R7F4HEIP-DAC16B

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8005-D  P. 3 / 7

 

SENSOR EXC. AND I/O TERMINAL ASSIGNMENTS

Applicable connector: DFMC0,5/13-ST-2,54 (Phoenix Contact) (included in the package)
Applicable wire size: 0.14 - 0.5mm

2

, stripped length 7mm

Recommended solderless terminal:
· AI0,14-6GY 0.14mm

(Phoenix Contact)

· AI0,25-6YE 0.25mm

2

 (Phoenix Contact)

· A0,34-7 0.34mm

2

 (Phoenix Contact)

1 2 3 4 5 6 7 8 9 10 11 12 13 27 28 29 30 31 32 33 34 35 36 37 38 39

14 15 16 17 18 19 20 21 22 23 24 25 26 40 41 42 43 44 45 46 47 48 49 50 51 52

PIN No.

ID

FUNCTION

PIN No.

ID

FUNCTION

1

+24V1

24V DC

27

+24V2

24V DC

2

X0

Input 0

28

Y0

Output 0

3

+24V1

24V DC

29

+24V2

24V DC

4

GND1

0V

30

GND2

0V

5

X2

Input 2

31

Y2

Output 2

6

+24V1

24V DC

32

+24V2

24V DC

7

GND1

0V

33

GND2

0V

8

X4

Input 4

34

Y4

Output 4

9

+24V1

24V DC

35

+24V2

24V DC

10

GND1

0V

36

GND2

0V

11

X6

Input 6

37

Y6

Output 6

12

+24V1

24V DC

38

+24V2

24V DC

13

GND1

0V

39

GND2

0V

PIN No.

ID

FUNCTION

PIN No.

ID

FUNCTION

14

GND1

0V

40

GND2

0V

15

X1

Input 1

41

Y1

Output 1

16

+24V1

24V DC

42

+24V2

24V DC

17

GND1

0V

43

GND2

0V

18

X3

Input 3

44

Y3

Output 3

19

+24V1

24V DC

45

+24V2

24V DC

20

GND1

0V

46

GND2

0V

21

X5

Input 5

47

Y5

Output 5

22

+24V1

24V DC

48

+24V2

24V DC

23

GND1

0V

49

GND2

0V

24

X7

Input 7

50

Y7

Output 7

25

+24V1

24V DC

51

+24V2

24V DC

26

GND1

0V

52

GND2

0V

Содержание R7F4HEIP-DAC16B

Страница 1: ...protective measures to ensure the CE conform ity POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 24V DC rating 24V 10 approx 70mA GENERAL PRECAUTIONS Before you remove the unit or mount it turn off the power supply and input signal for safety Before you remove the terminal block or mount it make sure to t...

Страница 2: ... the signal status ON LED ON OFF LED OFF IP ADDRESS Set the host address 2 digit hexadecimal number in the IP address using rotary switches SA1 and SA2 for the first digit and the second digit respectively When using the host address in the IP address set on the PC configurator software model R7CFG set the switches to 00H When the network address Subnet Mask and Default Gateway need to be changed ...

Страница 3: ... 46 47 48 49 50 51 52 PIN No ID FUNCTION PIN No ID FUNCTION 1 24V1 24V DC 27 24V2 24V DC 2 X0 Input 0 28 Y0 Output 0 3 24V1 24V DC 29 24V2 24V DC 4 GND1 0V 30 GND2 0V 5 X2 Input 2 31 Y2 Output 2 6 24V1 24V DC 32 24V2 24V DC 7 GND1 0V 33 GND2 0V 8 X4 Input 4 34 Y4 Output 4 9 24V1 24V DC 35 24V2 24V DC 10 GND1 0V 36 GND2 0V 11 X6 Input 6 37 Y6 Output 6 12 24V1 24V DC 38 24V2 24V DC 13 GND1 0V 39 GND...

Страница 4: ...move the upper hook of the unit from the DIN rail 1 2 3 SURFACE MOUNTING 1 Insert the two DIN rail mounter sliders until it clicks once as shown below 1 1 2 Mount the unit with M4 screws referring to the External Dimensions Torque 1 4 N m DIN RAIL MOUNTING RIGHT ANGLE Mounting 1 Insert the longer DIN rail mounter slider until it clicks twice as shown below 2 Set the upper hook at the rear side of ...

Страница 5: ...mm wide 2 4 3 dia 4 deep CONNECTION DIAGRAM Note In order to improve EMC performance bond the FE terminal to ground Caution FE terminal is NOT a protective conductor terminal 1 The network cable can be connected to either one 1 EtherNet IP RJ 45 MODULAR JACK 1 EtherNet IP RJ 45 MODULAR JACK 3 4 2 25 26 24 1 14 29 30 28 51 52 50 27 40 4 5 1 24V DC FE 0V 24V1 X7 GND1 24V2 Y0 GND2 24V2 Y7 GND2 24V1 G...

Страница 6: ... software model R7CFG Refer to the users manual of the software for detailed operations CHANNEL BATCH SETTING PARAMETER SETTING RANGE DEFAULT SETTING Conversion rate 1 ms 5 ms 10 ms 20 ms 50 ms 70 ms 100 ms 200 ms 10 ms Output Hold Clear Hold Clear Hold ETHERNET SETTING PARAMETER SETTING RANGE DEFAULT SETTING IP Address 0 0 0 0 255 255 255 255 192 168 0 250 Subnet Mask 0 0 0 0 255 255 255 255 255 ...

Страница 7: ...ing command on the Windows MS DOS as follows C WINDOWS ping Enter IP address in decimal ping with 32 bytes of data Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Ping statistics for Packets Sent 4 Received 4 Lost 0 0 loss Replies in case of normal connection are as shown above If the connection can...

Отзывы: