background image

MSP40 / MSP50

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-4883    P. 3 / 18

2.  POINTS OF CAUTION

 

POWER INPUT RATING & OPERATIONAL RANGE

• Locate the power input rating marked on the product and 

confirm its operational range as indicated below:

    24V DC: 24V rating ±10%, approx. 0.6A

 

HUNTING

• Hunting is a condition in which the output stem is os-

cillated repeatedly and persistently without settling at a 
single position.

• The actuator unit must operate at an average duty cycle 

of 50% (approx. 13 strokes per minute) or less.

 

GENERAL PRECAUTIONS

• Remove the power supply to the actuator before wiring 

the unit.

• DO NOT install signal wires and power supply wires to-

gether in one duct because it may cause a malfunction 
due to induction noises.  Alternatively, use shielded cables 
for the input signal wires to prevent interference from 
such noises.

• If input signals are to be turned on/off with power sup-

plied to the actuator, be sure to specify the output stem 
operation for when abnormally low input is detected.

• DO NOT loosen the screws fixing the potentiometer in-

side the unit.

 

INSTALLATION

• Indoor, or outdoor where the unit is NOT exposed to di-

rect sunlight.

• Operating temperature -5 to +55°C (23 to +131°F)
• Operating humidity 30 to 85% RH (non-condensing)
• The unit is not designed to withstand all vibrations.  

M-System does not guarantee long-term use of the unit 
even with small vibrations.  Please use the unit only after 
evaluating in an actual installation environment.  Par-
ticularly, avoid using under the condition where valve 
cavitation or water hammer is likely to occur.

• Install the unit where it can be reached for maintenance 

and inspection.  Be sure to allow at least 20 cm (7.9 inch-
es) clearance above the unit and around the terminal box.

• Keep away from hazardous atmosphere such as explosive 

or corrosive gases.

 

PID CONTROL SIGNAL

• Choose PID parameters carefully so that the MV remains 

as stable as possible to prevent hunting.  Unstable control 
shortens the life of actuator and valve.

 

REATTACHING TERMINAL BOX COVER

• When reattaching the terminal box cover after wiring, 

make sure that the O-rings are securely in place.

 

SCREW TORQUE

• The torque for tightening screws for the terminal cover is 

between 1.2 – 2 N·m (0.89 – 1.5 ft·lbf).  The screws must 
be tightened evenly and crosswise in several steps to pre-
vent uneven clamping.

 

YOKE DESIGN

• When a foreign object is caught in the valve, an excessive 

torque may be applied to the yoke.  Taking it into account, 
design the yoke and joint so as to have sufficient margin 
in strength.

• When this unit is used in an application such as temper-

ature control of a steam line, the temperature can rise 
higher than the ambient temperature due to heat con-
ducted through or radiated from the piping.  Use a longer 
yoke for effective heat dissipation and apply insulation 
material.

Содержание MSP40

Страница 1: ...BLE CONNECTIONS 6 7 OUTPUT STEM STROKES 7 8 SEAL SPRING CONTRACTION AND THRUST 7 9 COMBINATION WITH VALVE 8 10 AUTO SETUP MODE 9 11 PROGRAMMING UNIT MODEL PU 2x 12 12 MODBUS COMMUNICATION 13 13 PARAME...

Страница 2: ...failure to observe the pre cautions could result in personal injury or damage to the property WARNING Remove power supply to the actuator before wiring to the unit It could cause electric shock Do not...

Страница 3: ...to withstand all vibrations M System does not guarantee long term use of the unit even with small vibrations Please use the unit only after evaluating in an actual installation environment Par ticula...

Страница 4: ...l Spring Stepping Motor Potentiometer Cover Nut Output stem Screw Figure 1 Component identification MSP40 MSP50 DA NC IN FE1 UPP UPP LOW LOW ALM ALM 24V GND COM OUT DB DG PWR UPPER LOWER INP STA COM A...

Страница 5: ...h 20 mA DC input ON Direct Output stem goes DOWN with 20 mA DC input SW1 4 OFF Output stem moves while the manual operation button is pressed in Manual Operation mode ON Output stem moves inch by inch...

Страница 6: ...retract UP extend DOWN alarm and or output signals as necessary Modbus communication allows operation without analog input and monitoring of the operation status of the unit DA DB DG IN COM OUT 24V GN...

Страница 7: ...RACTION AND THRUST Thrust and Seal Spring Contraction MODEL RATED THRUST N THRUST WHEN VALVE IS SEATED N THRUST WHEN AUTO SEUP IS COMPLETE N AJUSTABLE MAX CONTRACTION MAX THRUST N MAX THRUST WHEN OUTP...

Страница 8: ...void such a situation select an appropriate combination of an actuator and a valve to secure an enough opera tion distance In the example below the maximum stroke is 20 mm and thus the preferable oper...

Страница 9: ...h back to Automatic Operation mode Note that the actuator immediately starts to operate in accordance with a value of input signal DO NOT touch the output stem and its vicinity as it may cause serious...

Страница 10: ...ositions then stops to end Auto setup 4 Lower Upper seal springs MSP50 only 1 The output stem goes down until the valve contacts the seat surface Auto setup is interrupted if the valve reaches the low...

Страница 11: ...newly set the upper end position To complete the fine adjustment Lower end side Turn SW1 5 from OFF to ON then to OFF again to newly set the lower end position Upper end side Turn SW1 6 from OFF to ON...

Страница 12: ...e display of PU 2x comes on by power supplied to the actuator unit 3 To display a target item press ITEM then N N N represents numerical number 0 to 9 Alternatively use UP or DOWN button to shift to t...

Страница 13: ...ven if the address is writable make sure to set Modbus Operation mode address 111 in advance to enable writing ADDRESS MAP Refer to 13 PARAMETER ITEMS COMMON TO MODBUS AND PU 2x for Modbus address map...

Страница 14: ...04 Inp x R 18 I16 Position setpoint 1 5 0 to 105 0 05 Tar x R 19 I16 Position 1 5 0 to 105 0 06 Pos x R 1 The ratio to the operation distance i e a distance between the lower stop position and the up...

Страница 15: ...times when the duty cycle per minute exceeded 50 1 Clear 0 1 0 26 AccumClr x R W 52 I16 Time ratio of respective positions 1 Clear 0 1 0 27 PosRClr x R W 53 I16 Clear all diagnostics 1 Clear 0 1 0 28...

Страница 16: ...98 0 44 OpnSig x R W 136 I16 Extend DOWN signal position 5 0 to 25 0 2 0 45 ClsSig x R W 137 I16 Deadband 0 1 to 5 0 0 3 46 DBand x R W 138 I16 Restart limiting timer sec 0 0 to 30 0 1 5 47 Restart x...

Страница 17: ...guration mode Stops Modbus input Monitor mode Stops Modbus input mode Follows Modbus input Address 101 Configuration mode Stops ON N A 2 Monitor mode 4 Moves by button operation 1 Configurable on PU 2...

Страница 18: ...acement contact M System or our representatives LUBRICATION There is no need of oiling the Mini Top electronic actuator in normal operating conditions REGULAR TEST RUNNING If the valve is not frequent...

Отзывы: