HOW TO RESET

After you calibrated manually with these switches, you 
can reset them to its ex-factory state by pressing both UP/
DOWN switches at once.

 

ADJUSTMENT PROCEDURE

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for 
more than 20 minutes.

1) ZERO:  Apply 0% input.  Slide the Zero/Span Selector to 

the bottom position.  Press UP or DOWN switch and ad-

just output to 0%.

2) SPAN:  Apply 100% input.  Slide the Zero/Span Selector 

to the top position.  Press UP or DOWN switch and adjust 

output to 100%.

3) Check ZERO adjustment again with 0% input.
4) The ZERO and SPAN adjustments are processed in a dig-

ital processor, and therefore they do not interact.  Howev-

er, if ZERO value is changed, repeat the above procedure 

1) – 3).

I/O RANGE MODIFICATION

Configurator software is used to change input over the de-
scribed range of the selected suffix code.  For changing out of 
this range (between S1 and S2), set the Input Range Selec-
tor on the side of unit before software adjustment.
For a current input, set the Selector to the same setting as 
for S2 and use a receiving resistor.
Output ranges can be changed over the described range of 
the selected suffix code with the Configurator Software.
For changing out of this range, set the Output Range Selec-
tors before software adjustment.

UP/DOWN Switches

The front cover cannot be turned open by 180 deg. 

when there is no extra space between units.

Configurator Jack

■ 

FRONT VIEW (with cover open)

■ 

RIGHT SIDE VIEW

■ 

LEFT SIDE VIEW

    (with cover removed)

Status Indicator LED

Zero/Span Selector

Top: SPAN

Middle: OFF

Bottom: ZERO

Input Range Selector

Position L

Position H

: code S1

: code S2, Z1

Output Range Selectors

[e.g.]
Output code V1

O

N

2

1

3

4

5

6

7

8

O N

2

1

3 4

SW2

ATT

SW3

SW6

SW4

SW7

I

V

I

V

• 

Input range selector

CODE

USABLE RANGE

SETTING

S1

-1 to +1V DC

L

S2

-10 to +10V DC

H

Z1

0 to 50mA DC

H

• 

Output range selectors

SW2

SW3

1

2

3

4

V1

OFF

OFF

ON

ON

Not ATT

V2

OFF

OFF

ON

ON

Not ATT

Z1

ON

ON

OFF

OFF

Not ATT

SW4

1

2

3

4

5

6

7

8

V1

ON

ON OFF ON

ON

*

ON OFF

V2

ON OFF ON OFF ON

*

ON OFF

Z1

OFF OFF ON OFF OFF OFF OFF OFF

SW6

SW7

V

I

V

I

V1

ON

OFF

ON

OFF

V2

ON

OFF

ON

OFF

Z1

OFF

ON

OFF

ON

* ON/OFF position is irrelevant.

STATUS INDICATOR LED

The M2XF2 is provided with a status indicator LED which 
blinks in different patterns indicating various status of its 
CPU.
When it is functioning within normal parameters, the LED 
blinks in a regular pattern of ON and OFF.
When the unit is in an abnormality, it blinks in particular 
patterns repeating approximately in 1.3 seconds.
The following figure indicates typical patterns.  A white 
circle means that the light is OFF for 80 millisec., while a 
black one means ON for 80 millisec.

Running mode

Undefined functions

Program mode

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 20 minutes.  Apply 0%, 25%, 
50%, 75% and 100% input signal.  Check that the output 
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out 
of tolerance, recalibrate the unit according to the “ZERO/
SPAN ADJUSTMENTS” explained earlier.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.