UK │ 10. Electrical connection 

 

 

20 

5.  Run function test. Check that the impeller 

runs quietly and ensure if necessary. It is 

also important that the air can flow 

unhindered. 

6.  Switch off unit. 
 

11. Cleaning, Maintenance 

Cleaning and maintenance only permissible 

when carried out by trained specialists. 

 

DANGER 

Danger to life from electric shock.  

Before cleaning or maintenance work, 

switch the fan off with the service switch 

(position “off”) and secure it against being 

accidentally switched back on. 

 

 

CAUTION 

Regularly clean the fan. The operator 

should determine the cleaning intervals – 

the frequency depends on ambient 

conditions and anticipated impairments. 

 

11.1 Cleaning 

1.  Move service switch to the "Off" position 

and protect against switching back on 

again. 

2.  If required, clean the fan with a dry cloth. 

 

11.2 Maintenance 

1.  EZD-/DZD units require no maintenance. 

Despite this, check the unit from time to 

time for bearing noise, damage and 

disproportionate vibration. 

 

DANGER 

Danger of injury from rotating impeller 

after switching off. 

Switch service switch 

to "Off" position before removing the roof 

cowl. Wait until the impeller is stationary. 

 

2.  If necessary, clean the unit of dirt/foreign 

particles as described above. Never use 

water or a high-pressure cleaner on the 

interior. 

12. Fault rectification 

Check whether the thermal motor protection 

(PTC thermistor triggering device) has 

tripped. Once the motor protection has  

cooled down, switch the unit on and check  

for unusual noise.  

 

Fault finding and repairs only permissible 

when carried out by trained specialists. 

 

Fault

 

Cause, measure

 

Fan does not 

switch on. 

No mains voltage. 

Check whether the mains 

fuse has failed. Switch on  

if necessary.

 

If necessary, also check  

the service switch. 

Motor’s  

thermal 

overload 

protection 

switches the  

fan off. 

Motor too hot. 

Leave the unit switched off 

until the motor and the 

temperature limiter cool 

down. It may take 

up to  

30 minutes

 to cool down. 

Only then, switch the unit 

back on. 

Fan does not 

switch on. 

Impeller is blocked. 

Check impeller and clean if 

necessary. 

 

Deposits on the 

impeller and in 

the housing 

caused by dust 

in the air. 

Install an air filter in the duct 

system. 

Under no circum-

stances

 should the inside 

of the unit be cleaned with 

water or a high-pressure 

cleaner. 

Impeller not 

turning. 

Switch off unit. Ensure that 

the impeller is not blocked 

by foreign bodies. 

 

 

If the fault still continues or occurs 

again, disconnect the fan from the 

power supply at all poles. 
Let a certified electrician determine 

the cause of the fault and eliminate it. 

 

Содержание EZD Series

Страница 1: ...instructions Axial roof fans Instructions de montage et Mode d emploi Tourelles h lico des EZD 25 4 E EZD 25 4 D EZD 25 2 B EZD 30 B EZD 35 B EZD 40 B EZD 50 B EZD 60 B DZD 25 4 D DZD 25 2 B DZD 30 B...

Страница 2: ...age 12 Wiring diagrams Page 33 Scope of delivery Axial roof fan with connection cable and terminal box Terminal block cable grommet capacitor EZD unit type in terminal box Mounting and operating instr...

Страница 3: ...A...

Страница 4: ...mischer berlastungsschutz 6 5 Bedienung Ein Ausschalten 6 6 Technische Daten 7 7 Transport Lagerung 7 7 1 Transport 7 7 2 Lagerung 7 8 Montagevorbereitungen 7 9 Montage 8 10 Elektrischer Anschluss 8 1...

Страница 5: ...ISO 13857 zu l ssig zum Beispiel mit Maico Schutzgitter SG EZD und DZD sind Dachventilatoren f r den haushalts hnlichen und leichten gewerblichen Einsatz Eine andere oder dar ber hinaus gehende Benut...

