MD-LC2

BEFORE USE ....

Thank you for choosing M-System.  Before use, check the 
contents of the package you received as outlined below.
If you have any problems or questions on the product, please 
contact M-System's Sales Office or representatives.

PACKAGE INCLUDES:

  Lightning surge protector ........................................... (1)

MODEL NO.

Check that model No. described on specification label is 
exactly what you ordered.

INSTALLATION / INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, installation, and basic maintenance 
procedure.

LIMITATION APPLICABLE TO M-RESTER

The M-Rester will protect electronics equipment from 
damage caused by lightning by absorbing most of the 
surge voltages.
However, M-Rester may not be effective against certain 
extremely high voltages caused by a direct or almost direct 
hit by lightning.
M-Rester must be installed according to this installation 
/ instruction manual.

POINTS OF CAUTION

ENVIRONMENT

• When  heavy  dust  or  metal  particles  are  present  in  the 

atmosphere, install M-RESTER inside proper housing and 
ventilate it.

•  Do  not  install  the  M-RESTER  where  it  is  subjected  to 
continuous vibration.  Do not apply physical impact to the 

M-RESTER.

• Environmental temperature must be within -5 to +55°C 
(23 to 131°F) and relative humidity within 30 – 90% RH in 

order to ensure adequate life span and operation.

DIELECTRIC STRENGTH TEST

• The unit will start discharging when 15V or greater voltage 

is applied bewteen lines and ground.  Remote the unit from 
the base socket when performing dielectric strength tests.

AND ....

• We recommend that you keep spare M-RESTERs so that 

you can replace them when necessary.

• Lightning surge can enter not only through signal lines 
but also through power supply lines.  We recommend that 

you also use the Lightning Surge Protector for Power Lines 
for sufficient protection.

COMPONENT IDENTIFICATION

SPECIFICATIONS

LIGHTNING SURGE PROTECTOR FOR STRAIN GAUGE USE

(6-wire remote sensing)

MODEL

MD-LC2

INSTALLATION / INSTRUCTION  MANUAL

Body

Base Socket

Specification

 Label

SIG (L1 to L2)

EXC (+ to –)

EXC (S+ to S–)

SIG (L1, L2) to GND

EXC (S+, +) to G

EXC (S–, –) to G

Discharge voltage

±0.3V min.

15V min.

15V min.

±15V min.

+30/-15V min.

±15V min.

Max. surge voltage*

±20V max.

40V max.

40V max.

±40V max.

+65/-40V max.

±40V max.

Leakage current

≤0.2µA

@±0.3V DC

≤2µA

@15V DC

≤2µA

@±15V DC

≤2µA

@±15V DC

Max. line voltage

±0.3V

15V

15V

±15V

+30/-15V

±15V

Response time

4 nanosec.

Discharge current

5000A

(8/20 µsec.)

capacity
Int. series resist.

approx. ≤10Ω

approx. ≤4Ω

approx. ≤10Ω

(each line)
Max. load current

100mA

200mA

100mA

(each line)

*The maximum voltage that could pass through M-RESTER.  Protected equipment must be able to withstand this voltage for a very short time period.