10. Failures during Operation
The failures mentioned below generate a general fault message which is available also
potential-free as break contact (voltage loss and electric break protection) for external fault
detection systems (BMS/GLT).
Agitator:
A motor overload switch monitors continuously the power device of the agitator. In case of
a failure the reason for the failure needs to be eliminated and the motor overload switch is
to be released. The text display says “Fault MOS drives”. The failure needs to be
confirmed by pushing the button “Acknowledge General Fault”.
Pump:
A motor overload switch monitors continuously the power device of the pump. In case of a
failure the reason for the failure needs to be eliminated and the motor overload switch is to
be released. The text display says “Fault MOS drives”. Then, the failure needs to be
confirmed by pushing the button “Acknowledge General Fault”.
Solenoid Valve:
The operating time of the solenoid valve is always controlled. If the switch-off signal for the
filling unit is not reached after a predefined monitoring time the system generates a
general fault and the valve is deactivated. The text display says “Filling Time too long”.
Then, the failure needs to be confirmed by pushing the button “Acknowledge General
Fault”.
Advice
If you cannot remedy a failure please contact our after-sales service.