MSP40 / MSP50

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-4883    P. 16 / 18

13.7.  Modbus setting

MODBUS

ITEM

VALUE RANGE

STANDARD

EX-FACTORY

*

4

PU-2x

R/W SAVE

ADDRESS TYPE

ITEM

DISPLAY

121

I16

Node address

1 to 247

1

60

Addr:x

R/W

122

I16

Baud rate

 0: 4.8 kbps
 1: 9.6 kbps
 2: 19.2 kbps
 3: 38.4 kbps

0 to 3

3

61

Baud:x

R/W

123

I16

Internal terminating resistor

 0: OFF
 1: ON

0, 1

0

62

Term:x

R/W

124

I16

Input mode

 0: Analog input
 1: Modbus input

0, 1 

0

63

InputSel:x R/W

125

I16

Modbus disconnection detection time

(When Modbus disconnection is detected 
during Modbus input mode, the actuator 
operates according to SW1-1 and 1-2 set-
tings of the unit.)

 0: No detection
 1:  Detects disconnection when a Modbus 

command is not issued for the set time 
period

0 to  300

0

64

Timeout:x R/W

*4  The standard EX-factory setting will be applied unless otherwise specified when ordering.

13.8.  Basic setting

MODBUS

ITEM

VALUE RANGE

STANDARD 

EX-FACTORY

*

4

PU-2x

R/W SAVE

ADDRESS TYPE

ITEM

DISPLAY

131

I16

Upper-stop position %

8.0 to 100.0

100.0

40

OpnPos:x

R/W

132

I16

Lower-stop position %

0.0 to 92.0

0.0

41

ClsPos:x

R/W

133

I16

Upper-end limit %

75.0 to 105.0

100.0

42

OpnLim:x R/W

134

I16

Lower-end limit %

-5.0 to 25.0

0.0

43

ClsLim:x

R/W

135

I16

Retract/UP signal position %

75.0 to 105.0

98.0

44

OpnSig:x

R/W

136

I16

Extend/DOWN signal position %

-5.0 to 25.0

2.0

45

ClsSig:x

R/W

137

I16

Deadband %

0.1 to 5.0

0.3

46

DBand:x

R/W

138

I16

Restart limiting timer (sec.)

0.0 to 30.0 

1.5

47

Restart:x

R/W

139

I16

Moving distance of the output stem for fine 
adjustment in Manual Operation mode

 0: 0.02 mm
 1: 0.05 mm
 2: 0.1 mm

0 to 2

1

48

Manual:x

R/W

*4  The standard EX-factory setting will be applied unless otherwise specified when ordering.

13.9.  Setting/executing Auto-setup

MODBUS

ITEM

VALUE RANGE

STANDARD

EX-FACTORY

*

4

PU-2x

R/W SAVE

ADDRESS TYPE

ITEM

DISPLAY

141

I16

Auto-setup type

 0: Lower seal spring
 1:  Lower seal spring & Stroke specified
 2: Upper seal spring
 3:  Upper seal spring & Stroke specified
 4:  Lower & Upper seal springs
(2 to 4 are available only for MSP50)

MSP40: 0, 1

MSP50: 0 to 4

0

50

ASType:x

R/W

142

I16

Lower seal spring contraction amount (mm)

0.1 to 1.2

0.1

51

ASPushDn:x R/W

143

I16

Upper seal spring contraction amount (mm)

0.1 to 1.2

0.1

52

ASPushUp:x R/W

144

I16

Stroke / operation distance (mm)

3.0 to 20.0

5.0

53

ASStroke:x R/W

145

I16

Execute Auto-seup

 1: Start
 2: Abort / Clear error

0 to 2

0

54

ASStart:x R/W

146

I16

Auto-setup history 1: Upper-stop position %

8.0 to 100.0

0.0

55

AS1Opn:x

R

147

I16

Auto-setup history 2: Lower-stop position %

0.0 to 92.0

0.0

56

AS1Cls:x

R

148

I16

Auto-setup history 3: Upper-stop position %

8.0 to 100.0

0.0

57

AS2Opn:x

R

149

I16

Auto-setup history 4: Lower-stop position %

0.0 to 92.0

0.0

58

AS2Cls:x

R

*4  The standard EX-factory setting will be applied unless otherwise specified when ordering.

Содержание MSP40

Страница 1: ...BLE CONNECTIONS 6 7 OUTPUT STEM STROKES 7 8 SEAL SPRING CONTRACTION AND THRUST 7 9 COMBINATION WITH VALVE 8 10 AUTO SETUP MODE 9 11 PROGRAMMING UNIT MODEL PU 2x 12 12 MODBUS COMMUNICATION 13 13 PARAME...

Страница 2: ...failure to observe the pre cautions could result in personal injury or damage to the property WARNING Remove power supply to the actuator before wiring to the unit It could cause electric shock Do not...

Страница 3: ...to withstand all vibrations M System does not guarantee long term use of the unit even with small vibrations Please use the unit only after evaluating in an actual installation environment Par ticula...

Страница 4: ...l Spring Stepping Motor Potentiometer Cover Nut Output stem Screw Figure 1 Component identification MSP40 MSP50 DA NC IN FE1 UPP UPP LOW LOW ALM ALM 24V GND COM OUT DB DG PWR UPPER LOWER INP STA COM A...

Страница 5: ...h 20 mA DC input ON Direct Output stem goes DOWN with 20 mA DC input SW1 4 OFF Output stem moves while the manual operation button is pressed in Manual Operation mode ON Output stem moves inch by inch...

Страница 6: ...retract UP extend DOWN alarm and or output signals as necessary Modbus communication allows operation without analog input and monitoring of the operation status of the unit DA DB DG IN COM OUT 24V GN...

Страница 7: ...RACTION AND THRUST Thrust and Seal Spring Contraction MODEL RATED THRUST N THRUST WHEN VALVE IS SEATED N THRUST WHEN AUTO SEUP IS COMPLETE N AJUSTABLE MAX CONTRACTION MAX THRUST N MAX THRUST WHEN OUTP...

Страница 8: ...void such a situation select an appropriate combination of an actuator and a valve to secure an enough opera tion distance In the example below the maximum stroke is 20 mm and thus the preferable oper...

Страница 9: ...h back to Automatic Operation mode Note that the actuator immediately starts to operate in accordance with a value of input signal DO NOT touch the output stem and its vicinity as it may cause serious...

Страница 10: ...ositions then stops to end Auto setup 4 Lower Upper seal springs MSP50 only 1 The output stem goes down until the valve contacts the seat surface Auto setup is interrupted if the valve reaches the low...

Страница 11: ...newly set the upper end position To complete the fine adjustment Lower end side Turn SW1 5 from OFF to ON then to OFF again to newly set the lower end position Upper end side Turn SW1 6 from OFF to ON...

Страница 12: ...e display of PU 2x comes on by power supplied to the actuator unit 3 To display a target item press ITEM then N N N represents numerical number 0 to 9 Alternatively use UP or DOWN button to shift to t...

Страница 13: ...ven if the address is writable make sure to set Modbus Operation mode address 111 in advance to enable writing ADDRESS MAP Refer to 13 PARAMETER ITEMS COMMON TO MODBUS AND PU 2x for Modbus address map...

Страница 14: ...04 Inp x R 18 I16 Position setpoint 1 5 0 to 105 0 05 Tar x R 19 I16 Position 1 5 0 to 105 0 06 Pos x R 1 The ratio to the operation distance i e a distance between the lower stop position and the up...

Страница 15: ...times when the duty cycle per minute exceeded 50 1 Clear 0 1 0 26 AccumClr x R W 52 I16 Time ratio of respective positions 1 Clear 0 1 0 27 PosRClr x R W 53 I16 Clear all diagnostics 1 Clear 0 1 0 28...

Страница 16: ...98 0 44 OpnSig x R W 136 I16 Extend DOWN signal position 5 0 to 25 0 2 0 45 ClsSig x R W 137 I16 Deadband 0 1 to 5 0 0 3 46 DBand x R W 138 I16 Restart limiting timer sec 0 0 to 30 0 1 5 47 Restart x...

Страница 17: ...guration mode Stops Modbus input Monitor mode Stops Modbus input mode Follows Modbus input Address 101 Configuration mode Stops ON N A 2 Monitor mode 4 Moves by button operation 1 Configurable on PU 2...

Страница 18: ...acement contact M System or our representatives LUBRICATION There is no need of oiling the Mini Top electronic actuator in normal operating conditions REGULAR TEST RUNNING If the valve is not frequent...

Отзывы: