7 Mounting preparations

5

• the evaluation criteria drawn up by the respons-

ible, regional master chimney sweep are met;

• Parallel operation of air-ventilated fireplaces for

liquid or gaseous fuels and air-extracting equip-
ment can be prevented using safety devices or

• the extraction of exhaust gas from the air-ventil-

ated fireplaces is monitored by special safety
devices. The ventilation system or the fire-
places must be switched off if the equipment is
triggered.

6.3 Technical data table

Rated voltage

 Centro-

E/Centro-H

230 V

Power frequency

Centro-E/Centro-H

50 Hz/60 Hz

Degree of protection

IP X5

Protection class

Centro-E-APB

II

Centro-H-APB

II

Minimum volumetric
flow

30 m³/h

Air volume

30 / 65 m³/h

Sound pressure level

L

WA7

26 to 33 dB(A), depend-
ing on unit model

Weight

0.8 kg

For more technical data → rating plate.

For characteristic curves → 

www.maico-ventil-

atoren.com

6.4 Storage

Only store unit horizontally in a suitable, dry
room. Ambient temperature – 10 °C to + 60 °C.

Maico

 accepts no liability for corrosion damage

caused by improper storage, e.g. storage in a
damp environment.

7 Mounting preparations

 Suitable mounting material is to be

provided by the customer.

8 Installation

8.1 Installation information on flush-
mounted housing

 The installation of flush-mounted housing

and the shut-off device is described in detail in
the ER/Centro main instructions. Be sure to
proceed as described there. Also observe the
requirements in line with the approval.

8.2 Electrical connection

Centro-E and Centro-H

 The electrical connection of Centro-E and

Centro-H devices is described in detail in the
ER UP/Centro main instructions. Be sure to
proceed as described there. The electrical con-
nection must be made in accordance with the
wiring diagram.

Centro-E

Centro-H

8.3 Installation of spiral housing and
upper part of housing

 DANGER Danger to life from electric

shock.

Prior to accessing the connection terminals,
switch off all supply circuits. Switch off mains
fuse, secure against being accidentally switched
back on and position a visible warning sign.

Содержание Centro-E

Страница 1: ...Installation and operating instructions Flush mounted exhaust air elements for Centro centralised ventilation system according to DIN 18017 3 Centro M Centro E Centro H www maico ventilatoren com...

Страница 2: ...s 4 6 Technical data 4 6 1 Environmental conditions and oper ating limits 4 6 2 Regulations for operation with fire places 4 6 3 Technical data table 5 6 4 Storage 5 7 Mounting preparations 5 8 Instal...

Страница 3: ...ate in terior bathrooms toilet rooms and open plan kit chens with exterior windows storage rooms etc After completion of the interior building work the exhaust air elements are inserted into the flush...

Страница 4: ...d housing Shaft level difference according to DIN 4109 tested by IAB Oberursel The Institute for Acoustics and Building Physics in Germany Cover with exhaust air filter and time strip Air filters are...

Страница 5: ...table dry room Ambient temperature 10 C to 60 C Maico accepts no liability for corrosion damage caused by improper storage e g storage in a damp environment 7 Mounting preparations Suitable mounting m...

Страница 6: ...sk of damage if ESD sensitive com ponents on the board are touched Avoid direct touching of the components or con tact surfaces NOTICE The noise level will increase if the housing floor seal is fitted...

Страница 7: ...y first fit a spacing or wall frame 3 With second room extraction insert regulating plate below locking tabs at the side on the in take grille of the cover insert filter mat 4 Lock cover The lock must...

Страница 8: ...reference value during opera tion the newly established reference value is saved The exhaust air element then automatic ally switches back to base load operation or to Off Demand based ventilation aut...

Страница 9: ...15 minutes and resets the refer ence value Additional consumers connected to terminal 4 Damage to the unit if connected incorrectly Do not connect addi tional consumers to ter minal 4 The unit may onl...

Страница 10: ...rior to accessing the connection terminals switch off all supply circuits Switch off mains fuse secure against being accidentally switched back on and position a visible warning sign 1 Remove spiral h...

Страница 11: ...Notes...

Страница 12: ...Maico Elektroapparate Fabrik GmbH Steinbeisstr 20 78056 Villingen Schwenningen Deutschland Service 49 7720 6940 info maico de D07 21_EN_DSW AV...

Отзывы: