R6-NP1
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-7792 Rev.2 P. 3 / 4
COMPONENT IDENTIFICATION
ERR Indicator LED
Configuration Jack
Station No. Setting
Rotary SW, lower digit
Network Connector
Station No. Setting
Rotary SW, upper digit
RUN Indicator LED
8
67
345
2
1
0
F E D C B A
9
8
67
345
2
1
0
F E D C B A
9
■
PROFIBUS INTERFACE
6
9
1
5
PIN NO.
SIGNAL
SIGNIFICANCE
1
NC
Not used
2
NC
Not used
3
B_ine
Network, B-line
4
RTS
RTS signal
5
GND
0V
6
P5V
5V
7
NC
Not used
8
A_line
Network, A-line
9
NC
Not used
■
FRONT ROTARY SW
• Station No.: SA1, SA2
Station No. is set in Hexadecimal.
(Setpoint adjustment: 00 – 7D)
■
INDICATOR LED
ID
STATE
EXPLANATION
RUN
Green ON
Transmitting
Green blinking
Data hold
OFF
Communication error
Red ON
Hardware error
ERR
OFF
Normal operating
Transmitting
Green ON/
blinking
I/O module error
Red ON
No master
Red blinking
Address error
PC CONFIGURATOR
With configurator software, settings shown below are available.
Refer to the software manual of R6CON for detailed operation.
■
INTERFACE MODULE SETTING
PARAMETER
AVAILABLE RANGE
DEFAULT SETTING
Card map
1 to 31