Full Height Turnstile MPT-132
Configuring the pedestrian barrier
47
7.2.1
DIP switch block S1
DIP S1.x
Function
Description
1 Pulse
storage
When pulse storage is deactivated, the barrier is cleared via a
pulse to one of the two opening inputs. If further opening
pulses are received while the barrier is still open, they are ig-
nored.
With opening pulse storage activated, several opening pulses
can be stored. The barrier then remains open until the num-
ber of stored pulses is again zero. With each passage, the
number of stored pulses is reduced by one.
Options:
OFF: No pulse stored
ON: Up to 5 pulses stored for each rotational direction
2 Buzzer
function
The buzzer emits permanent warning sound in the following
situations:
during homing
during a passage in the wrong direction
if there is a error in the control
if the barrier is vandalised
The buzzer also emits an acknowledge sound in the following
situations:
when the lane is free for the next passage
Options
OFF: Buzzer completely switched off
ON: Buzzer switched on
3
Response after power is
restored
This option can be used to specify whether, once power has
been restored, the controller first waits for a pulse at the
"Manual reset" pulse or whether it starts to home imme-
diately.
Options
DIP S1.3
Response after power is restored
OFF Automatic
reset
ON Manual
reset