Maico ECA 100 K SERIES Скачать руководство пользователя страница 7

5

Installation

For minimum spacing to wall and ceiling, please
refer to Figure 1A.

In order to stop the impeller [5] catching, don’t
install the housing [1] crookedly or under tension.

VZ, VZC, I and F fans: Board components [2] are
sensitive to electro-static discharge. Avoid direct
contact with the components/contact areas in
question.

Protection class is only guaranteed if the surface
or flush mounted cabling is inserted into the
housing seals correctly (

round holes, no slots

).

Otherwise the guarantee is invalidated.

For installations with FE 100 window installation
kit please take note of the extra instructions
included.

Figure 1: Wall installation
A

Prepare the corresponding hole in the wall. Lay
the cabling.

B

Fix the fan with corresponding screws (to be
supplied by the customer).

C

Surface installation: Cut a round hole (not a slit)
in the seal and connect the power cable as
shown in the wiring diagram.

D

Flush installation: Cut a round hole (not a slit) in
the seal and connect the power cable as shown
in the wiring diagram.

E

Press the cover [8] squarely onto the housing
[1] until it clicks into place. Don’t bend it.

Figure 2: Ceiling installation

: See Wall installation

Figure 3: Shaft installation

: See Wall installation

Please note: Not suitable for single ventilation
equipment, according to DIN 18017

Figure 4: Ducting installation

: See Wall installation

Please note: Always snap off both spring-hooks
when installing in flexible ducting. Fix fan with screws
(to be supplied by the customer)

Figure 5: Dismantling

: Press and release locking

hooks with a screwdriver. Pull the cover straight off

ECA boards [2] – Settings

Standard model

Variable speed setting with base board [2.1]

VZ model with time-delay switch

With VZ 6 board [2.2] and safety cover; single speed
only. Start delay and overrun time fixed at approx.
50 seconds and approx. 6 minutes respectively.

VZC model with settable time delay switch

With VZ 24 C board [2.3] and safety cover; single
speed only. Start delay can be set with the Tv setting
screw from 0 seconds to approx. 150 seconds. The
overrun time can be set with the Tn setting screw from
1.5 to approx. 24 minutes.

I model with interval control

With VZI 10 board [2.4] and safety cover; single
speed only. Time interval can be set with the Ti setting
screw to an operating time from 1 to approx. 15 hours,
in 10 minute intervals.
With manual operating, e.g. with a light switch,  start
delay and overrun time are fixed at approx. 50 se-
conds and approx. 10 minutes respectively.

F model, with light control

With F board [2.5] and safety cover; single speed
only. Switch-on brightness min. 30 lux, switch-off
brightness (at unit) max. 0.3 lux. Start delay and
overrun time fixed at approx. 50 seconds and approx.
6 minutes respectively.
The F fan is designed for installation dark rooms with
no windows. The room must be dark for the fan to
switch off.

P model with pull-cord switch

With base board [2.1], pull-cord switch and pull-cord
(no picture). Single speed only.

24V model, with safety extra-low voltage

With base board [2.1]; single speed only. Rated
voltage 24 V, 50 Hz.

Maintenance/Cleaning

The fan does not need any maintenance. If dirty,
clean the fan with a damp cloth.
Make sure to disconnect the power supply first!

In the case of a malfunction

Check whether the motor temperature overload
protection has been activated. The fan will switch
back on automatically once it has cooled down.

Check whether the contact breaker switch is
switched off

If the malfunction continues, switch the contact
breaker switch off and contact an electrician

Technical data

Please refer to rating plate or a current catalogue.

Subject to change !

Содержание ECA 100 K SERIES

Страница 1: ...maico de ECA 100 ECA 100 K ECA 120 ECA 120 K Montage Betriebsanleitung Mounting Operating instructions Instructions de montage Mode d emploi Kleinraum Ventilator Small Room Fan A rateur pour petits lo...

Страница 2: ...8 1E 1B AP UP 1A AP 1C UP 1D...

Страница 3: ...4 5 2 3...

Страница 4: ...icherung im Sicherungskasten ausschalten Komponenten Ersatzteile Hinweis zu Ersatzteil Bestellungen Geben Sie generell die Druck Nr 0185 0984 0000 das Produktionsdatum X Stempel im Anschlussraum und d...

Страница 5: ...altverz gerung ca 50 Sekunden und Nachlaufzeit ca 6 Minuten fest eingestellt VZC Ausf hrung mit einstellbarem Verz gerungszeitschalter Mit VZ 24 C Platine 2 3 und Schutzabdeckung nicht drehzahlsteuerb...

Страница 6: ...ng replacement parts always quote the number 0185 0984 0000 the manufacturing date X stamp near the connector and the corresponding position number 1 Housing with motor 2 ECA board 2 1 Base board 2 2...

Страница 7: ...h VZ 6 board 2 2 and safety cover single speed only Start delay and overrun time fixed at approx 50 seconds and approx 6 minutes respectively VZC model with settable time delay switch With VZ 24 C boa...

Страница 8: ...l appareil tous les p les du secteur Pour ce faire arr ter le disjoncteur secteur dans la bo te fusible Composants pi ces de rechange Remarque relative aux commandes de pi ces de rechange Indiquez to...

Страница 9: ...ercle de protection vitesse de rotation non r glable Temporisation de d marrage env 50 secondes et fonctionnement par inertie d environ 6 minutes r gl s de fa on fixe Version VZC avec temporisateur r...

Страница 10: ...A 100 24 V ECA 120 24 V ECA 100 KF ECA 120 KF ECA 100 KP ECA 120 KP ECA 100 P 24 V ECA 100 KP 24 V ECA 120 P 24 V ECA 120 KP 24 V N L M 1 1 L N N L M 1 1 L N TRE 50 230 24V M 1 1 N L L N t1 t2 VZ F N...

Отзывы: