Logic Inputs C2 Submenu
100
Logic Inputs C2 Submenu
NOTE: The user can assign particular
functions to each input terminal. Only one
function per terminal is allowed and multiple
terminals cannot have the same function.
When a function is assigned to an input
terminal, it is removed from the list of possible
selections for subsequent terminals.
NOTE: When
Hidden Item
appears with the
parameter description, it indicates that its
appearance in the list is controlled by the
HIDDEN ITEMS setting. See details on page
119.
NOTE: When
Run lock out
appears with the
parameter description, the parameter cannot
be changed when the drive is in the RUN
mode.
NOTE: The
current
setting of each parameter
is displayed in all caps; all other choices in the
list are displayed in lower case.
Parameter
[Alphanumeric]
Description
Default
Hidden
Item
Run
lock out
ENGLISH (U3)
METRIC (U3)
Logic Input 1
[C201]
Logic Input 1
DRIVE ENABLE
Y
Y
Logic Input 2
[C202]
Logic Input 2
RUN
CONTACT CFIRM
Y
Y
Logic Input 3
[C203]
Logic Input 3
FAULT RESET
RUN UP
Y
Y
Logic Input 4
[C204]
Logic Input 4
UP/DWN
RUN DOWN
Y
Y
Logic Input 5
[C205]
Logic Input 5
S-CURVE SEL 0
Y
Y
Logic Input 6
[C206]
Logic Input 6
STEP REF B0
Y
Y
Logic Input 7
[C207]
Logic Input 7
STEP REF B1
Y
Y
Logic Input 8
[C208]
Logic Input 8
STEP REF B2
Y
Y
Logic Input 9
[C209]
Logic Input 9
SAFE-OFF
Y
Y
choices…
choice descriptions…
contact cfirm
[1]
(Contactor Confirm) Closure of the auxiliary contacts confirming closure of the motor
contactor.
drive enable
[2]
(Drive Enable) Must be asserted to permit drive to run. This does not initiate run, just
permits initiation.
extrn fault 1
[3]
(External Fault 1) User input fault #1
Closure of this contact will cause the drive
to declare a fault and perform a fault
shutdown.
extrn fault 2
[4]
(External Fault 2) User input fault #2
extrn fault 3
[5]
(External Fault 3) User input fault #3
extrn /flt 4
[6]
(External / Fault 4) User input fault #4. Opening of this contact will cause the drive to
declare a fault and perform a fault shutdown.
fault reset
[7]
(Fault Reset) If the FAULT RESET SRC (C1) is set to EXTERNAL TB1, the drive’s fault
circuit will be reset when this signal is true. If the FAULT RESET SRC switch is set to
AUTOMATIC, the drive’s fault circuit will be reset when this signal is true and the automatic
fault reset counter, defined by FLT RESETS/HOUR, will be reset to zero. NOTE: this input
is edge sensitive and the fault is reset on the transition from false to true.
low gain sel
[8]
(Low Gain Selection) If the HI/LO GAIN SRC switch is set to EXTERNAL TB1, the low gain
mode is chosen for the speed regulator when this signal is true.
mains dip
[9]
(Mains Dip Selection) Requests the drive to enter mains dip mode. Only valid when MAINS
DIP (C1) = EXTERNAL TB.
mech brake hold
[10]
(Mechanical Brake Hold) Auxiliary contact closures confirming when the mechanical brake
is in the hold mode (engaged).
mech brake pick1
[11]
(Mechanical Brake Pick) Auxiliary contacts from mechanical brake switch 1. Asserted when
brake is picked (lifted).
Содержание HPV 900 Series 2
Страница 4: ......
Страница 195: ...APPENDIX Dimensions Mounting Holes Weights 173 Figure 46 Frame 2 Dimensions Mounting Holes and Weight...
Страница 196: ...APPENDIX Dimensions Mounting Holes Weights 174 Figure 47 Frame 3 Dimensions Mounting Holes and Weight...
Страница 197: ...APPENDIX Dimensions Mounting Holes Weights 175 Figure 48 Frame 3 5 Dimensions Mounting Holes and Weight...
Страница 198: ...APPENDIX Dimensions Mounting Holes Weights 176 Figure 49 Frame 4 Dimensions Mounting Holes and Weight...
Страница 199: ...APPENDIX Dimensions Mounting Holes Weights 177 Figure 50 Frame 5 Dimensions Mounting Holes and Weight...
Страница 227: ...205 Z Z MARKER LOST 150 Zero Speed Level parameter 47 Zero Speed logic output 105 Zero Speed Time parameter 47...
Страница 228: ......
Страница 229: ......