CONNECTION DIAGRAM

+

INPUT

1

5

4

+

SENSOR EXCITATION

+

OUTPUT

9

12

U(+)

V(–)

POWER

13

14

4kΩ

■ 

Mechanical Contact, Open Collector

    or Clamp-on Pulse Sensor CLSP

Input Connection Examples 

+12V

■ 

Voltage Pulse

+12V

■ 

Open Collector

Output Connection Examples 

+

9

12

+

■ 

Voltage Pulse

+

9

12

+

+

+

PWR

+

+


PWR

+

1

4

+ 5

+

1

4

+ 5

U

■ 

Dry Contact AC/DC Switch

• AC Powered

LOAD

Relay or 

Counter Coil

Varistor or Spark 

Quenching Circuit

• DC Powered

LOAD

Relay or 

Counter Coil

Spark Quenching Diode

9

12

9

12

WIRING INSTRUCTIONS

 

SCREW TERMINAL

Torque: 0.8 N·m

 

SOLDERLESS TERMINAL

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm

2

 (AWG 22 to 16)

Recommended manufacturer: Japan Solderless Terminal 
MFG.Co.Ltd, Nichifu Co.,ltd

6 (.24) max

3.3 (.13) max

mm (inch)

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input voltage:  Check voltage across the terminal 

13 – 14 with a multimeter.

3) Input:  Check that the input frequency is 30 Hz or less for 

relay contact, 10 kHz or less for other types of input.

  Check also that the input pulse is of 10 msec. or wider for 

relay contact, 10 µsec. or wider for other types of input. 

4) Output:  Check that the load resistance meets the de-

scribed specifications as shown below.

OUTPUT

LOAD REQUIREMENTS

Open collector

50V DC @ 100mA max.

Voltage pulse

250Ω min. for 5V
600Ω min. for 12V
1200Ω min. for 24V

Dry contact 
AC/DC switch

132V AC @ 200mA max. (cosø=1)
30V DC @ 200mA max. (resistive load)

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.