215104
108
Revision A
4.3.4
Setting the Hydraulic Overload Pressure
The hydraulic overload pressure setpoint sets the upper limit of the pressure bar graph, which displays when the optional
pressure sensor is enabled.
NOTE:
•
This procedure requires installation of the optional pressure sensor (MD #B5574). For overload pressure values, refer to
pressure sensor installation instructions (MD #169031).
•
To enable sensor, refer to
4.8.2 Switching the Installed Header Sensors ON or OFF, page 143
1011760
CXXX
EXXX
WINDROWER SETUP?
NO/YES
A
B
C
Figure 4.23: CDM Programming Buttons
1.
Turn the ignition key to RUN, or start the engine.
2.
Press PROGRAM (A) and SELECT (C) on the cab display
module (CDM) to enter programming mode.
•
WINDROWER SETUP? is displayed on the upper line.
•
NO/YES is displayed on the lower line.
3.
Press right arrow (B) to select YES. Press SELECT (C).
•
SET KNIFE SPEED? is displayed.
1011805
CXXX
EXXX
OVERLOAD PRESSURE?
4000 PSI
D
C
B
A
Figure 4.24: Hydraulic Overload Pressure
4.
Press SELECT (D) until OVERLOAD PRESSURE? is displayed
on the upper line.
•
The current overload pressure is displayed on
lower line.
NOTE:
Pressure range is 17,237
–
34,474 kPa (2500
–
5000 psi).
5.
Press left (B) or right (C) arrows to set hydraulic overload
pressure. Press SELECT (D).
6.
Press PROGRAM (A) to exit programming mode or press
SELECT (D) to proceed to next WINDROWER SETUP action.