5.7.5 Torque Detection
The overtorque detection circuit activates when the motor load causes the motor current to exceed the overtorque
detection level (L06.02). When an overtorque condition is detected, alarm signals will be shown on the keypad as
well, and can be sent to a multi-function digital output. To output an overtorque detection signal, select torque
detection 1 at either of the multi-function digital outputs (H02.xx = “00B,” “017,” “10B,” or “117”).
Table 5-9: Torque Detection 1 Selection Definition
NOTE:
•
To detect overtorque/undertorque during acceleration or deceleration, set to “02” or “04” / “06” or “08”.
•
To continue operation after overtorque/undertorque detection, set to “01” or “02” / “05” or “06”. During
detection, the keypad displays an “OT1/UT1” alarm (blinking).
•
To stop after an OT1 or UT1 fault, set to “03” or “04” / “07” or “08”. During detection, the keypad displays an
“OT1/UT1” fault.
Parameter
Name
Function
Range
Default
L06.01
Torque Detect 1 Select
Activates overtorque/undertorque detection
and selects whether detection generates an
alarm or a fault
00–08
00
00 Disable
01 Overtorque At Speed Agree
(Alarm)
02 Overtorque At Run (Alarm)
03 Overtorque At Speed Agree
(Fault)
04 Overtorque At Run (Fault)
05 UT At Speed Agree (Alarm)
06 UT At Run (Alarm)
07 UT At Speed Agree (Fault)
08 UT At Run (Fault)
Setting
Description
00
Torque detection is disabled (
default
).
01
Overtorque detection is enabled whenever at the speed agree level (when VFD is not accelerating or
decelerating). Continue running after detection (OT1 alarm).
02
Overtorque detection is enabled always. Continue running after detection (OT1 alarm).
03
Overtorque detection is enabled whenever at the speed agree level. Coast to a stop after detection (OT1 fault).
04
Overtorque detection is enabled always. Coast to a stop after detection (OT1 fault).
05
Undertorque detection is enabled whenever at the speed agree level (when VFD is not accelerating or
decelerating). Continue running after detection (UT1 alarm).
06
Undertorque detection is enabled always. Continuing running after detection (UT1 alarm).
07
Undertorque detection is enabled whenever at the speed agree level. Coast to a stop after detection (UT1 fault).
08
Undertorque detection is enabled always. Coast to stop after detection (UT1 fault)
Содержание IMPULSE G+ Mini
Страница 15: ...IMPULSE G Mini Technical Manual November 2020 Page 15 Figure 2 1 Long Time Storage...
Страница 17: ...IMPULSE G Mini Technical Manual November 2020 Page 17 Figure 2 2 Diagram A Figure 2 3 Diagram B...
Страница 18: ...IMPULSE G Mini Technical Manual November 2020 Page 18 Figure 2 4 Diagram C...
Страница 56: ...IMPULSE G Mini Technical Manual November 2020 Page 56 Figure 5 8 DC Injection Brake Time Calculation...
Страница 181: ......
Страница 182: ...IMPULSE G Mini Adjustable Frequency Crane Controls Technical Manual November 2020...