Страница 6: ...erden wenn der Ber hrungsschutz des Fl gelrades gem DIN EN ISO 13857 gew hrleistet ist Verletzungs und Gesundheitsgefahr bei Ver nderungen oder Umbauten oder bei Einsatz von nicht zugelassenen Kompone...

Страница 7: ...gen Bei der Elektroinstallation die geltenden Vorschriften beachten z B DIN EN 50110 1 in Deutschland insbesondere VDE 0100 mit den entsprechenden Teilen Am Montageort unbedingt einen Repara turschalt...

Страница 8: ...rwahrung Volumenstrom gegen ber Bemessungs betrieb um ca 35 reduziert Blickrichtung von Dachverwahrung 14 auf Fl gelrad 10 4 3 Thermischer berlastungsschutz EZD E EZD D und EZD B sind serienm ig mit e...

Страница 9: ...tten verwenden Seile oder Ketten nur an den beiden Transport sen 3 befestigen Wenn m glich Ger t mit einem Kran am Aufstellungsort auf dem Dach absetzen Bei unsachgem em Transport ber nimmt Maico kein...

Страница 10: ...d mmmaterial anbringen 4 Bei freier Ansaugung von unten am Ger t ein Schutzgitter Type SG als Ber hrungs und Einsaugschutz anbringen 5 Ger t absetzen und fest mit dem Dach Dachsockel verschrauben Ansc...

Страница 11: ...bauseitig abdichten 6 Netzanschluss an der Klemmenleiste ge m Schaltbild Kapitel 16 vornehmen Anzugsmoment der Schrauben beachten 7 Thermischen berlastungsschutz Kap 4 3 anschlie en Anzugsmoment beach...

Страница 12: ...en Ventilator bei Bedarf mit einem trockenen Tuch 11 2 Wartung 1 EZD DZD Ger te sind wartungsfrei Pr fen Sie das Ger t dennoch von Zeit zu Zeit auf Lagerger usche Besch digungen und unverh ltnism ige...

Страница 13: ...ile sind in Kapitel 3 1 fettgedruckt Geben Sie bei Bestellungen bitte an 1 Druck Nr der Anleitung 0185 0089 0002 2 Produktionsdatum siehe Stempel auf Geh use 13 z B 039208 3 Nr des Typenschilds S1 und...

Страница 14: ...Transportation storage 17 7 1 Transport 17 7 2 Storage 17 8 Installation preparations 17 9 Installation 18 10 Electrical connection 18 10 1 Fan connection 19 10 2 EZD units Operation with speed contr...

Страница 15: ...ed These prevent the transmission of vibrations to the duct system With a free inlet operation is only permit ted with protection against accidental contact according to EN ISO 13857 for example with...

Страница 16: ...health risk in the event of changes or modifications or if components which are not permitted are used The unit may only be operated with original components Changes and modifications are not permitt...

Страница 17: ...ticularly VDE 0100 with the corresponding parts A service switch must be fitted at the installation location so that the unit can be completely disconnected from the power supply on site for cleaning...

Страница 18: ...oof cowl roof flashing Volumetric flow reduced by approx 35 compared with measuring mode Looking roof flashing 14 to impeller 10 4 3 Thermal overload protection EZD E EZD D and EZD B are equipped with...

Страница 19: ...of Maico accepts no indemnification or warranty claims in the event of improper transport 7 2 Storage Only store fan horizontally in a suitable dry room ambient temperature 10 to 60 C Before installin...

Страница 20: ...olded spiral seams ducts flush against the fan on the suction side Observe spacing for flexible cuffs or flexible couplings types EL ELA 2 Secure folded spiral seams ducts to fan with flexible cuffs o...

Страница 21: ...tening torque of screws 8 Fit service switch HS 3 catalogue Internet near unit 9 Fit an On Off switch provided by the customer 10 Connect optional accessory components Chapter 10 2 or 10 3 NOTICE Unit...

