Macurco MRS-485 Modbus RS-485 Adapter
REV – 1.0
[34-2900-0019-7]
9
|
P a g e
Figure 3-1 BRS-485 Installation Expanded
5.
The 6-Series detector mounts on a 4”x 4” electrical box supplied by the contractor.
6.
Connect the detector to the control cables with terminal plugs. When making connections, make sure
the power is off.
7.
There are two terminals for the dry alarm relay contacts, again with no polarity preference. The alarm
relay can switch up to 0.5 A 120 V, or 60 VA. The alarm relay is activated if gas reaches or exceeds the
alarm settings. See Operation of the detector User Instructions for details on relay settings.
8.
The alarm relay can be configured to normally open (default) (N.O.) or normally closed (N.C.) and will
activate if the gas concentration exceeds alarm set point. It will deactivate once the gas concentration
drops below the alarm set point. Note that the “disable” setting will cause the alarm relay not to engage
at all.
9.
The dry contact, SPDT fan relay has three terminals: The Common (COM), normally open (N.O.) and the
normally closed (N.C.) contact. The fan relay can switch up to 5.0 A up to 240 VAC. See Operation section
of the detector User Instructions for details on relay settings.