INSTRUCTION MANUAL

LIGHTNING SURGE PROTECTOR FOR

PHOTOVOLTAIC SYSTEM

MODEL

MATP

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Surge protector ....................................................................(1)

 

MODEL NO.

Check that the model No. described on the specifications 
matches the operational line voltage and other specifica-
tions as shown in ‘PERFORMANCE’ hereafter.

 

INSTALLATION / INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, installation, and basic maintenance 
procedure.

LIMITATION APPLICABLE TO MATP

The MATP will protect electronics equipment from dam-
age caused by induced lightning by absorbing most of 
the surge voltages.
However, MATP may not be effective against certain 
extremely high voltages exceeding its discharge current 
capacity (20 kA or 40 kA @ 8/20 µsec. waveform) caused 
by a direct or almost direct hit by lightning.
The MATP must be installed according to this installa-
tion / instruction manual.

PERFORMANCE

Max. continuous operating voltage (Uc): 600 V DC
Discharge voltage: (Line to earth) 600 V DC
Maximum surge voltage: 2.5 kV
Maximum (Imax) and Nominal (In) discharge current: (8/ 
20 μsec.)
• MATP-600Mx: 20 kA (Imax), 10 kA (In)
• MATP-600Hx: 40 kA (Imax), 20 kA (In)
Response time: ≤ 4 nsec.
Leakage current: ≤ 1 mA
Insulation resistance: ≥ 100 MΩ with 500 V DC (line to 
alarm output)
Dielectric strength: 2000 V AC @ 1 minute (line to alarm 
output)

POINTS OF CAUTION

 

INSTALLATION

• DANGER!

   DO NOT install the MATP at the point common to an 

external lightning protection device such as a lightning 
rod.  The MATP will be subject to the danger of direct 
lightning.

• DANGER!

   DO NOT perform an installation and wiring of the MATP 

during thunder storms.

• Indoor use.
• Be sure to house the MATP inside an metal enclosure for 

safety.  Even though the MATP is capable of withstanding 
an induced discharge current expected in normal condi-
tions, it is entirely possible to be hit by a certain strong 
lightning exceeding its designed capacity.  It is also sub-
ject to a direct hit by a lightning.  The MATP will be de-
stroyed by such high lightning energy.

• We recommend to install the MATP in a position where 

the monitor LED is clearly visible to facilitate inspection 
and maintenance.

• DO NOT install the MATP where it is subjected to con-

tinuous vibration.  Do not apply physical impact to the 
MATP.

• Environmental temperature must be within -25 to +80°C 

(-13 to +176°F) and relative humidity within 30 to 90% 
RH in order to ensure adequate life span and operation.

 

HIGH TEMPERATURE

• DANGER!

   The front parts of the surface may be hot.  DO NOT grab 

the sides of the module.  When the MATP’s discharge 
element  (zinc oxide element) gradually degrades, its in-
creased leakage current causes high temperature at the 
surface of the MATP, until the discharge element is final-
ly separated from the power line by the thermal breaker.  
However, a part of the module may already be too hot to 
touch safely if the module is near the end of its life. 

 

DIELECTRIC STRENGTH TESTING

• Conduct the dielectric strength test with all power sup-

ply wires removed.  The MATP will start discharging at 
the described discharge voltage if a test voltage is applied 
with all power supply wires connected.  It will result in an 
insulation failure.

 

AND....

• We recommend that you keep spare MATPs so that you 

can replace them quickly when necessary.