please provide the following details 1 Print no 0185 0928 0004 of these instructions 2 Rating plate no rating plate on unit or title page 3 Ite...

Страница 22: ...tre ex cut s que par des lectriciens qualifi s On entend par lectricien qualifi une personne qui par son apprentissage sa formation et son exp rience conna t les normes et directives en vigueur est ca...

Страница 23: ...e jamais utiliser le ventilateur dans une atmosph re explosive risque d explosion Des gaz et poussi res explosifs risquent de s enflammer et de provoquer une grave explosion ou un incendie Ne jamais u...

Страница 24: ...chelles appropri s Assurer la stabilit le cas ch ant faire appel une 2 me personne pour maintenir l chelle Veiller avoir une position stable et ce que personne ne s journe sous l appareil missions so...

Страница 25: ...ble Le couvercle de bornier doit tre pos correctement de mani re ce que le joint qui l entoure repose compl tement sur le bornier Type de protection IP 54 IP 55 assur uniquement avec montage horizonta...

Страница 26: ...e en cas de surcharge surchauffe Exception appareils inversion de la polarit et DZR 25 4 D Avant sa remise en service le ventilateur doit rester l arr t jusqu refroidissement du moteur et du limiteur...

Страница 27: ...transport Il est interdit toute personne de s journer sous des charges en suspens PRUDENCE Risque de coupure par les tranchants des t les du bo tier Porter des gants de protection ATTENTION Endommagem...

Страница 28: ...r le site 5 Du c t air aspir et air comprim poser les tuyaux agraf s en spirale fleur du ventilateur Respecter les carts pour les manchettes flexibles ou les manchettes de raccordement flexibles types...

Страница 29: ...tesse transformateur 5 plots Chapitre 10 2 ou 10 3 10 Poser le couvercle du bornier Veiller la propret du bornier et l tanch it du couvercle de bornier qui doit reposer en affleurement avec le bornier...

Страница 30: ...ruits atypiques D tection d erreurs et r parations uniquement par des lectriciens professionnels Dysfonction nement Cause mesure Le ventilateur ne se met pas en marche Pas de tension du secteur Contr...

Страница 31: ...Fax 49 7720 694 175 Courriel ersatzteilservice maico de 15 D montage Seul un lectricien qualifi peut se charger du d montage 1 D connecter le fusible secteur s curiser et apposer un panneau d avertiss...

Страница 32: ...er STX STSX With STX STSX speed controller Avec variateur de vitesse STX STSX EZR B EZR D S1 Aus Taster Off switch Bouton d arr t S2 Ein Taster On switch Bouton de marche Q1 Sch tz US 16 Contactor US...

Страница 33: ...vec disjoncteur protecteur de moteur MVE 10 1U 1V1W 1U 1V1W M 1 L N TKTK TKTK S2 S1 Q1 L N PE 3 2 1 TRE 1 2 3 EZR B EZR D 1U 1V1W 1U 1V1W M 1 L N TKTK TKTK S2 S1 Q1 L N PE 3 2 1 TRE 1 2 3 EZR 25 2B S1...

Страница 34: ...r protection switch Avec variateur de vitesse STX STSX et disjoncteur protecteur de moteur MVE 10 EZR 25 2 B Mit Drehzahlsteller STX STSX und Motorschutzschalter MVE 10 With STX STSX speed controller...

Страница 35: ...ransformator TRE und Motorschutzschalter MVE 10 With TRE 5 step transformer and MVE 10 motor protection switch Avec transformateur de tension 5 plots TRE et disjoncteur protecteur de moteur MVE 10 1U...

Страница 36: ...ZR B Mit Motorschutzschalter MV 25 und 5 Stufentransformator TR With MV 25 motor protection switch and TR 5 step transformer Avec disjoncteur protecteur de moteur MV 25 et transformateur de tension 5...

Страница 37: ...with Dahlander circuit With MV25 motor protection switch inversion de la polarit 2 vitesse de rotation avec commutation Dahlander Avec disjoncteur protecteur de moteur 1U 1V 1W 1U 1V 1W TKTK TKTK M 3...

Страница 38: ...formator TR 0 4 With MV motor protection switch and 5 step transformer TR 0 4 Avec disjoncteur protecteur de moteur MV et transformateur de tension 5 plots TR 0 4 1 2 3 1 2 3 3 M DZR25 4D L1 L2 L3 PE...

Отзывы: