AE 10/1, AE 15/1
FR
DE
UK
a danger of short-circuits/damage to the
unit if condensation builds up in the hous
-
ing.
Thermally insulate ventilation ducts
properly. Allow for a condensation drain or
condensate collector in the riser.
●
Mounting material is to be provided by the
customer.
●
Only install unit on a dry, flat surface. Any
installation position can be selected.
●
Only operate the unit when it is completely
installed.
●
Danger of electric shock.
Before accessing
the connection terminals, shut down all
supply circuits, switch off mains fuse,
secure against being accidentally switched
back on and position warning sign.
●
Only connect unit to a permanently wired
electrical installation with NYM-O or
NYM-J, 3 x 1.5 mm², cables.
●
A mains isolation device with contact
openings of at least 3 mm at each pole is
mandatory.
●
The unit may only be operated using the
voltage and frequency shown on the rating
plate.