Страница 22: ...dirt foreign particles as described above Never use water or a high pressure cleaner on the interior 12 Fault rectification Check whether the thermal motor protection PTC thermistor triggering device...

Страница 23: ...beisstra e 20 78056 Villingen Schwenningen Germany Tel 49 7720 6940 Fax 49 7720 694 175 E mail ersatzteilservice maico de 14 Dismantling Dismantling may only be undertaken by a trained electrician 15...

Страница 24: ...7 6 Caract ristiques techniques 27 7 Transport Stockage 27 7 1 Transport 27 7 2 Stockage 28 8 Pr paratifs de montage 28 9 Montage 28 10 Branchement lectrique 29 10 1 Branchement du ventilateur 30 10 2...

Страница 25: ...onduits des tu yaux agraf s manchettes de raccordement flexibles sont prescrits Ceux ci emp chent la transmission des vibrations au syst me gaine ronde Dans le cas d une aspiration l air libre le fonc...

Страница 26: ...blessure par rotation de l h lice Les cheveux v tements bijoux etc peuvent tre happ s par le ventilateur si vous vous tenez trop pr s de l appareil Pour viter ces dangers gardez une distance suffisan...

Страница 27: ...travailler sur le ventilateur couper tous les circuits d alimentation lectrique couper le fusible secteur le s curiser contre toute remise en service intempestive et apposer un panneau d avertissement...

Страница 28: ...1 Ex cutions EZD 25 4 D et EZD B Mod le monophas courant alternatif avec moteur condensateur Pour la ventilation ou l vacuation d air interrupteur s par r versible Soufflant dans le sens horizontal V...

Страница 29: ...nctionnement pr voir une arriv e d air suffisante Interrupteur de r paration sur le lieu d installation lors des travaux de nettoyage d entretien ou de r paration r gler l interrupteur de r paration s...

Страница 30: ...it l aide d une grue situ e sur le lieu d installation Fixer le c ble secteur sur le lieu d installation Veiller ce que le support soit bien adapt et plan Utiliser des mat riaux d isolation thermique...

Страница 31: ...n thermique et phonique adapt s 10 Branchement lectrique ATTENTION Risque d endommagement de l appareil en cas de court circuit Isoler les conducteurs non utilis s Remarques importantes Lors de l inst...

Страница 32: ...e la r glette de bornier Respecter le couple de serrage des vis 8 Poser l interrupteur de r paration HS 3 Catalogue Internet proximit de l appareil 9 Poser un interrupteur Marche Arr t fourni par le c...

Страница 33: ...l interrupteur de r paration position Arr t et s curiser contre toute remise en service PRUDENCE Nettoyez r guli rement le ventilateur C est l exploitant qu il revient de d finir la fr quence des inte...

Страница 34: ...ur haute pression L h lice ne tourne pas Mettre l appareil l arr t S assurer que l h lice n est pas bloqu e par un corps tranger Si l anomalie persiste ou se r p te couper le ventilateur du secteur su...

Страница 35: ...tion Standard Rotation gauche vacuation d air Standard EZD B Rechtslauf Bel ftung Rotation clockwise ventilation Rotation droite insufflation EZD B mit Drehzahlsteller ST STU STS with speed controller...

Страница 36: ...UWK 1 with speed controller STU and UWK 1 avec variateur de vitesse STU et UWK 1 EZD D Linkslauf Entl ftung Standard Rotation ccw air extraction Standard Rotation gauche vacuation d air Standard EZD 2...

Страница 37: ...zahl Rotation ccw air extraction Standard 1 speed Rotation gauche vacuation d air Standard 1 vitesse F r Rechtslauf am Ventilator anschluss 2 Phasen tauschen Replace 2 phases for clockwise rotation on...

Страница 38: ...sen tauschen Replace 2 phases for clockwise rotation on fan connection Pour la rotation droite changer 2 phases au branchement lectrique DZD B Linkslauf Entl ftung Standard mit 5 Stufentransformator T...

Отзывы: