R3-NMW1F

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8286  P. 3 / 10

COMPONENT IDENTIFICATION

Antenna Connector

■ 

FRONT VIEW

■ 

SIDE VIEW

RUN LED

ERR LED

Maintenance

Connector

920Run LED

920Link LED

SW2

ON

8

7

6

5

4

3

2

1

SW3

ON

4

3

2

1

ON

8

7

6

5

4

3

2

1

SW1

DIP SW

Tension clamp

Terminal

Configuration Jack

RUN Contact Output,

Power Input Terminal

NC

NC

NC

NC

RUN

ERR

920Run

920Link

CFG1

CFG2

 

STATUS INDICATOR LED

ID

STATUS

COLOR FUNCTION

RUN*

1

ON

Green

Output writable port: normal 
communication

ON

Red

Wired: receiving data

ERR*

1

ON

Green

Output writable port: commu-
nication error

ON

Red

Wired: transmitting data

920Run

ON

Green

Wireless: normal communica-
tion

920Link

ON

Green

Wireless: coordinator is con-
nected

0.5 Hz 

blinking

Green

Wireless: coordinator connec-
tion in process

Blinking

Red

Network authentication failure

ON

Red

NO detour

*1. Refer to “LED Function: SW3-4” below.

 

SIDE DIP SW

(*) Factory setting

• Data Allocation: SW1, SW2

Data Allocation Type*

2

 must be assigned to each I/O module 

slot position to specify how many data areas (four types) are 
to be occupied by each module.
Two bits from SW1 and SW2 are assigned to each position, 
so as to specify data areas for each of the slots No. 1 to 8. 
Setting for No. 9 and later slots is identical to No. 8.

SW ASSIGNMENT

SLOT

SW1-1

SW1-2

1

SW1-3

SW1-4

2

SW1-5

SW1-6

3

SW1-7

SW1-8

4

SW2-1

SW2-2

5

SW2-3

SW2-4

6

SW2-5

SW2-6

7

SW2-7

SW2-8

8

SW SETTING

DATA ALLOCATION

OFF

OFF

1

ON

OFF

4

OFF

ON

8

ON

ON

16

*2.  Refer to the specifications of the related series for the Data 

Allocation Type of I/O modules.

• Dual Communication: SW3-1

When two network modules are mounted, one must be 
‘Main’ (OFF) network and the other must be ‘Sub’ (ON) net-
work.  For single communication, the network module must 
always be set to ‘Main’ (OFF).

SW

DUAL COMMUNICATION

MAIN 

(*)

SUB

SW3-1

OFF

ON

• Input Error Data: SW3-2

Hold

: When the communication from an input module is lost 

due to the input module error, the network module holds the 
signal and stands by until the communication recovers.

Set to ‘0’

: When the communication from an input module 

is lost due to the input module error, the network module 
outputs ‘0.’

SW

INPUT ERROR DATA

HOLD 

(*)

SET  ‘0’

SW3-2

OFF

ON

• Main/Sub Switching Control: SW3-3

The host PC or PLC can choose whether ‘Main’ or ‘Sub’ bus 
is used when the switching control is set to ‘Host.’
In ‘Normal’ mode, ‘Main’ bus is normally used, while ‘Sub’ 
bus is when the main communication has failed.

SW

MAIN/SUB SWITCHING CONTROL

NORMAL 

(*)

HOST

SW3-3

OFF

ON

Note 1:  Be sure to match this control mode for both network 

modules in dual communication mode.

Note 2: Must be “OFF” in single communication mode.

• LED Function: SW3-4

Functions assigned to the front RUN and ERR LEDs can 
be selected.

SW3-4

LED FUNCTION

RUN

ERR

OFF (*)

Green when normal
OFF when Timeout

Green ON/blinking when abnormal 
OFF when normal

ON

Red when receiving Red when transmitting

Содержание R3-NMW1F

Страница 1: ...cles are present in the air install the unit inside proper housing with sufficient ventilation Do not install the unit where it is subjected to continuous vibration Do not subject the unit to physical...

Страница 2: ...s own expense This transmitter must not be co located or operated in conjunction with any other antenna or transmitter FCC RF EXPOSURE INFORMATION This equipment complies with FCC radiation exposure l...

Страница 3: ...SW1 2 1 SW1 3 SW1 4 2 SW1 5 SW1 6 3 SW1 7 SW1 8 4 SW2 1 SW2 2 5 SW2 3 SW2 4 6 SW2 5 SW2 6 7 SW2 7 SW2 8 8 SW SETTING DATA ALLOCATION OFF OFF 1 ON OFF 4 OFF ON 8 ON ON 16 2 Refer to the specifications...

Страница 4: ...selectable up to 10 channels 0 Short address 0000 invalid 0001 to FFFD hexadecimal 4 digits 0000 Network name English one byte characters within 16 characters one byte space _ are usable Blank Encrypt...

Страница 5: ...S Connect the unit as in the diagram below EXTERNAL DIMENSIONS unit mm inch 109 4 29 45 1 77 200 7 87 TERMINAL COVER 109 4 29 2500 98 43 Dia 3 12 Dia 1 2 05 Dia 27 1 06 36 1 42 80 3 15 WITH SLEEVE ANT...

Страница 6: ...rawing below for recommended ring tongue terminal size Spade tongue type is also applicable Solder less terminals with insulation sleeve do not fit Recommended manufacturer Japan Solderless Terminal M...

Страница 7: ...ad write 07 Read Exception Status 08 Diagnostics 09 Program 484 10 Poll 484 11 Fetch Comm Event Counter 12 Fetch Comm Event Log 13 Program Controller 14 Poll Controller 15 Force Multiple Coils X Digit...

Страница 8: ...t corresponding to such module turns to 1 Main Sub Switching Commands given to the network modules result as follows MAIN MODULE SUB MODULE OUTPUT MODE 1 0 Main bus is used Red LED turns on at RUN LED...

Страница 9: ...nt 0 15 TEMPERATURE DATA 16 bit data models R3 RS4 TS4 and US4 etc 16 bit binary data With C temperature unit raw data is multiplied by 10 For example 25 5 C is converted into 255 With F temperature u...

Страница 10: ...1025 0 Address 01025 1 R3 sub network main sub switching control 1 2 3 4 5 1 When the main sub switching control for both main and sub network is set to 0 all contact outputs are off and analog output...

Отзывы: