Macurco DVP-120C Manual
REV – 1.0
[34-8708-4770-8 ]
71
|
P a g e
9.1.5
Enter Password
If the password has not yet been entered, then when the first digit of any parameter is entered the panel will
prompt for the current password. Note that the first digit entered is discarded; it does not count toward the
password or toward the parameter entry.
E n t e r P a s s w o r d
_ _ _ _
Figure B-9 Enter Password
If the password is not entered correctly the panel will display as follows:
W r o n g P a s s w o r d
Figure B-10 Wrong Password Prompt
Once the current password has been entered, the panel will prompt for the configuration parameter being changed.
If the password has been lost:
→
Power down the DVP-120
→
Remove the Jumper Shorting Connector from the EXT header and place the Jumper Shorting Connector onto
the top two pins of the SYS header.
→
Power up the DVP-120. The first display is the current password on the unit.
→
Remove the Jumper Shorting Connector from the SYS header and install back onto the two bottom pins of
the EXT header.
9.2
Configure Sensors Submenu
9.2.1
9.2.2
9.2.3
9.2.4
4.13.3 Configure Sensors Submenu
Press Menu to display Hardware Summary
↑
x 2 Configure Sensors
•
Sensor
S e n s o R 0 1 C O
A : 2 0 0 W : 5 0
Figure B-11 Sensor Summary
↑
Sensor type (set sensor type)
1=CO, 2=NO2, 3=EX, 4=NH3, 5=H2S, 6=REF, 7=CO2, 8=O2 and 0=None
S e n s o r 0 1 C O
T y p e : 1
Содержание MRS-485
Страница 2: ...Macurco DVP 120C Manual REV 1 0 34 8708 4770 8 2 P a g e ...
Страница 77: ...Macurco DVP 120C Manual REV 1 0 34 8708 4770 8 77 P a g e 11 Appendix D DVP 120 Quick Start Guide ...
Страница 78: ...Macurco DVP 120C Manual REV 1 0 34 8708 4770 8 78 P a g e ...
Страница 79: ...Macurco DVP 120C Manual REV 1 0 34 8708 4770 8 79 P a g e ...