Thank you for purchasing a Macnaught DM100  
Positive Displacement Fuel Meter.
 

The  Macnaught  DM100  fuel  meter  has  incorporated  the 
oval rotor principal into its design. This has proven to be a 
highly  reliable  and  highly  accurate  method  of  measuring 
flow, providing exceptional repeatability and high accuracy. 

The low pressure drop through the meter makes the meter  
ideally  suited    for  use  in  gravity  applications  or    with  the 
Macnaught range of electric fuel pumps.  

Macnaught manufacture a full range of pumps, meters and 
accessories  to  suit  most  of  your  fluid  transfer  needs. 
Pease  consult  your  local  Macnaught  reseller  for  more 
information. 

With  your  appropriate  care  combined  with  the  Macnaught 
Guarantee of dependable after sales service, (provided by 
our worldwide distribution network), you will be assured of 
continuous safe, efficient and reliable product operation. 

Please read and retain this instruction manual to  
assist  you  in  the  operation  and  maintenance  of  this 
quality product. 

General Information 

This manual assists you in operating and maintaining your 
new  DM100  Fuel  Meter.  The  information  contained  will 
help  you  ensure  many  years  of  dependable  performance 
and trouble free operation.

 

Please  take  a  few  moments  to  read  through  this  manual 
before installing and operating your new fuel meter. 
 
If  you  experience  problems  with  the  product,  refer  to  the 
Maintenance  and  Trouble  Shooting  sections  of  this 
manual.    
 
If  you  require  further  assistance  please  contact  your  local 
Macnaught  Distributor,  Authorised  Macnaught  Service 
Centre or Macnaught P/L.

 

Macnaught recommends, that as added protection to your 
equipment you install a Macnaught fuel filter  
assembly    in  line  before  the  inlet  of  your  DM  Fuel  Meter. 
Contact your local Macnaught distributor for further details.   

Observe  precautions  against  fire  or  explosion  when 
dispensing flammable liquid. Do not operate the meter 
in  the  presence  of  any  source  of  ignition  including 
running  or  hot  engines,  lighted  cigarettes  or  gas  or 
electric heaters. 

Ensure  that  you  follow  all  the  correct  earthing  and 
grounding procedures before use. 

Inspect  seals  and  connections  for  leaks  weekly  when 
using flammable liquids. 

Do  not  use  Teflon  tape  on  any  connections  when 
using flammable liquid. 

Installation 

1) Ensure the meter is installed so the flow of the liquid is 
in the direction of the arrows embossed on the meter body. 

2) The meter can be installed in any orientation as long as 
the meter shafts are in a horizontal plane. (see fig 2 for 
correct installation). The register assembly may be rotated 
to suit the individual installation.

 

(fig 2) 

Note:  Incorrect  installation  can  cause  premature  wear 
of components. 

INSTRUCTION  MANUAL 

DM100  

POSITIVE DISPLACEMENT  

FUEL METER 

Introduction 

 IMPORTANT 

 CAUTION 

3) Do not over tighten connections. 

Includes Models

DM100-01
DM100-02
DM100-03
DM100-04
DM100-05

Содержание DM100-01

Страница 1: ... you experience problems with the product refer to the Maintenance and Trouble Shooting sections of this manual If you require further assistance please contact your local Macnaught Distributor Authorised Macnaught Service Centre or Macnaught P L Macnaught recommends that as added protection to your equipment you install a Macnaught fuel filter assembly in line before the inlet of your DM Fuel Met...

Страница 2: ...re at 90O to each other see fig 3 Check the rotor rotation by turning either of the rotors If the rotors are not in mesh correctly or do not move freely remove one of the rotors and replace it correctly at 900 to the other rotor Recheck the operation of the rotors 3 Insert o ring into the o ring groove on the register base 4 Carefully align the spring pins on the meter body to the spring pin holes...

Страница 3: ...8 1 A O ring Viton BS150V 9 1 n a new meter required Register base 10 1 Dow el pins 11 4 Hex screw M6 X 20 12 4 Nut M6 13 1 1st Gear 14 1 2nd Gear 15 1 3rd Gear 16 1 4th Gear 17 1 ME035s Litre Output shaft 18 1 ME035US US Gal Circlip 19 1 Washer 20 1 A O ring Viton BS007V 21 1 Gear box cover 22 1 Bush 23 1 Gear 24 1 A O ring Viton BS032V 25 2 Screw M4 X 16 26 1 Register assembly 27 1 Facia plate 2...

Страница 4: ...rotors 6 7 for installation w ear or damage Replace as required Fluid flow s but no reading on the meter a Drive gear loose 23 a Replace gear box cover assembly 16 23 b Rotor 6 drive gear damaged b Replace rotor 6 c Gearbox gears 13 16 damaged c Replace damaged gears d Register gears damaged d Replace register assembly Fluid leaks into the register assembly Damaged o ring 20 or o ring 24 Replace g...

Отзывы: