Specifications and Site Requirements
Electrical Specifications
54
MagneMotion
Rockwell Automation Publication MMI-UM002E-EN-P - March 2016
Node Controller LITE
7 - 18 VDC, 5 W maximum based on configuration and operating mode. Refer to
for the mechanical drawing.
AC Power Option
The optional remote power supply for the Node Controller LITE (NC LITE) requires 90 -
264 VAC @ 47 - 63 Hz, single phase (phase to phase or phase to neutral), 0.7 A at 100 VAC
(25 W max), based on configuration and operating mode. Inrush current 45 A/240 VAC max.
Refer to the manufacturer’s data sheet for mechanical information.
The actual power being drawn will depend upon operations being performed, however all
power wiring must be capable of carrying the full load.
DC Power Option
DC power from a user-supplied power supply requires 7 - 18 VDC, 5 W.
The Node Controller LITE can be powered by the MMI custom Power over Ethernet (PoE)
switch or by a compatible PoE network. The remote power supply is not required in these
cases.
CAUTION
High Voltage Hazard
90 - 264 VAC, 25 W
AC power must be disconnected before servicing.
NOTICE
Any user-supplied power supply must be NRTL/ATL approved.