Troubleshooting
Fault
Possible cause
Action
Alarm priority
Fan is not
rotating or
stops after
a various
time.
No supply voltage present.
Check the supply voltage directly at the fan.
In case of fault check the fuses and the wiring of the
service switch.
---
Missing setpoint.
Check the setpoint and its correct polarity.
---
Missing enable signal.
Check the 24VDC between “DIN (Enable)“ and GND
clamps.
---
Internal protective feature
has tripped. (Failure can be
read out with the Software
“EC-Param”)
“Over voltage“-
Input voltage rises above the tolerance
limit of the specified line voltage.
Check main supply and fuses.
Failure resets automatically after the voltage falls un-
der the maximum limit.
C
“Locked rotor“
Check the fan impeller for overload caused by dirt or for-
eign matters and turn by hand. Check fastenings of motor
and nozzle.
Reset failure
C
“Motor phase error“
Winding interrupted, wire break.
Contact Maico support
C
“Motor over current, I Hi alarm“
Motor-side short circuit.
Contact Maico support
C
“Over temperature motor“
Check the airflow and ambient temperature for its limits.
Ensure better cooling. Check the fan impeller for overload
caused by dirt or foreign matters.
Reset failure
C
“24V supply overload“
Check current consumption of connected devices, re-
move short-circuit.
Failure resets automatically after the value falls under
the maximum limit.
C
Fan turns
but there is
no or not
enough air-
flow.
Rotation speed of the fan too
low.
Please see “fan does not run at maximum speed“.
---
Air flow interrupted.
Check duct system (e.g. suction, filter, sealing caps).
---
Calculated pressure does
not correspond to the real
value.
Check fan selection.
---
Unfavorable installation con-
ditions.
Check the installation situation.
(section 6.1)
---
Impeller is rotating in wrong
direction because of external
effects.
“Wrong rotating direction (Windmilling)“
Check installation situation, restart the air-handling unit to
stop the convers airflow.
Reset failure
NC/C