background image

INSTRUCTION MANUAL

Read and understand all of the instructions and safety information in 

this manual before operating this product.

MAN-004 Rev G

            02/2019

© 2019 MAC Medical, Inc.

SS Series Surgical Scrub Sinks

Installation - Operation - Maintenance - Cleaning

OSHPD

Pre-Approved

SS32 Model

SS64 Model

SS96 Model

C

Содержание SS Series

Страница 1: ...instructions and safety information in this manual before operating this product MAN 004 Rev G 02 2019 2019 MAC Medical Inc SS Series Surgical Scrub Sinks Installation Operation Maintenance Cleaning OSHPD Pre Approved SS32 Model SS64 Model SS96 Model C ...

Страница 2: ...ng Specifications SS32 Single Basin 9 Recommended Mounting Specifications SS64 Double Basin 10 Recommended Mounting Specifications SS96 Triple Basin 11 Connect Drain Pipe to Drain and Plumbing to Water Lines 12 Plumbing Install Instructions 12 Preventative Maintenance 13 Troubleshooting 13 Replacement Parts for Manual Knee Operated and Infrared Self Activated Sink Plumbing 14 Plumbing Access Manua...

Страница 3: ... with this equipment The use of inexperienced unqualified persons to service the equipment or the installation of unauthorized parts could cause serious personal injury or result in costly damage Always unplug power cord from power source prior to attempting any repairs or servicing WARNING Burn Hazard DO NOT CHANGE temperature settings on thermostatic mixing valve unless you are a trained mechani...

Страница 4: ...equirements for sinks with optional infrared sensor operations a 120 Volt 60 Hz single phase 3 0 amp GFIC protected electrical outlet by others b 220 VAC 60 Hz single phase 1 5 amp c to be installed per local building codes 5 Sink Weight a Single basin 130 lbs b Double basin 230 lbs c Triple basin 320 lbs 6 Sink Certifications a UL and cUL certified b California OSHPD pre approved when mounted on ...

Страница 5: ...ction of excessive or insufficient flow rates Switch Ratings Max Resistive Load Switch Timer Controller Maintenance Accumulation of foreign debris should periodically be removed from these switches Occasional wipe down cleaning when excessive contamination is present is all that is normally required To Clean Remove unit from system and disassemble as shown below Clean all parts reassemble and rein...

Страница 6: ...Instruction Manual MAN 004 6 www macmedical com Sink Dimensions SS32 SS64 SS96 Models Fig 2 SS32 single basin Fig 3 SS64 Dual Basin Fig 4 SS96 Triple Basin ...

Страница 7: ...nded mounting specifications for Z brackets shown in Fig 13 SS32 Fig 16 SS64 and Fig 19 SS96 on page 9 through page 11 B IMPORTANT For wall mounted units the wall structure must be capable of supporting the load C Optional wall mounting systems in wall chair carrier and pedestal style and their mounting specifications shown in Fig 15 part S0001 for sink SS32 Fig 18 part S0002 for sink SS64 and Fig...

Страница 8: ...out item 1 through the small hole at the top of the sink Fig 9 The nut item 2 should rest on top of the sink 3 Re install the bushing onto the spout from inside the cabinet Fig 10 4 Attach the soap tubing to the spout and soap pump circled in red as shown in Fig 11 and Fig 12 To Operate the Soap Pump press the soap spout down repeatedly to start the flow of the soap Fig 8 Soap Spout with nut and b...

Страница 9: ...mended Mounting Specifications SS32 Single Basin For the assembly drawing of In line wall carrier mount S0001 see page 20 Fig 13 Z bracket mounting locations SS32 Fig 14 In line wall carrier mount S0001 Fig 15 In line wall carrier mounting locations SS32 ...

Страница 10: ...nded Mounting Specifications SS64 Double Basin For the assembly drawing for the In line Wall Carrier Mount S0002 see page 21 Fig 16 Z bracket mounting locations SS64 Fig 17 In line wall carrier mount S0002 Fig 18 In line wall carrier mounting locations SS64 ...

Страница 11: ...mended Mounting Specifications SS96 Triple Basin For the assembly drawing of the In Line Wall Carrier Mount S0003 see page 22 Fig 19 Z bracket mount locations SS96 Fig 20 In line wall carrier mount S0003 Fig 21 In line wall carrier mounting locations SS96 ...

Страница 12: ...pection and Yearly Maintenance Periodic inspection and yearly maintenance by a licensed contractor is required Corrosive water conditions temperatures over 200 F unauthorized adjustments or repair could render the valve ineffective for service intended Regular checking and cleaning of the valve s internal components and check stops helps assure maximum life and proper product function Frequency of...

Страница 13: ...logged cartridge 2 Flow of water is completely cut off A Valves upstream from supply completely closed B Failure of cold water supply pressure mixing value is designed to shut off on a cold water supply failure C Checkstops completely closed 3 Flow is untempered hot or cold water A Accumulation of time deposits in hot water pipes restricting the flow of hot water B Thermostatic actuator failure re...

Страница 14: ...lumbing S0010 4 1 2 Balance Flow Control Valve S0024 Solenoid Valve for Infrared S0013 5 Knee Operated Water Valve S0029 Infrared Sensor S0012 6 Inline Flow Switch Timer for infrared activated plumbing S0130 01 7 Checkstop Strainer L R for both knee operated or infrared activated plumbing S0011 8 Swivel Aerator for both knee operated or infrared activated plumbing S0032 9 Soap Spout for both knee ...

Страница 15: ... The sensors determines the range during initialization period The time after initial power until the light turns off is approximately 5 minutes The range is approximately 12 14 in front of the sensor and is 25 degrees at peak During the initialization period the sensors allow for fixed objects that may be within the sensors range The sensors are equipped with a 2 second on off delay and no time o...

Страница 16: ...leaning pads Soft bristle brush Mild detergents Sodium Bicarbonate baking soda Distilled water pH rating 7 alone or with a mild detergent White vinegar in a spray bottle Isopropyl Alcohol Hospital grade non bleach disinfectants Cleaners approved for use on stainless steel Cleaning Stainless Steel Surfaces 1 Using a damp lint free cloth and approved cleaner wipe down the entire exterior surface of ...

Страница 17: ...er read out 2 Place a grommet in the 0 38 diameter wire threading hole Grommet to be supplied by others 3 Mount the timer housing to the top of the sink in the 0 31 diameter drilled holes Mounting studs 0 25 diameter are provided on the housing Secure to sink top with the provided hex nuts 4 Thread the 3 flow switch timer wires through the drilled hole on top of the sink Fig 32 circled in red 5 Co...

Страница 18: ...ming parameters can be accessed when the Program Enable input is active by pressing the Down key To edit a parameter use the Down key to scroll until the desired parameter appears on the screen Pressing the Next key will cause the leftmost digit of that value to begin to flash Use the Next and Down keys in combination to choose individual digits and change their value Front Panel Reset Enable When...

Страница 19: ...ight Approximately 64 grams 2 25 ounces Rear Terminal Connections Timer Battery Replacement The unit is shipped with one CR AA size 3V Lithium battery which is pre installed To change the battery remove the battery cover by pushing inward and down Install the battery in either of the two slots The unit runs on a single battery and the second slot is provided to allow for installing a new battery b...

Страница 20: ...ends that the In line Wall Carrier Mount Assembly be tied into the existing wall support structure All applicable local and state building codes should be adhered to when mounting this unit 3 8 U BOLTS HDW0003 01 QTY 6 3 8 FLAT WASHER HDW0001 01 QTY 12 3 8 HEX NUT HDW0002 01 QTY 12 1 4 HEX NUT HDW0002 02 QTY 33 1 4 ALL THREAD ROD HDW0004 01 QTY 11 BOTTOM CARRIER PLATE SMS0052 01 QTY 1 TOP CARRIER ...

Страница 21: ...ends that the In line Wall Carrier Mount Assembly be tied into the existing wall support structure All applicable local and state building codes should be adhered to when mounting this unit SINK POST SMS0050 QTY 3 TOP CARRIER PLATE SMS0051 02 QTY 2 BOTTOM CARRIER PLATE SMS0052 02 QTY 1 1 4 ALL THREAD ROD HDW0004 01 QTY 12 1 4 HEX NUT HDW0002 02 QTY 36 3 8 HEX NUT HDW0002 01 QTY 18 3 8 FLAT WASHER ...

Страница 22: ...mends that the In line Wall Carrier Mount Assembly be tied into the existing wall support structure All applicable local and state building codes should be adhered to when mounting this unit SINK POST SMS0050 QTY 4 TOP CARRIER PLATE SMS0051 03 QTY 1 BOTTOM CARRIER PLATE SMS0052 03 QTY 1 1 4 ALL THREAD ROD HDW0004 01 QTY 14 1 4 HEX NUT HDW0002 02 QTY 42 3 8 HEX NUT HDW0002 01 QTY 24 3 8 FLAT WASHER...

Страница 23: ...e factory It is the customer s responsibility to inspect the product for packaging damage before signing the BOL This warranty does not apply to products which have been subject to abuse misuse accident modification alteration tampering negligence lack of routine maintenance or misapplication or products that have been repaired by other than MAC Medical or its authorized representatives This warra...