EN
25
Only lay single cable cores in the unit. To
1.
do this, remove power cable sheathing
over a length of 90 mm. Strip single cable
cores to 9 to 10 mm.
Insert housing [1] into wall breakthrough/
2.
wall sleeve and secure with two screws.
Do not insert the housing such that it is
twisted or crushed. Make sure you use
mounting material which is sized for the
purpose.
Electrically connect power cable to spring
3.
clip [11] according to connection wiring
diagram [12]
wiring diagrams in Chap. 16.
Check position of cable grommet. It must
4.
be well sealed.
Fit electronics cover.
5.
NOTICE
Danger of short-circuits and
damage to the unit. Humidity
will penetrate if electronics
cover is not positioned correctly.
Press electronics cover firmly
onto housing such that it is
sealed and flush all the way
around. Do not press the set up
button [10].
Locate the 3 locking tabs on the electronic
6.
cover over the housing cut-outs
I, II
and
III
and press the cover in, until the tabs engage.
In addition, press the electronics cover
firmly on to the housing at the points
indicated by the word "PRESS".
With RCH unit models, plug the supplied
7.
sensor [9] correctly (arrow X) into the
connector sockets.
Fit cover [6].
8.
Fit designer cover [7] (
fold-out page,
9.
Fig. B).
Install all other system components
10.
according to their mounting instructions.
8.3 Commissioning
Operation with a single fan (individual
operation)
Switch the mains fuse on.
1.
First set up the RLS RC room air control
2.
and then the radio switch and/or radio
window contacts at the fan, as described
in Chapter 9.
Set up the remaining system components.
3.
Carry out a function test with all system
4.
components.
Operation in master/slave network
Switch the mains fuse on.
1.
Set up the pre-configured RLS RC room
2.
air control at the master fan.
Set up the radio switch, radio window
3.
contacts and further slave fans at the
master fan, as described in Chapter 9.
Set up further radio switches and/or radio
4.
window contacts at the slave fans (max.
2 fans).
Carefully press the cover [6] (with designer
5.
cover [7]) onto the housing, until it locks
into the safety catches.
Carry out a function test with all system
6.
components.