EM-7801-AD  P. 1 / 9

INSTRUCTION MANUAL

DC VOLTAGE OUTPUT MODULE, 4 points

(CC-Link V.1.10)

MODEL

R7C-YV4

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

DC voltage output module ..................................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• The equipment must be mounted inside the instrument

panel of a metal enclosure.

• The actual installation environments such as panel con-

figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system.  The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.

 

POWER INPUT RATING & OPERATIONAL RANG

• Locate the power input rating marked on the product and

confirm its operational range as indicated below:

24V AC rating: 24V ±10%, 50/60Hz, approx. 180mA
24V DC rating: 24V ±10%, approx. 90mA

 

GENERAL PRECAUTIONS

• Before you remove the unit or mount it, turn off the power 

supply and output signal for safety.

• DO NOT set the switches on the module while the power

is supplied.  The switches are used only for maintenance
without the power.

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the

air, install the unit inside proper housing with sufficient
ventilation.

• Do not install the unit where it is subjected to continuous

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -10 to +55°C

(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.

 

WIRING

• Do not install cables close to noise sources (relay drive

cable, high frequency line, etc.).

• Do not bind these cables together with those in which

noises are present.  Do not install them in the same duct.

 

AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Содержание R7C-YV4

Страница 1: ...OPERATIONAL RANG Locate the power input rating marked on the product and confirm its operational range as indicated below 24V AC rating 24V 10 50 60Hz approx 180mA 24V DC rating 24V 10 approx 90mA GEN...

Страница 2: ...ss Setting x10 BAUD RATE Baud Rate is selected with the rotary switch 5 4 3 2 1 0 9 8 7 6 Baud Rate Setting 0 156 kbps 1 625 kbps 2 2 5 Mbps 3 5 Mbps 4 10 Mbps OPERATING MODE Factory setting Output at...

Страница 3: ...addressed to the station due to noise interference Missing parts of the data sent from the master ON OFF OFF OFF OFF Unable to receive data due to wire breakdown ON OFF ON OFF ON OFF Faulty Baud Rate...

Страница 4: ...LS for OUTPUT 6 24 50 1 97 6 24 18 5 73 115 4 53 DIN RAIL 35mm wide 5 20 30 1 18 54 2 13 17 66 CONNECTION DIAGRAM 4 7 6 3 2 5 1 V U FG SLD DG DB DA OUTPUT 0 In order to improve EMC performance bond th...

Страница 5: ...ON Unused Unused Unused Unused RWrn 0 1 2 3 Analog output 0 Analog output 1 Analog output 2 Analog output 3 RWwn 0 1 2 3 Interval timed Response X Refresh Data Y ANALOG OUTPUT I O DATA DESCRIPTIONS 0...

Страница 6: ...hick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out of the control panel Choose a thick and short cable to ground the FG terminal of the R7C module to...

Страница 7: ...he panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impedance using e g braided wires Keep the opening for ventilation as small as...

Страница 8: ...s are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise overlapping to the cables Attach a ferrite core to reduce noise impact to the...

Страница 9: ...Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of the shielded cable cover and ground it to the internal panel plate using an earth clamp To connect...

Отзывы: