Control unit MGC mTripod
Parameterising the mTripod
3.2.2
Connection via Ethernet module EM01
Further information on the Ethernet module: Technical Manual "Ethernet
Module" (Doc.ID: 5815,0001).
For pedestrian gates with the option "Ethernet module EM01", the Ethernet
module is installed ex works.
1. Connect the EM01 Ethernet module to the customer's network via a
customer-side network cable.
2. Check whether the LEDs on the EM01 Ethernet module are flashing. If the
LEDs flash, the Ethernet module is connected correctly.
3. If necessary, set the IP address of the Ethernet module. DHCP is activated
ex works. Note the IP address.
4. Start the "MGC.Connect" programme on the laptop.
√
The MGC.Connect start view is displayed.
√
The "Configuration" window is displayed:
Fig. 4:
"EM01 configuration" window
5. Select the connection "EM01".
6. Enter the previously noted IP address of the pedestrian gate.
7. Click the "Apply" button.
√
The connection between pedestrian gate and "MGC.Connect" programme
is established.