background image

7.1.5.  COMMUNICATION ERROR OPERATION

The actuator operation in case of a communication error 
once normal communication is established after the power 
is turned on is defined as follows:

SW6-3

SW6-4

COMM. ERROR OPERATION

OFF

OFF

Stop

ON

OFF

0% position

OFF

ON

100% position

ON

ON

Stop

7.2.  CC-Link
7.2.1.  STATION NO.

Set the upper digit (x10) with SW1 and the lower digit (x1) 
with SW2.
This device occupies one station.

7.2.2. BAUD RATE

The baud rate is selected with the SW3.

SW3

BAUD RATE

0

156 kbps

1

625 kbps

2

2.5 Mbps

3

5 Mbps

4

10 Mbps

All other settings are invalid.

7.2.3. COMMUNICATIONS

 

MASTER to SLAVE

DATA TYPE

ADDRESS

FUNCTION

DETAIL

Bit

RY0

Forced Closed Position Input *

1

0 : Disable     1 : Position = 0%

RY1

Forced Open Position Input *

1

0 : Disable     1 : Position = 100%

RY2
RY3
RY4
RY5
RY6
RY7
RY8

Enable Target Position Input

0 : Disable     1 : Enable

RY9
RYA

Reset Motor Deadlock Alarm

Motor deadlock alarm is canceled when ‘1’ is set.

RYB

Clear Motor Starting Counter

Motor starting counter is reset to 0 when ‘1’ is set.

RYC

Clear Motor Reversing Counter

Motor reversing counter is reset to 0 when ‘1’ is set.

RYD

Clear Accumulated Running Distance Accumulated running distance is reset to 0 when ‘1’ is set.

RYE
RYF

Word

RWw0

Target Position Input

Signed, 0.01% increments (e.g. 100 = 1.00%)
Valid only when Enable Target Position Input is enabled.

RWw1
RWw2
RWw3

*1. Valid regardless of the RY8 (Enable Target Position Input) status.  Stopped when ‘1’ is set both at RY0 and RY1.

MSP4C / MSP5C / MSP6C

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-4862  Rev.1  P. 7 / 9

Содержание MSP4C

Страница 1: ...7 1 1 GENERAL PROCEDURE 6 7 1 2 ZERO SPAN 6 7 1 3 DEADBAND 6 7 1 4 RESTART LIMITING TIME 6 7 1 5 COMMUNICATION ERROR OPERATION 7 7 2 CC Link 7 7 2 1 STATION NO 7 7 2 2 BAUD RATE 7 7 2 3 COMMUNICATIONS...

Страница 2: ...together with mains supply ca bles or high voltage cables Do not install them in the same duct OUTDOOR USE When installing the MSPxC outdoor or where it is ex posed to rain or water drops be sure to f...

Страница 3: ...R XS2M D424 2 OMRON PIN ASSIGNMENT 1 24 V 2 Not used 3 GND 4 Not used COMMUNICATION MONITOR INDICATOR LED ID STATUS MEANING L RUN ON Communicating Blink OFF Not entering the network yet Timeout L ERR...

Страница 4: ...signals 25 50 75 100 0 INPUT Adjustable SPAN at ZERO CCW counterclockwise Adjustable SPAN at ZERO CW clockwise 0 25 50 75 100 OUTPUT STEM POSITION SPAN CCW ZERO CW ZERO CCW SPAN CW Adjustable SPAN Ad...

Страница 5: ...Check that the opening between the yoke and valve bonnet is closed Fix the yoke and valve 7 Attach the position indicator if required MSPxC Bolt M5 Position Indicator Yoke Actuator Stem Lock Nut Valve...

Страница 6: ...acted position valve s extended position is ad equate For three way valves the sealing pressure can be adjust ed to be applied in the direction where the output stem is fully retracted not available f...

Страница 7: ...Forced Open Position Input 1 0 Disable 1 Position 100 RY2 RY3 RY4 RY5 RY6 RY7 RY8 Enable Target Position Input 0 Disable 1 Enable RY9 RYA Reset Motor Deadlock Alarm Motor deadlock alarm is canceled w...

Страница 8: ...ed 16 bit data representing 0 01 by 1 LSB Set Enable Target Position Input to 1 Set Target Position Input For example set 5000 in binary for 50 setpoint Set 50 for 0 5 Binary must be 2 s complement Po...

Страница 9: ...perated run a test operation regularly once a week for example to check proper functions 9 TROUBLESHOOTING TROUBLE L RUN L ERR POSSIBLE CAUSE HOW TO PROCEED No Func tion ON OFF Normal communication Co...

Отзывы: