Installation instructions 

Centrifugal roof fan 

DRD EC

 

 
 

 

Version 5 

– 05.2014 – subject to errors and alterations 

Page 6 of 8 

 

MAICO Ventilatoren · Steinbeisstrasse 20 · D-78056 VS-Schwenningen · www.maico-ventilatoren.com 

 

0

5

.1

4

_

tr

 

5  MALFUNCTIONS, CLEANING, SERVICING 

Do not carry out any repairs to the device. Always send 
the device to the manufacturer for replacement or repair. 
 

 

WARNING! 
The  motor  starts  up  automatically  again 
if  a  control  voltage  is  applied  or  speed 
setpoint is stored, e.g. following a power 
outage. 
Risk of injury! 

  Do  not  remain  in  the  hazard  area  of  the 

device. 

  Switch off the power supply when working 

on  the  machine  and  secure  against  unin-
tentional start-up. 

  Wait until the device has come to a stand-

still. 

 

 

NOTE! 

If the device has been left standing for a long-
er period, it is recommended that the device is 
started  up  for  at  least  two  hours,  to  allow  any 
condensate that may have infiltrated to evapo-
rate and the bearing to be moved. 

5.1  Malfunctions 

 

Malfunc-
tions/defec
ts 

Possible 
causes 

Possible remedy 

Motor is 
not rotat-
ing 

Mechanical 
blockage 

Switch off, isolate from 
the power supply and 
remove mechanical 
blockage. 

 

Power supply 
defective 

Check power supply, 
restore supply voltage. 

 

Faulty connec-
tion 

Adjust connection, see 
terminal assignment. 

 

Temperature 
sensor has 
responded 

Allow the motor to cool, 
find cause of the defect 
and rectify it, where 
appropriate release 
anti-pumping device. 

Impeller is 
running 
untrue

 

Imbalance in 
the moving 
parts 

Clean device. If there 
continues to be an 
imbalance after clean-
ing, replace device. 

 

Defective 
cooling 

Improve cooling, if pos-
sible. Reset by switch-
ing off the supply volt-
age for 
at least 20 s 

 

Ambient tem-
perature too 
high 

Lower ambient tem-
perature 
, if possible. 

 

Inadmissible 
operating point 

Check operating point 

 
Contact  the  manufacturer  if  you  have  further  malfunc-
tions. 

5.2  Cleaning 

 

NOTE! 

Damage  to  the  device  through  cleaning. 
Malfunction possible. 

  Do not clean the device with a water jet or 

high-pressure cleaner. 

  Do  not  use  any  acid,  alkali  cleaning 

agents  or  cleaning  agents  containing  sol-
vents. 

5.3  Maintenance

 

 

What needs to be 
checked? 

How do you check? 

Protective casing

 

Periodic visual inspec-
tion 

Check the device for damage

 

Periodic visual inspec-
tion 

Secure the device

 

Periodic visual inspec-
tion 

Secure the 
connection leads

 

Periodic visual inspec-
tion 

Secure the 
protective conductor

 

Periodic visual inspec-
tion 

Isolate the leads

 

Periodic visual inspec-
tion 

Contamination, damage, 
corrosion 

Periodic visual inspec-
tion 

 

 

6  CIRCUIT DIAGRAMS 

6.1  Wire allocation 

Termi-
nal 

Colour 

Comments 

Black 

230VAC, 50Hz 

Blue 

Neutral conductor 

PE 

Green/yello

Protective conductor 

orange 

not switched 

+10VDC 

red 

Voltage output 10VDC, max 
1.1mA, not short-circuit-
proof 

AIn1U 

yellow 

Control input 0-10VDC 

GND 

dark blue 

Control interface connection 

Tacho 

white 

Speed output 

COM 

white 

Potential-free status signal-
ling contact, opener in the 
event of fault (2A, max 
250VAC) 

NC 

white 

Potential-free status signal-
ling contact, opener in the 
event of a fault 

 

Содержание DRD EC 010

Страница 1: ...fety regulations 2 1 4 Electrical current 2 1 5 Electro magnetic radiation 2 1 6 Storage 2 1 7 Disposal 3 2 INTENDED USE 3 3 TECHNICAL DATA 3 3 1 Rated values 3 3 2 Mounting data 3 3 3 Device drawings 3 3 4 Transport and storage conditions 4 4 CONNECTION AND COMMISSIONING 4 4 1 Make mechanical connection 4 4 2 Make electrical connection 4 4 2 1 Requirements 4 4 3 Check connections 4 4 4 Switch on ...

Страница 2: ... the commercial sector The oper ator of the device is thus subject to the statutory obliga tions on occupational safety Alongside the safety regulations in these instructions the safety accident prevention and environmental safe ty regulations that are applicable for the area of use of the device must be complied with Alterations extensions or modifications are not permitted without the permission...

Страница 3: ... by the manufacturer that arise from the fan s optional equipment are de scribed in the customer specification WARNING Danger from non intended use Every application that goes beyond intended use and or other use of the device can lead to dangerous situations Therefore Use the device only for its intended pur pose Strictly comply with all information in these operating instructions Claims of any k...

Страница 4: ...ust be avoided Check the device for any transport damage Dam aged devices may no longer be mounted Mount the undamaged device on a suitable base based on its application Connect pressure line on the pressure tapping on site in the duct or pipeline 4 2 Make electrical connection DANGER Danger of lethal electrocution from elec trical current Contact with live parts poses a risk to life Switched on e...

Страница 5: ...are pre set and fastened on the bolt Their purpose is to fix the lid and may not be removed to release the mounting bracket Remove mounting bracket and lid store safely Feed cable as shown through the opening in the outer coating 1 and the cable screw fitting in the inner ring 2 Insert cable with suitable radius into the junction box 3 Connect cable cores to the appropriate terminals based on the ...

Страница 6: ...mpeller is running untrue Imbalance in the moving parts Clean device If there continues to be an imbalance after clean ing replace device Defective cooling Improve cooling if pos sible Reset by switch ing off the supply volt age for at least 20 s Ambient tem perature too high Lower ambient tem perature if possible Inadmissible operating point Check operating point Contact the manufacturer if you h...

Страница 7: ...rifugal roof fan DRD EC Version 5 05 2014 subject to errors and alterations Page 7 of 8 MAICO Ventilatoren Steinbeisstrasse 20 D 78056 VS Schwenningen www maico ventilatoren com 05 14_tr 6 2 Version with EC 3 6 3 Version with EC 010 ...

Страница 8: ...ctions Centrifugal roof fan DRD EC Version 5 05 2014 subject to errors and alterations Page 8 of 8 MAICO Ventilatoren Steinbeisstrasse 20 D 78056 VS Schwenningen www maico ventilatoren com 05 14_tr 6 4 Version with EC 230 ...