44
UK | 10 Connections
Power consumption
(unit) at
100 Pa
counter
pressure per duct
310/410
34 ... 220 W
320/470
K/B/KB:
34 ... 220 W
320/470
ET/BET/KET/
KBET: 33 ... 215 W
170
16 ... 75 W
160 Flat
16 ... 74 W
Trio
18 ... 65 W
Weight
310/410
max. 65 kg
320/470
max. 73 kg
170
47 kg
160 Flat
28 kg
Trio
LZ, QZ AL, QZ AR: 38 kg
Trio
QD AL, QD AR: 50 kg
10 Connections
Simple control unit [1]
in solo mode (=
standard setting), without comfort control unit
(touchscreen control unit RLS T1 WS). Up to
4 more single control units can be connected
in parallel
wiring diagram, chapter 14 t o17.
Touchscreen control unit RLS T1 WS
(optional)
can be combined with up to 5 single control
units as auxiliary control units
wiring dia
-
gram, chapter 14 to 17.
310/410
320/470
160 Flat
Trio
with
multi-function contact
– Potential-free swit
-
ching contact for connecting one of the follo
-
wing components: alarm display, filter change
display, operating display, supplementary
heating, PTC heat register, external shutter,
brine EHE (unregulated pump), cooling func
-
tion
wiring diagram, chapter 14 to 17.
ModBus (optional):
Only if there is no com-
fort control unit (touchscreen control unit RLS
T1 WS) connected and the parameters have
been set with the commissioning software.
Can be combined with up to 5 single control
units as auxiliary control units
wiring dia
-
gram, chapter 19.
External sensors (optional)
wiring diagram, chapter 18
●
Humidity sensor (FFT 30 K)
●
CO
2
sensor (SKD) or
●
VOC sensor (air quality controller EAQ 10/3)
i
External sensors need a 0-10 V output
and a linear characteristic curve.
Sensors 1 and 2 are connected at terminal
block X12/sensors with 24 VDC (= standard
installation).
If there is no simple control unit connected, the
connections on terminal block X13/RLS can
be used for 2 other sensors (sensor 3 and 4,
12 VDC each). The voltage at the terminals of
sensors 1 and 2 can be used to supply sensors
3 and 4 with 24 VDC (double assignment).
EnOcean plug-in module E-SM or KNX
plug-in module K-SM (optional)
. For
recommended components
Wiring dia
-
gram, chapter 20 and Internet
Содержание 0095.0220
Страница 2: ...WS 160 Flat Kap Chap 3...
Страница 3: ...WR 310 WR 410 WS 320 WS 470 Kap Chap 3...
Страница 4: ...WS 170 Kap Chap 3...
Страница 5: ...Trio Kap Chap 3...
Страница 104: ......
Страница 105: ......
Страница 108: ......
Страница 109: ......
Страница 110: ...106...
Страница 111: ...107...