MODEL: W2XR

Space-saving Dual Output Signal Conditioners

Mini-MW Series

RTD TRANSMITTER

(PC programmable)
Functions & Features
• Accepts direct input from a RTD
• 4-wire connection available
• Two independent output ranges
• Linearization and burnout
• PC programmable
• High-density mounting

Typical Applications
• Long distance transmission between the RTD
and the transmitter
• Combination with intrinsic safety barriers

89

(3.51)

29.5 (1.16)

124

(4.88)

mm (inch)

MODEL: W2XR–[1][2][3]-[4][5]

ORDERING INFORMATION

• Code number: W2XR-[1][2][3]-[4][5]
Specify a code from below for each [1] through [5].
(e.g. W2XR-4Z1V3-M2/N/Q)
• Temperature range (e.g. 0 – 100 °C)
• Output 1 range (e.g. 4 – 20 mA DC)
• Output 2 range  (e.g. 1 – 5 V DC)
• Specify the specification for option code ‘Q.’
(e.g. /C01/S01)
Note: If one of the outputs should be a current range,
specify it for the Output 1 to allow a greater load.

[1] INPUT RTD

1: JPt 100 (JIS'89)

(Usable range: -200 to +500°C, -328 to +932°F; min.span: 20°C, 36°F)

3: Pt 100 (JIS'89)

(Usable range: -200 to +650°C, -328 to +1202°F; min.span: 20°C, 36°F)

4: Pt 100 (JIS'97, IEC)

(Usable range: -200 to +850°C, -328 to +1562°F; min.span: 20°C, 36°F)

5: Pt 50 Ω (JIS'81)

(Usable range: -200 to +649°C, -328 to +1200°F; min.span: 20°C, 36°F)

7: Pt 1000

(Usable range: -200 to +850°C, -328 to +1562°F; min.span: 20°C, 36°F)

9: Cu 10 @25°C

(Usable range: -50 to +250°C, -58 to +482°F; min.span: 20°C, 36°F)

0: Specify (Please provide a resistance table.)
(Configurator software is used to change the input type and
precise range.)

[2] OUTPUT 1

Current

Z1: Range 0 – 20 mA DC

Voltage

V2: Range -10 – +10 V DC
V3: Range -5 – +5 V DC
(Configurator software is used to change output over the
described range of the selected suffix code.
For changing between suffix codes, set the Output Range
Selector on the side of unit before software adjustment.)

[3] OUTPUT 2

Same range availability as Output 1
Y: None
(Configurator software is used to change output over the
described range of the selected suffix code.
For changing between suffix codes, set the Output Range
Selector on the side of unit before software adjustment.)

[4] POWER INPUT

AC Power

M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
 47 – 66 Hz)

DC Power

R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
R2: 11 – 27 V DC
(Operational voltage range 11 – 27 V, ripple 10 %p-p max.)
P: 110 V DC
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)

[5] OPTIONS (multiple selections)

Standards & Approvlas (must be specified)

/N: Without CE

Other Options

blank: none
/Q: Option other than the above (specify the specification)

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Содержание W2XR

Страница 1: ...to 1562 F min span 20 C 36 F 9 Cu 10 25 C Usable range 50 to 250 C 58 to 482 F min span 20 C 36 F 0 Specify Please provide a resistance table Configurator software is used to change the input type an...

Страница 2: ...ance range 0 23 mA DC Minimum span 1 mA Offset Lower range can be any specific value within the output range provided that the minimum span is maintained Load resistance Output drive 12 V max for Outp...

Страница 3: ...IP SW Output 1 Configuration DIP SW OFF ON 1 2 3 4 OFF ON 1 2 3 4 Provided only for two output type Refer to the instruction manual for detailed procedures EXTERNAL DIMENSIONS TERMINAL ASSIGNMENTS uni...

Страница 4: ...en line is only with 2nd output option DIP SW DIP SW Digital Computation Low Drift Amplifier STATUS 2 5V 13k CONFIGURATOR JACK A 2 wire RTD 3 wire RTD 4 wire RTD B A B B A B A B Specifications are sub...

Страница 5: ...ket or mount it turn off the power supply and input signal for safety ENVIRONMENT Indoor use When heavy dust or metal particles are present in the air install the unit inside proper housing with suffi...

Страница 6: ...CKING 1 Terminal wiring Check that all cables are correctly con nected according to the connection diagram 2 Check DIP switch setting 3 Power input voltage Check voltage across the terminal 10 11 with...

Страница 7: ...MODE ERROR MODE Parameter Error Error occurred when reading parameters from the internal memory LD1 LD2 LD3 A A G Overrange Input The input is below 15 or above 115 LD1 LD2 LD3 R G G G A Burnout PC Co...

Страница 8: ...ether with a copy of its original sales invoice THIS IS THE ONLY WARRANTY APPLICABLE TO M SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING ANY IMPLIED WARRANTIES OF M...

Отзывы: