8 Installation
38
Minimum wall thickness 265 mm, slide-in
module must not protrude out of wall sleeve.
The profile seal on the outside of the slide-in
module serves to fix the unit in place and
avoid air from infiltrating. The motor connec-
tion cable must not be strained when installed.
When sliding in the slide-in module, ensure
that the `Oben/Top´ sticker is facing upwards.
11.Press fan connection cable into notch (arrow)
so that it is fixed and not strained.
9
Fan connection cable
10
Plug
11
Enclosed sheet metal
12.With
PP 45 O units
(12 V DC), insert the en-
closed sheet metal in the 2 locking tabs so
that it engages. Wire connector with the 12 V
control cable of the room air control (
in appendix).
Plug connector onto the sheet metal and con-
nect it with plug.
13.For
PP 45 K units
(12 V DC) loosen the
screws of the circuit board cover, remove the
cover. Plug the fan connection cable directly
onto the circuit board. Wire the 12 V control
cable of the room air control (
board cover.
14.Attach front cover of internal housing at top in
two housing studs and swivel down until front
cover engages on locking lever.
8.4 230 V electrical connection
PP 45 RC
and
RLS 45 O
/
RLS 45 K
controls are
supplied with a 230 V mains voltage.
Note the following safety instructions.
DANGER Danger of electric shock.
Before installing the electrics, shut down all sup-
ply circuits, switch off mains fuse, secure against
being accidentally switched back on and position
a visible warning sign. During operation, the
board cover and front cover of the internal hous-
ing must be mounted.
WARNING Danger of burns/fire due to
overload caused by incorrect connection or
connecting too many units to a RLS 45 O /
RLS 45 K.
Connect units in accordance with connection dia-
gram. Observe permissible number of ventilation
units per room air control/power unit.
WARNING Danger of electric shock if the
12 V low voltage and 230 V are not disconnec-
ted or are insufficiently disconnected.
Ensure a safety distance between 230 V and 12
V cables. Ensure minimum distance of 8 mm.
Содержание DS 45 RC
Страница 2: ...Inhaltsverzeichnis Deutsch 3 English 29 Fran ais 53...
Страница 4: ...Steuerungskonzept PP 45 4 Steuerungskonzept PP 45...
Страница 5: ...Steuerungskonzept PP 45 RC PPB 30 RC 5 Steuerungskonzept PP 45 RC PPB 30 RC...
Страница 30: ...PP 45 control concept 30 PP 45 control concept...
Страница 31: ...PP 45 RC PPB 30 RC control concept 31 PP 45 RC PPB 30 RC control concept...
Страница 54: ...Concept de commande PP 45 54 Concept de commande PP 45...
Страница 55: ...Concept de commande PP 45 RC PPB 30 RC 55 Concept de commande PP 45 RC PPB 30 RC...
Страница 98: ...Produktdatenbl tter Product data sheets Fiches techniques du produit 98 PP 45 O PP 45 K mit PP 45 HYI...
Страница 99: ...Produktdatenbl tter Product data sheets Fiches techniques du produit 99 PP 45 RC...
Страница 100: ...Produktdatenbl tter Product data sheets Fiches techniques du produit 100 PP 45 RC mit PP 45 HYI...
Страница 101: ...Notizen...
Страница 102: ......
Страница 103: ......