manualshive.com logo in svg
background image

R7HL-DC16A

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-7812-G  Rev.4  P. 2 / 5

COMPONENT IDENTIFICATION

X10

X1

STATION ADD.

1

2

3

4

5

6

7

8

10 11 12 13

2

3

4

1

15 16 17 18

7

8

9

6

14

5

4

5

6

7

1

2

3

TERM

ON

OFF

RUN

PWR

ON

0

1

2

3

4

5

6

7

8

9

A

B

C

D

E

F

■ 

FRONT VIEW

■ 

SIDE VIEW

012

34

56

789AB

C

D

EF

012

34

56

789AB

C

D

EF

Terminating Resistor SW

Output Terminals

Network, Power Supply

Terminals

Status Indicator LED

Station Address Setting Rotary SW

Operating Mode Setting DIP SW (SW1)

Discrete Output

Status Indicator LED

 

STATUS INDICATOR LED

ID

COLOR

FUNCTION

PWR

Green

Turns on when the internal 5V is sup-
plied normally.

RUN

Green

Turns on when the refresh data is re-
ceived normally. 

 

DISCRETE OUTPUT STATUS INDICATOR LED

LED indicators shows the signal status.
    ON   : LED ON (red)
    OFF : LED OFF

 

STATION ADDRESS

The left switch determines the sixteenths place digit, while 
the right switch does the ones place digit of the address.
(Range: 01H to 3FH)

Station Address Setting (x1)

Station  Address Setting (x16)

012

34

56

789AB

C

D

EF

012

34

56

789AB

C

D

EF

 

OPERATING MODE

(*) Factory setting

• Output at the loss of communication (SW1-7)

SW1-7

OUTPUT AT THE LOSS OF COMMUNICATION

OFF

Hold the output (*)
(maintains the last data received normally) 

ON

Reset the output (turned off) 

• Transfer rate (SW1-8)

SW1-8

TRANSFER RATE

OFF

12 Mbps (*)

ON

6 Mbps

Note: Be sure to set unused SW1-1 through 1-6 to OFF.

 

TERMINATING RESISTOR

To use the terminating resistor, turn the switch ON, and 
OFF to invalidate.  (Factory setting OFF)

 

NETWORK, POWER SUPPLY TERMINAL ASSIGNMENT

• Full-duplex communication

4

RXD+

5

6

7

1

2

3

RXD– +24V 0V

TXD+ TXD– FG

NO.

ID

FUNCTION, NOTES

1

TXD+

Network (slave, transm)

2

TXD–

Network (slave, transmission –)

3

FG

FG

4

RXD+

Network (master, transm)

5

RXD–

Network (master, transmission –)

6

+24V

Power input (24V DC)

7

0V

Power input (0V)

• Half-duplex communication

4

TR

+

5

6

7

1

2

3

TR

– +

24V

0V

NC

NC

FG

NO.

ID

FUNCTION, NOTES

1

NC

No connection

2

NC

No connection

3

FG

FG

4

TR+

Network

5

TR–

Network

6

+24V

Power input (24V DC)

7

0V

Power input (0V)

Отзывы: