background image

507861-01

Issue 2120

Page 9 of 15

Operation

Sequence of Operation

Upon initial “power up” to unit, there is a 3-minute time delay 

to the compressor contactor (R to Y). Any 24V interrupt (R, 

C) to the defrost control will initiate the 3-minute delay to 

the contactor.

Cooling

When the thermostat is in the cooling mode, the O circuit 

is powered which energizes the reversing valve. Upon 

cooling demand, the thermostat closes circuit R to Y and 

G. Closing R to Y closes the unit contactor, starting the 

compressor and outdoor fan, and signaling the indoor 

blower to run at cooling speed. Upon satisfying cooling 

demand, the thermostat will open the above circuits and 

open the main contactor, stopping the compressor and 

outdoor fan. The unit is equipped with a blower OFF delay; 

the blower will continue to operate for a fixed 90 seconds 

after the thermostat is satisfied.

Heating

Upon heating demand, the thermostat closes circuit R to 

Y, which closes the unit contactor, starting the compressor 

and outdoor fan. The reversing valve is not energized in 

the heating mode. The Y signal from the thermostat brings 

the indoor blower on at heat pump speed. The second 

stage of the thermostat closes circuit R to W, which closes 

the unit sequencers, bringing the auxiliary electric heat on. 

The W signal from the thermostat brings the indoor blower 

on at electric heat speed. Upon satisfying heating demand, 

the thermostat opens the above circuits and stops unit 

operation. 

The unit is equipped with a blower OFF delay; the blower 

will continue to operate for a fixed 90 seconds (heat pump) 

or 120 seconds (electric heat) after the thermostat is 

satisfied.

NOTE: 

The  7.2  and  10  kW  heats  strips  offer  a  W1  and 

W2  thermostat  connection.  Taking  advantage  of  the  two 

heat strip circuits requires a 3-stage thermostat (Y for heat 

pump,  W1  for  electric  heat  stage  1,  and  W2  for  electric 

The location of fresh air capable models must conform to 

the requirements of National Fire Protection Association 

NFPA No. 54 in regards to proximity of forced air inlets 

to flue gas terminals. Improper installation could result 

in personal injury or death.

 WARNING

Figure 7. Auxiliary and Factory Panel for Outdoor Air 

Duct

Factory panel

Outdoor

Air Duct

Auxillary panel

with knockouts

1

2

3

4

5

6

7

8

9

Thermostat

The room thermostat should be located on an inside 

wall where it will not be subject to drafts, sun exposure, 

or  heat  from  electrical  fixtures  or  appliances.  Follow 

manufacturer’s instructions enclosed with the thermostat 

for general installation procedures. Color-coded insulated 

wires (#18 AWG) should be used to connect the thermostat 

to the unit.

Electrical Connections

All wiring must be done in accordance with the National 

Electrical Code (NEC), ANSI/NFPA No. 70 (latest edition); 

Canadian Electrical Code CSA C22.2 Part 1 (latest edition); 

or local codes, where they prevail. Any alteration of internal 

wiring will void certification and warranty.

Units are factory wired for a 230 volt power supply. If power 

supply is 208 volts, it will be necessary to change a wire 

connection on unit transformer from 240 volt terminal to 

208 volt terminal as shown on the wiring diagram.

Use wiring with a temperature limitation of 75°F minimum. 

Run  the  208  or  230  volt,  single  phase,  60  hertz  electric 

power supply through a fused disconnect switch to the 

control box of the unit and connect as shown in the unit’s 

wiring diagram.

The unit must be electrically grounded in accordance with 

local codes or, in the absence of local codes, with the 

National Electrical Code ANSI/NFPA No. 70 (latest edition) 

or CSA C22.2 Part 1 (latest edition).

Power supply to the unit must be NEC Class 1 and must 

comply with all applicable codes. A fused disconnect switch 

should be field provided for the unit. The switch must be 

separate from all other circuits. If any of the wire supplied 

with the unit must be replaced, replacement wire must be 

of the type shown on the wiring diagram. Electrical wiring 

must be sized to minimum circuit ampacity marked on the 

unit. 

Use copper conductors only

. Each unit must be 

wired with a separate branch circuit and be properly fused.

NOTE: 

Some MHP4 models require two separate power 

supply  circuits.  See  the  unit  wiring  diagrams  and  rating 

plates for specifications.

Содержание All-In-One MHP4 Series

Страница 1: ...e consulted before installation is made Such applicable regulations or requirements take precedence over the general instructions in this manual CAUTION P 507861 01 P507861 01 Installation These units are not approved for mobile home applications Such use could result in property damage personal injury or death WARNING General These instructions explain the recommended method of installation of th...

Страница 2: ...n company If any damages are discovered and reported to the carrier do not install the unit as claim may be denied Check the unit rating plate to confirm specifications are as ordered Limitations The unit should be installed in accordance with all national and local safety codes Limitations of the unit and appropriate accessories must also be observed The outdoor fan is designed to operate against...

Страница 3: ...f unit is required for service If the unit is enclosed a door or access panel aligned with the front of the unit is the preferred method of providing access The door or access panel opening must be a minimum of 30 wide centered on the unit and be as tall as the unit If a return duct is not installed in order to provide adequate return air the minimum clearance required between the front of the uni...

Страница 4: ...rille Installation Refer to installation instructions included with the wall sleeve kit and the louver grille kit along with Figure 2 for guidance in assembling and installing the wall sleeve and louver grille The sleeve is not intended as the sole support for the unit An additional support must be provided for adequate support see Figure 2 CAUTION Installing and Securing Unit to Wall Sleeve 1 Mak...

Страница 5: ...ion to top and bottom corners of unit to sleeve seal Caulk if needed Ductwork Ductwork should be designed and sized according to the methods in Manual Q of the Air Conditioning Contractors of America ACCA Check unit air supply outlet for debris before making ductwork connections It is recommended that supply and return duct connections at the unit be made with flexible joints If flexible ducts are...

Страница 6: ...kW TAP 4 AUX HEAT 615 93 590 97 555 101 N A N A N A N A TAP 5 AUX HEAT 715 127 685 134 655 140 630 146 600 151 5 kW TAP 4 AUX HEAT 665 110 635 114 605 118 N A N A N A N A TAP 5 AUX HEAT 750 148 725 154 700 160 675 166 650 171 7 kW TAP 4 AUX HEAT 725 137 705 144 675 150 N A N A N A N A TAP 5 AUX HEAT 825 194 800 200 780 205 755 209 725 213 10 kW TAP 4 AUX HEAT 750 148 725 154 700 161 N A N A N A N ...

Страница 7: ...peed for Cooling operation Blower speed must be field adjusted to Speed Tap 3 for higher duct static applications As shipped speed for Heating operation Blower speed must be field adjusted to Speed Tap 5 for higher duct static applications Table 3 Blower Performance 208V or 230V Air Filter All indoor return air must be filtered A washable filter is furnishedwiththeunit locatedinthereturnaircompart...

Страница 8: ...e wall sleeve and louver assembly to the outside of the building Use thread sealant on the threaded fittings Install threaded fittings by hand only Do not over torque the fittings Do not thread metal condensate fittings to unit drain pans CAUTION Outdoor Ventilation Air Units are fitted with a panel that seals the return air compartment at the outdoor air duct If introduction of outdoor air is des...

Страница 9: ...r inlets to flue gas terminals Improper installation could result in personal injury or death WARNING Figure 7 Auxiliary and Factory Panel for Outdoor Air Duct Factory panel Outdoor Air Duct Auxillary panel with knockouts 1 2 3 4 5 6 7 8 9 Thermostat The room thermostat should be located on an inside wall where it will not be subject to drafts sun exposure or heat from electrical fixtures or appli...

Страница 10: ...fort during defrost The unit will remain in defrost until the defrost sensor has determined that the frost has been removed from the coil or a 14 minute time period has elapsed The defrost control is also equipped with a set of pins to aid in the troubleshooting of the defrost system see Figure 9 The following is a brief outline of the testing of the defrost system 1 Defrost sensor must be closed ...

Страница 11: ...m cleaner Wash filter in soap or detergent water and replace after filter is dry It is not necessary to oil the filter after washing Motors The indoor and outdoor fan motors are permanently lubricated and require no maintenance Outdoor Coil Foreign material should not be allowed to accumulate on the outdoor coil surface or other parts in the air circuit Cleaning should be as often as necessary to ...

Страница 12: ...m Color 29 Height ALVRAL 1P Extruded Aluminum Louver Kit 33 Height ALVRAL 2 Extruded Aluminum Louver Kit Custom Color 33 Height ALVRAL 2P Extruded Aluminum Louver Kit 33 Height ALVRAL 7 Extruded Aluminum Louver Kit Custom Color 33 Height ALVRAL 7P Extruded Aluminum Louver Kit 45 Height ALVRAL 3 Extruded Aluminum Louver Kit Custom Color 45 Height ALVRAL 3P Extruded Aluminum Louver Kit 45 Height ALV...

Страница 13: ... Louver ASLEEVE8 2 8 32 3 4 16 16 5 8 32 7 8 for 45 Louver ASLEEVE8 5 8 45 16 16 5 8 45 1 8 10 Wall Sleeve Kit for 29 Louver ASLEEVE10 1 10 29 16 16 5 8 29 1 8 for 33 Louver ASLEEVE10 2 10 32 3 4 16 16 5 8 32 7 8 for 45 Louver ASLEEVE10 5 10 45 16 16 5 8 45 1 8 12 Wall Sleeve Kit for 29 Louver ASLEEVE12 1 12 29 16 16 5 8 29 1 8 for 33 Louver ASLEEVE12 2 12 32 3 4 16 16 5 8 32 7 8 for 45 Louver ASL...

Страница 14: ...Page 14 of 15 507861 01 Issue 2120 Wiring Diagrams Figure 11 Connection Diagram MHP With Single Circuit and Hard Start Enabled ...

Страница 15: ...507861 01 Issue 2120 Page 15 of 15 Figure 12 Connection Diagram MHP With Dual Circuit and Hard Start Enabled ...

Отзывы: