• Only connect the fan according to the circuit diagram/

wiring diagram. A permanent electrical installation is
mandatory. Note the voltage and frequency stated on
the rating plate. Use a mains isolation device with con-
tact openings of at least 3 mm at each pole.

• Use cables of type NYM-O or NYM-J, with 3 x 1.5 mm² or

5 x 1.5 mm², suitable for the unit type.

• The 

degree of protection

 stated on the 

rating plate

 is

only guaranteed if installation is undertaken correctly
and the connection cable is inserted correctly.

• With protection class I, connect the PE conductor and

check the connection.

• Perform a function test after completing installation,

maintenance and repair work.

• Proceed with caution in the event of a malfunction. The

fan may also be energized when at a standstill and may
be switched on automatically by sensors (time delay, hu-
midity etc.) or by the thermal switch in the motor wind-
ing. Maintenance and fault finding only permissible
when carried out by qualified electricians.

4 Intended use

AWV

 are centrifugal external wall fans with an integrated

shutter. They are used for 

air extraction

 from rooms in do-

mestic or commercial areas. Example: Machine extraction,
workplace, commercial space, fitness room, canteen, etc.

Operation of the AWV is only permissible:

• with permanent installation on a flat exterior wall with

sufficient load-bearing capacity.

• with the shutter pointing downwards (towards the

floor).

• when connected to a ventilation duct that matches the

unit variant/nominal size.

• with upstream air filter.

• with permanent electrical installation.

• with free inlet with protection against accidental contact

in accordance with EN ISO 13857, for example with 

SGR/

MGR

 protective grille.

 The connection socket is prepared on the suc-

tion side for installation in the ventilation duct. IP
X4 degree of protection when installed in ventila-
tion ducts with at least 1 m of pipe on the suction
side.

 When connecting to ducts, folded spiral-seams

ducts with flexible couplings are prescribed. These
prevent the transmission of vibrations to the duct
system.

5 Product information

• Nominal sizes DN 100 to DN 200.

• For air extraction, blowing out downwards.

• Speed controllable.

• Fan on/off with separate switch (on site).

• Centrifugal impeller with backwards curved blades.

• AC variants with capacitor motor and thermal overload

protection.

• EC variants with EC motor.

6 Installation examples

7 Unit overview

1 Base plate with 4 mounting holes

2 Cover

3 Connection socket

4 Screw + tooth lock washer (2 of each)

5 Shutter, airstream-operated

6 Protective grille

7 Terminal block

8 Capacitor

S1 Sticker: Direction of impeller rotation

S2 Sticker: Circuit diagram

L Cable feedthrough

T Rating plate

8 Technical data

Permissible airstream tem-
perature at I

max.

AWV .. 

AC

 variants

-20 °C to +40 °C. 
AWV 10: -20°C to +30°C

Permissible airstream tem-
perature at I

max.

AWV ../2 

EC

 variants

-20°C to +60°C

Rated voltage

230 V AC

Power frequency 
AWV ...
AWV ../2 EC

50 Hz
50 Hz, 60 Hz

Degree of protection

IP X4

Weight

Up to 8.3 kg, depending on
unit variant

For more technical data → rating plate.

9 Transport, storage

WARNING! Observe the enclosed safety instruction
sheet for industrial fans.

CAUTION! Wear protective gloves to prevent cuts
caused by sharp-edged housing plates.

Only store fan 

vertically

 and 

dry

 (-10 °C to +60 °C). Avoid

storage periods that are too long. Recommendation: store
for a max. of 1 year. Before installation, check that the
moving parts (impeller) can move freely.

10 Preparation for installation

• Attach wall breakthrough and, if necessary, wall sleeve.

• Lay the power cable to the installation site.

• Install ventilation ducts professionally.

• In the case of a free inlet, fit a protective grille in front of

the fan/duct system.

• Unpack the unit. Dispose of packaging material.

11 Wall mounting, electrical connection

1. Remove cover. To do this, loosen the two screws at the

bottom of the unit, swing out the cover and lift it up-
wards.

2. Guide the connection cable through one of the two

cable feedthroughs into the housing. 

ATTENTION:

 Sheet metal has sharp edges. Do not dam-

age the power cable.

Содержание AWV Series

Страница 1: ...auten oder bei Einsatz von nicht zugelassenen Komponenten Ver nderungen und Um bauten sind unzul ssig und entbinden den Hersteller von jeglicher Gew hrleistung und Haftung z B wenn das Geh use an unzu...

Страница 2: ...ch unten Richtung Boden gerichteter Verschluss klappe bei Anschluss an einer zur Ger tevariante Nennweite passenden L ftungsleitung mit vorgeschaltetem Luftfilter mit fest verlegter elektrischer Zulei...

Страница 3: ...tor wird am Bedienort mit einem Ein Aus Schalter bauseitig ein bzw ausgeschaltet W hrend des Betriebs f r ausreichend Zuluft sorgen 15 Reinigung Wartung Der Ventilator ist wartungsfrei Pr fen Sie den...

Страница 4: ...hich is not permitted Secure work areas against unauthorised entry falling and falling objects Risk of injury equipment damage if the fan or an object falls during installation removal cleaning mainte...

Страница 5: ...red on the suc tion side for installation in the ventilation duct IP X4 degree of protection when installed in ventila tion ducts with at least 1 m of pipe on the suction side When connecting to ducts...

Страница 6: ...an on off switch provided by customer Ensure sufficient supply air during operation 15 Cleaning maintenance The fan is maintenance free Nevertheless check the fan from time to time for bearing noises...

Страница 7: ...ssions sonores ou pour le d couplage acoustique Recommandation isoler les gaines rectangulaires pour assurer une tanch it suffisante la diffusion N utilisez jamais le ventilateur pour le transport des...

Страница 8: ...e l arr t le ventilateur peut tre sous tension et tre mis automatiquement en marche par les d tecteurs temporisation humidit etc ou par l interrupteur thermique dans la bobine de moteur L entretien et...

Страница 9: ...uer un test de fonctionnement Ce faisant v ri fier et s assurer que la turbine tourne sans coups L air doit pouvoir circuler librement 14 Utilisation Le ventilateur est activ d sactiv sur le lieu d ut...

Страница 10: ...ilder Circuit diagrams Sch mas de branchement AWV AWV S Mit Ein Aus Schalter With on off switch Avec interrupteur Marche Arr t AWV AWV S Mit Drehzahlsteller STX With STX speed controller Avec r gulate...

Отзывы: