INSTRUCTION MANUAL

DISCRETE OUTPUT MODULE

(NPN transistor output, 16 points)

MODEL

R30YN16A

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Discrete output module.......................................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• 

The equipment must be mounted inside the instrument 
panel of a metal enclosure.

• 

The actual installation environments such as panel con-
figurations, connected devices and connected wires may 
affect the protection level of this unit when it is integrat-
ed in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure CE conformity.

 

GENERAL PRECAUTIONS

• 

Before you remove the terminal block or mount it, turn off 
output signals for safety.

 

HOT INSERTION/REMOVAL OF MODULES

• 

It is possible to replace the module with the power sup-
plied, provided that modules are of the same model num-
ber and that the same Installation Base slot is used.

• 

Turn off output signals before replacing the module for 
safety.  Note that replacing multiple modules at once may 
greatly change line voltage levels.  We recommend that 
you replace them one by one.

 

ENVIRONMENT

• 

Indoor use.

• 

When heavy dust or metal particles are present in the 
air, install the unit inside proper housing with sufficient 
ventilation.

• 

Do not install the unit where it is subjected to continuous 
vibration.  Do not subject the unit to physical impact.

• 

Environmental temperature must be within -10 to +55°C 
(14 to 131°F) with relative humidity within 10 to 90% RH 
in order to ensure adequate life span and operation.

 

WIRING

• 

Do not install cables close to noise sources (relay drive 
cable, high frequency line, etc.).

• 

Do not bind these cables together with those in which 
noises are present.  Do not install them in the same duct.

• 

Be sure to attach the terminal cover for safety.

 

AND ....

• 

The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

 

OUTPUT AT THE LOSS OF COMMUNICATION

• 

Holds the output of the last normally received data.

• 

“Reset to 0” setting is not available. 