1.
With the display function turned “On”, the CD
-xxH/MC will show the current concentration of CO
P
2
P
ppm in the air.
Normal outdoor concentration ranges between 350-450 ppm. When the CO
P
2
P
concentration reaches the Fan Relay
setting (2000
ppm, for example) the display will flash back and forth between “FAn” and “
current gas reading
”. With
the display function turned “Off”, the display does not show the CO
P
2
P
concentration but will show “FAn” as long as the
fan relay is activated.
2.
With the display function turned “On” and the CO
P
2
P
concentration reaching the Alarm Relay setting, (4000 ppm, for
example) the display will flash back and forth between “ALr” and “
current gas reading
”. The buzzer will sound
indicating “Alarm” if the buzzer is turned “On”. With the display function turned off the display does not show the CO
P
2
P
concentration but will show “ALr” when the Alarm relay is activated.
3.
With the 4-20 mA funct
ion turned “On” and the CO
P
2
P
concentration climbing, the 4-20 mA signal will ramp up
corresponding to the concentration (0-
5000 ppm, for example). The display will show “FAn” and “ALr” and sound as
outlined above.
4.1
Power up
The CD-xxH/MC cycles through an internal self-test cycle for the first minute that it is powered. The unit will execute the test
cycle any time power is dropped and reapplied (i.e. power failure). During the self-test cycle the unit will display the firmware
version number, then count do
wn from 60 to 0 (if the display setting is “On”) and finally go into normal operation. The alarm
relay will be activated for 10 seconds and the fan relay for 60 seconds during the power-
up cycle unless the “Power Up Test”
(PUt) option is OFF. The indicator light (LED) will flash green during the self-test cycle. At the end of the 1-minute cycle, the unit
will take its first sample of the air and the indicator light will turn solid green.
4.2
Display turned “
O
n”
Clean Air
–
With the display function turned “On”,
the CD-xxH/MC will show the current concentration of CO
P
2
P
ppm.
Note: CO
P
2
P
in “clean air” will not show 0 as normal atmospheric CO
P
2
P
levels are between 350 ppm and 450 ppm.
Fan level
–
When the CO
P
2
P
concentration reaches the Fan Relay setting (2000 ppm, for example) the display will flash back and
forth between “FAn” and “
2000
”
(or current gas reading).
Alarm level
–
With the display function turned “On” and the CO
P
2
P
concentration reaching the Alarm Relay setting, (4000 ppm, for
example) the display will flash back and forth between “ALr” and “
current gas reading
”. The buzzer will sound indicating “Alarm”
if the buzzer is turned “On”.
Trouble
–
With the display function turned “On” and the device is in a trouble state, the display will display the “t” Error code
(t01 for example). If the Trouble Fan Setting is enabled, the Fan relay will switch activating the relay. See section
4.3
Display turned “Off”
Clean Air
–
With the display function turned” Off”, the
display does not show the CO
P
2
P
concentration. Only the Power indicator
light on will be on.
Fan Level
–
When the CO concentration reaches the Fan Relay setting (2000 ppm, for example) the display will flash back and
forth between “FAn” and “blank” as long as the fan relay is enabled. This appears as slowly flashing “FAn”.
Alarm Level
–
With the display function turned off the display does not show the CO
P
2
P
concentration but will show “ALr” when
the Alarm relay is activated.
Trouble
–
With the display
function turned “On” and the device is in a trouble state, the display will display the “t” Error code
(t01 for example). If the Trouble Fan Setting is enabled, the Fan relay will switch activating the relay. See section
Содержание CD Series
Страница 31: ...Macurco CD xx H MC Manual REV 1 1 34 2900 0510 8 31 P a g e 9 Appendix B Menu Structure 9 1 Main Menu ...
Страница 32: ...Macurco CD xx H MC Manual REV 1 1 34 2900 0510 8 32 P a g e 9 2 Auto Test Menu bUZ ...
Страница 33: ...Macurco CD xx H MC Manual REV 1 1 34 2900 0510 8 33 P a g e 9 3 Configuration Menu CON ...
Страница 34: ...Macurco CD xx H MC Manual REV 1 1 34 2900 0510 8 34 P a g e ...
Страница 35: ...Macurco CD xx H MC Manual REV 1 1 34 2900 0510 8 35 P a g e ...
Страница 36: ...Macurco CD xx H MC Manual REV 1 1 34 2900 0510 8 36 P a g e ...
Страница 37: ...Macurco CD xx H MC Manual REV 1 1 34 2900 0510 8 37 P a g e ...
Страница 38: ...Macurco CD xx H MC Manual REV 1 1 34 2900 0510 8 38 P a g e ...
Страница 39: ...Macurco CD xx H MC Manual REV 1 1 34 2900 0510 8 39 P a g e 9 4 Select Test Menu tst ...
Страница 40: ...Macurco CD xx H MC Manual REV 1 1 34 2900 0510 8 40 P a g e 9 5 CAL Menu CD xxMC Only ...