9 Electrical connection and installation of the fan insert

6

3. Place the seal, included in the scope of deliv-

ery, on the housing floor. When doing so, pay
attention to the guide edges of the seal.

4. Make the electrical connection: 

Electrical con-

nection and installation of the fan insert
[

}

 6]

.

9 Electrical connection and install-
ation of the fan insert

9.1 Electrical connection of the fan
insert

ER EC RF17 may only be connected accord-
ing to the wiring diagrams:

 

Wiring diagrams

[

}

 8]

.

To prevent the unit and/or electric components
from malfunctioning as a result of reverse polarity
voltages and induction (incorrect ignition or glow-
ing/flaring of LED, energy-saving or neon lamps),
the unit and electric components connected in
parallel, such as room lighting, should be connec-
ted via a double-pole switch.

 DANGER Danger to life from electric

shock.

Prior to accessing the connection terminals,
switch off all supply circuits. Switch off mains
fuse, secure against being accidentally switched
back on and position a visible warning sign.

 DANGER Danger to life from electric

shock/The unit will be damaged if installed in-
correctly with too long a power cable.

If the cable feed is too long inside the housing,
the fan insert cannot be installed correctly. The
power cable may be damaged when inserting the
fan unit.
Do not cut the power cable inside the housing too
short.

 Risk of damage to unit in the event of

short-circuits.

→ Cut off and insulate PE conductor and indi-
vidual cable cores that are not required.
Always note the relevant specifications for elec-
trical installations and when fitting equipment. In
Germany, observe DIN VDE 0100 and the corres-
ponding parts in particular.

• Take ambient conditions and technical data into

account.

• Prior to accessing the connection terminals,

switch off all supply circuits. Switch off mains
fuse, secure against being accidentally
switched back on and position a visible warning
sign.

• Cut off and insulate PE conductor and indi-

vidual cable cores that are not required.

• Remove power cable’s sheathing and cut to

length.

• Wire power cable to the terminal box according

to the wiring diagram.

• The degree of protection is only guaranteed:

• for intended installation;

• if the power cable is correctly guided through

the intended cable grommet, if fan unit is cor-
rectly engaged in ER-UP housing and if cover
is closed and engaged.

• Observe permitted duct cross-section of max.

1.5 mm².

Close the fan insert using the adapter board and
the terminals in accordance with the desired con-
trol variant. To do so, observe the wiring dia-
grams: 

Wiring diagrams [

}

 8]

.

Содержание ER EC RF17

Страница 1: ...Installation and operating instructions ER EC flush mounted exhaust air systems according to DIN 18017 3 ER EC RF17 www maico ventilatoren com...

Страница 2: ...ty instructions for electrics 5 7 Technical data 5 8 Preparation for installation 5 9 Electrical connection and installation of the fan insert 6 9 1 Electrical connection of the fan in sert 6 9 2 Inst...

Страница 3: ...le operation The unit must not be used in the following situations under any circumstances DANGER Risk of combustion fire from flammable materials liquids or gases in the vicinity of the unit Do not p...

Страница 4: ...e are no air filters Heavily soiled or moist air filters can accumulate harmful substances mould germs etc This may also happen if the unit is shut down for an extended period If the air filter is mis...

Страница 5: ...J cables depending on the unit variant 3 x 1 5 mm or 5 x 1 5 mm Units may only be operated using the voltage and frequency shown on the rating plate Unit may be energized even when at a standstill an...

Страница 6: ...de the housing the fan insert cannot be installed correctly The power cable may be damaged when inserting the fan unit Do not cut the power cable inside the housing too short Risk of damage to unit in...

Страница 7: ...n angle 1 Mount the fixing cover included in the scope of delivery at the bottom left with the respect ive fillister head screw 2 For ER A continue with step 3 For ER AK ER AH ER AB plug cover s flat...

Страница 8: ...and base load can be switched Please tick the connection variant Nominal load switchable with 2 cable cores Base load switchable with 2 cable cores If the units are connected with 2 cable cores nomina...

Страница 9: ...Notes...

Страница 10: ......

Страница 11: ......

Страница 12: ...Maico Elektroapparate Fabrik GmbH Steinbeisstr 20 78056 Villingen Schwenningen Deutschland Service 49 7720 6940 info maico de D01 21_EN_AS AV...

Отзывы: