8. INPUT RANGE SELECTING
Select switches to match the input signal according to the table below. For fine range setting, the R1X
Configurator Software (model: R1CON) including a dedicated cable is required.
SW311 SW305 SW304 SW303 SW302
SW405 SW404 SW403 SW402
SW301
O
N
2
1
3
4
5
6
7
8
SW411
SW401 SW308 SW307 SW306
SW408 SW407 SW406
O
N
2
1
3
4
5
6
7
8
INPUT
SWITCHES
SETTING
NOTES
Thermocouple
SW301 – SW308 (ch 1 – ch 8)
SW401 – SW408 (ch 9 – ch 16)
Set to position “1”
Attenuation OFF
SW311 (ch 1 – ch 8)
SW411 (ch 9 – ch 16)
OFF
Voltage input, 0.8V or less
SW301 – SW308 (ch 1 – ch 8)
SW401 – SW408 (ch 9 – ch 16)
Set to position “1”
Attenuation OFF
SW311 (ch 1 – ch 8)
SW411 (ch 9 – ch 16)
ON
Voltage input, above 0.8V (*)
SW301 – SW308 (ch 1 – ch 8)
SW401 – SW408 (ch 9 – ch 16)
Set to position “3”
Attenuation ON
SW311 (ch 1 – ch 8)
SW411 (ch 9 – ch 16)
ON
(*) Factory setting unless specific input types and ranges are specified when ordering
R1C-GH
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-5956 Rev.11 P. 8 / 13