Installation instructions 

KUS ultrasonic flow sensor 

1

 

General information 

1.1

 

Use 

The instrument described in this manual is a flow sensor  designed 
for  use    with  a  calculator  for  determining  the  consumption  of 
thermal energy in heating or cooling systems that use water. 
The flow meter consists of a metal measuring part  combined with  
a calculator. These two components are connected by a cable.  

1.2

 

General notes 

The flow meter left the factory in a faultless condition where safety 
is  concerned.  The  manufacturer  will  provide  additional  technical 
support  on  request.  Calibration  relevant  security  seal  on  the  flow 
meter must not be damaged or removed. Otherwise the guarantee 
and calibration validity of the flow meter will lapse. 

 

Keep the packaging so that you can transport the flow meter in 
its original packaging following expiry of the calibration validity. 

 

Lay all cables at a minimum distance of 500 mm to high voltage 
and high frequency cables. 

 

A relative humidity of < 93 % at 25 °C is permissible (without 
condensation). 

 

Avoid cavitation in the whole system due to overpressure i.e. at 
least 1 bar at qp and approx. 3 bar at qs (applies for approx. 
80 °C). 

2

 

Safety information 

 

The  flow  meter  may  only  be  used  in  building  service 
engineering  systems  and  only  for  the  applications 
described. 

 

The  local  regulations  (installation  etc.)  must  be  adhered 
to.  

 

Adhere to the operating conditions according to the dial 
plate  during  use.  Non-adherence  can  cause  hazards  and 
the guarantee will lapse.  

 

The  flow  meter  is  only  suitable  for  circulating  water  in 
heating systems. 

 

 

The flow meter is not suitable for drinking water.

 

 

Adhere  to  the  AGFW  requirements  regarding  circulating 
water (FW510).

 

 

Do not lift the flow meter by the calculator.

 

 

Be  aware  of  sharp  points  on  the  thread,  flange  and 
measuring tube.

 

 

Only personnel, trained in the installation and operation 
of meters in heating and cooling systems, may install and 
remove the flow meter.

 

 

Only install or remove the flow meter when the pipes are 
pressure-less.

 

 

After  installing  the  flow  meter,  check  the  leak-tightness 
of the system.

 

 

Guarantee  and  calibration  validity  will  lapse  if  the 
calibration relevant security seals are broken.

 

 

 

Only  clean  the  flow  meter  from  outside  with  a  soft, 
lightly  wetted  cloth.  Do  not  use  any  spirit  or  cleaning 
solvent. 

 

 

As far as disposal is concerned, the flow meter is a waste 
electronic  appliance  in  the  sense  of  European  Directive 
2012/19/EU  (WEEE)  and  it  must  not  be  disposed  of  as 
domestic  waste.  The  relevant  national,  legal  regulations 
must be observed as the appliance must be disposed of 
via the channels provided for this purpose. The local and 
currently valid legislation must be observed.

 

 

The  meter  contains  lithium  batteries.  Do  not  dispose  of 
the  meter  and  the  batteries  with  domestic  waste. 
Observe the local stipulations and laws on disposal. 

 

You can return the lithium batteries to the manufacturer 
for  appropriate  disposal  following  use.  When  shipping 
please  observes  legal  regulations,  in  particular,  those 
governing  the  labelling  and  packaging  of  hazardous 
goods.

 

 

Do  not  open  the  batteries.  Do  not  bring  batteries  into 
contact  with  water  or  expose  to  temperatures  above 
80 °C.

 

 

The  flow  meter  does  not  have  any  lightning  protection. 
Ensure lightning protection via the in-house installation.

 

3

 

Installation 

Proceed as follows to install the flow meter: 

 

Observe the dimensions of the flow meter and check whether 
there is sufficient space available. 

 

Rinse the system thoroughly before installing the flow meter. 

 

Fit the flow meter vertically or horizontally between two slide 
valves so that the arrow on the housing and the flow direction 
match. Also observe the installation situations and the 
following examples of installation (see figure 2 and figure 3). 

 

Loosen the elastic band or the cable tie, provided for the 
transport, from the volume measurement unit. In operation, 
the control cable should not depend directly on the volume 
measurement unit.  

 

If you install the flow meter for cold metering, follow the 
appropriate instructions.  

Recommendation:

  If  you  are  installing  more  flow  meters  in  one 

unit,  make  sure  that  all  the  flow  meters  operate  under  the  same 
mounting conditions. 

3.1

 

Installation notes 

 

Note:

  When  installing  the  flow  meter  the  locally 

applicable installation regulation for flow meters must be 
observed. 

Upstream and downstream straight pipes are not necessary. If you 
install  the  flow  meter  in  the  common  return  of  two  circuits, 
determine  a  place  of  installation  with  a  minimum  distance  of 
10 × DN  from  the  T-piece.  This  distance  ensures  a  good  thorough 
mixing of the different water temperatures.  
 

 

Fig. 1: Mixture of different return temperatures

 

0 01/19 

Sub

je

ct

 

to

 

te

chn

ic

a

l c

ha

ng

 