5.7.4 Reference Detection
Speed Agree 1
•
When enabled using MFDO “H02.xx = 2", the contact closes when the output frequency (U01.02) is equal to
the frequency reference (U01.01) plus or minus the speed agree detection width (L04.02).
•
U01.02 = (U01.01 ± L04.02)
•
When enabled using MFDO “H02.xx = 3”, the contact closes when the output frequency (U01.02) is equal to
the speed agree detection level (L04.01) plus or minus the speed agree detection width (L04.02).
•
U01.02 = (L04.01 ± L04.02)
Speed Agree 2
•
When enabled using MFDO “H02.xx = 13”, the contact closes when the output frequency (U01.02) is equal to
the frequency reference (U01.01) plus or minus the speed agree detection width (L04.04).
•
U01.02 = (U01.01 ± L04.04)
•
When enabled using MFDO “H02.xx = 14”, the contact closes when output frequency (U01.02) is equal to the
speed agree detection level (L04.03) plus or minus the speed agree detection width (L04.04).
•
U01.02 = (L04.03 ± L04.04)
Frequency Detect
When Frequency Detect is enabled using MFDO “H02.xx = 4":
•
Contact closes at start.
•
Contact opens when accelerating: U01.02
≥
(L04.01 + L04.02).
•
Contact closes again when decelerating: U01.02 < L04.01.
Parameter
Name
Function
Range
Default
L03.17
Overvoltage Suppression and
Stall Prevention
Sets the desired value for the DC bus voltage
during overvoltage suppression and Stall
Prevention during deceleration.
150–400 VDC
370
L03.23
Automatic Reduction Selection
for Stall Prevention during Run
Automatic Reduction Selection for Stall
Prevention during Run
00, 01
00
00 Sets the Stall Prevention level throughout the entire frequency range
to the value in parameter L03.06
01 Automatically lowers the Stall Prevention level in the constant output
range. The lower limit value is 40% of L03.06
L03.24
Motor Acceleration Time for
Inertia Calculations
Sets the time needed to accelerate the
uncoupled motor at rated torque from stop to
the maximum frequency. Setting the VFD
capacity to parameter O02.04 or changing
E02.11 will automatically set this parameter
for a 4-pole motor.
0.001–10.000
sec
Depends
on
O02.04
L03.25
Load Inertia Ratio
Sets the ratio between the connected
machinery and the motor
0.0–1000.0
1.0
Содержание IMPULSE G+ Mini
Страница 15: ...IMPULSE G Mini Technical Manual November 2020 Page 15 Figure 2 1 Long Time Storage...
Страница 17: ...IMPULSE G Mini Technical Manual November 2020 Page 17 Figure 2 2 Diagram A Figure 2 3 Diagram B...
Страница 18: ...IMPULSE G Mini Technical Manual November 2020 Page 18 Figure 2 4 Diagram C...
Страница 56: ...IMPULSE G Mini Technical Manual November 2020 Page 56 Figure 5 8 DC Injection Brake Time Calculation...
Страница 181: ......
Страница 182: ...IMPULSE G Mini Adjustable Frequency Crane Controls Technical Manual November 2020...