Description:

Features Include:

Equipment Needed for Installation:

Planning for Installation:

Select ONE of the Following Thermostat Configurations:

Dimensional Drawing:

The Bi-Directional, intelligent thermostat uses wireless communication to provide quick and easy implementation of 
energy saving HVAC controls. When the thermostat receives an “occupied” signal from a switch or sensor, the user 
immediately gains full control over the HVAC settings. When the thermostat receives an “unoccupied” signal, it sets the 
room back to the preset unoccupied temperature. It is designed for use with most basic gas/electric furnace/air conditioning 
units, PTHP/PTAC systems, 4-pipe, or 2-pipe fan coil systems. 

• Compatible with key card switch, occupancy sensor, window/door sensor and other wireless transmitters. 
• Controllable through smart phone as well as VenergyUI software
• Optional humidity sensor
• Optional manual controls
• Two way communication

• Phillips Screwdriver
• Electrical Tape
• Wire Nuts

• Take a moment to prepare for installation and ensure optimal communications with other system components in the space
• Always utilize a qualified installer
• Create separation distance between interfering electronics such as fluorescent tube ends, ballasts, electronic transformers, 
and motors. Avoid mounting inside of metal enclosures. 
• Obstructions of metal, concrete and dense building materials will reduce the range. Mount higher and away from obstruc-
tions to maximize range. 

WARNING: To avoid risk of fire, shock, or death, TURN OFF POWER at circuit breaker or fuse and verify that it is OFF before 
installation begins. Make
sure that it remains OFF until installation is complete. 

NOTE: Read the WARNINGS AND CAUTIONS section before beginning these installation options. Read all steps for this 
option before taking any action to
install the thermostat.

OPTION A: Heat Pump Configuration Installation

1. If retrofitting an old thermostat, remove the old device, carefully noting the wire connections on the old unit. Record wire 
color and terminal legends (Cable wire color for Control Feed, Load Feed, Common, Auxiliary Heat, Compressor, Low Fan, 
High Fan and Reversing Valve). Refer to Table A. 

2. Install mounting bracket to the junction box with provided mounting screws. 

3. Wire thermostat according to function as shown in Figure A. 

4. Push wires into junction box. Rest bottom of thermostat on mounting tabs in mounting plate. Push top of thermostat 
towards wall and secure into place with self tapping screw. 

5. Turn power on. 

Depth = 1”