INSTRUCTION MANUAL

DISCRETE OUTPUT MODULE

(relay contact output, 8 points, tension clamp terminal block)

MODEL

R3S-DC8

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Discrete output module.......................................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• This equipment is suitable for Pollution Degree 2 and 

Measurement Category II (output, transient voltage 
2500V).  Basic insulation (output to internal bus or in-
ternal power: 250V) is maintained.  Prior to installation, 
check that the insulation class of this unit satisfies the 
system requirements.

• Altitude up to 2000 meters.
• The equipment must be mounted inside the instrument 

panel of a metal enclosure.

• The equipment must be installed such that appropriate 

clearance and creepage distances are maintained to con-
form to CE requirements.  Failure to observe these re-
quirements may invalidate the CE conformance.

• The actual installation environments such as panel con-

figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure the CE conform-
ity.

 

HOT SWAPPABLE MODULES

• Replacing the module does not affect other modules on 

the same base.  Thus, the module can be replaced while 
the power is ON.  However, replacing multiple modules 
at once may greatly change live voltage levels.  We highly 
recommend to replace them one by one.

 

GENERAL PRECAUTIONS

• DO NOT set the switches on the module while the power 

is supplied.  The switches are used only for maintenance 
without the power.

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the 

air, install the unit inside proper housing with sufficient 
ventilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -10 to +55°C 

(14 to 131°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

 

WIRING

• Do not install cables close to noise sources (relay drive 

cable, high frequency line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

 

AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

INSTALLATION

Use the Installation Base (model: R3-BSx).