EM-8060  Rev.6  P. 1 / 5

INSTRUCTION MANUAL

LIGHTNING SURGE PROTECTOR FOR

L

ON

W

ORKS (ultra-slim, FTT-10A)

MODEL

MD7LWA

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Surge protector ....................................................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.

LIMITATION APPLICABLE TO M-RESTER

The M-RESTER will protect electronics equipment from 
damage caused by lightning by absorbing most of the 
surge voltages.
However, M-RESTER may not be effective against cer-
tain extremely high voltages caused by a direct or almost 
direct hit by lightning.
M-RESTER must be installed according to this installa-
tion / instruction manual.

GENERAL

 

FUNCTION & FEATURES

• High discharge current capacity 20 kA (8 / 20 µs), 1 kA

(10 / 350 µs)

• Ultra-thin 7-mm-wide module can be mounted in high

density

• Excellent protection employing multi-stage SPD circuits
• DIN rail mounting and grounding
• Shield terminal provided

 

SPECIFICATIONS

LINE TO

LINE

LINE TO

EARTH

SHLD TO

EARTH

Max. continuous
operating voltage (Uc)

±1.5V

±100V

±160V*

1

Voltage protection level
(Up) @4kV (1.2 / 50 µs)

±30V

±370V

±800V*

1

Leakage current @Uc

≤ 5µA

≤ 20µA

≤ 5µA*

1

Response time

≤ 4 nsec.

≤ 20 nsec. ≤ 20 nsec.*

1

Approx. capacitance
@10 kHz

100 pF

100 pF

5 pF*

1

Max. discharge current 
(Imax)

20kA (8 / 20 µs)

1.0kA (10 / 350 µs)

Nominal current (I

N

)

100mA

Internal series resistance

≤3.3Ω including return

Insertion loss

-0.5 dB max. @DC...5 MHz, Z

0

 = 100Ω

*1.  Values for the MD7LWA-FF.

Shortcircuited for the MD7LWA-FG.

POINTS OF CAUTION

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the

air, install the unit inside proper housing with sufficient
ventilation.

• Do not install the unit where it is subjected to continuous

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -25 to +85°C

(-13 to +185°F) with relative humidity within 30 to 90%
RH in order to ensure adequate life span and operation.

• This unit needs a DIN rail as earth grounding bar.  Ox-

ide coating of an aluminium rail may lower the electric
conductivity between this module and the ground.  Use a
steel or copper rail.

 

NETWORK SPECIFICATIONS

• The MD7LWA is applicable to networks which consist

only of FTT-10A.  Not applicable to the ones connected to
Link Power network.

• For detailed information on the network, refer to L

ON-

W

ORKS

 FTT-10A Free Topology Transceiver User’s Guide

provided by Echelon.

 

DIELECTRIC STRENGTH TESTING

• The surge protector starts discharging when 100V or

greater voltage is applied between lines and earth.  Re-
move the grounding wire before conducting a test.  Be
sure to return the wire after the test.

 

AND ....

• We recommend that you keep spare surge protectors so

that you can replace them when necessary.

• Lightning surge can enter not only through signal lines

but also through power supply lines.  We recommend that
you also use the Lightning Surge Protector for Power
Lines for adequate protection.