R8-DC4C
P. 3 / 4
EM-9743 Rev.1
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
COMPONENT IDENTIFICATION
RUN
Module Address Setting
Rotary SW
Function Setting
DIP SW
Terminator DIP SW
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
SW1
x10
1 2 3 4 5 6 7 8
x1
SW2
SW4
SW3
Term
On
On
Status Indicator LED
Output Status Indicator LED
Internal Bus Connector
Output Connectors
FRONT VIEW
SIDE VIEW
CARD ADD.
DO1
DO2
DO3
DO4
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
■
INDICATOR LED
LED
OPERATION
FUNCTION
Status
OFF
Stopping
Green ON
Valid host communication
Green Blinking
Reading/writing configuration
Red ON
Setting error
Red Blinking
Parameter error
Output
Status
OFF
OFF
Green ON
ON
■
OUTPUT CONNECTOR ASSIGNMENT
PIN
ID
FUNCTION
No.
1
DO
Discrete output
2
NC
No connection
3
NC No connection
4
DO
Discrete output
1
2
3
4
■
PC CONFIGURATOR
The following parameters can be set with using PC Configu-
rator Software (model: R8CFG):
• Output at the startup
• Output at the loss of communication
• Common setting (loss of internal bus communication de
-
tection time)
Turn SW4-8 ON to allow programming by the PC Configu
-
rator via the Power/Network Module.
Refer to the users manual for the R8CFG for detailed opera
-
tion of the software program.
■
MODULE ADDRESS
■
Module Address
The left switch determines the tenth place digit, while the
right switch does the ones place digit of the address.
Address is selected between 0 to 31.
(Factory setting: 0)
Module Address Setting (x1)
Module Address Setting (x10)
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
■
OPERATING MODE
*Factory setting
• Output at The Loss of Communication
OUTPUT AT THE LOSS OF COMMUNICATION
SW4-7
Output Hold (*)
(last data correctly rerceived is hold)
OFF
Stop output (Output fixed at OFF)
ON
• Configuration Mode
CONFIGURATION MODE
SW4-8
DIP switch setting (*)
OFF
PC Configurator and communicaton
ON
• Terminator DIP SW
TERMINATOR SW
SW3
Without (*)
OFF
With
ON
Caution
: Be sure to set unused SW 4-1 through 4-6 to OFF.