M5VS

P. 2 / 2

EM-2468 Rev.7

M-SYSTEM WARRANTY

M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship 
during the 36-month period following the date that such product was originally purchased if such product has been used under 
normal operating conditions and properly maintained, M-System’s sole liability, and purchaser’s exclusive remedies, under this 
warranty are, at M-System’s option, the repair, replacement or refund of the purchase price of any M-System product which is 
defective under the terms of this warranty.  To submit a claim under this warranty, the purchaser must return, at its expense, the 
defective M-System product to the below address together with a copy of its original sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, 
EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICU-
LAR PURPOSE.  M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR SPECIAL DAMAGES 
OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-
8510, E-mail: [email protected]

TERMINAL CONNECTIONS

Connect the unit as in the diagram below or refer to the con-
nection diagram on the front of the unit.

 EXTERNAL DIMENSIONS  unit: mm (inch)

 CONNECTION DIAGRAM

94 (3.70)

3 (.12)

25 (.98)

41 (1.61)

[3.3 (.13)]

• When mounting, no extra space is needed between units

.

DIN RAIL

35mm wide

8–M3.5 SCRE

W

7.3 (.29)

1 2

3 4

5 6

7 8

+

OUTPUT

5

6

7

8

+

INPUT

3

4

U(+)

V(–)

POWER

CHECKING

1)  Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2)  Power input voltage:  Check voltage across the terminal 

7 – 8 with a multimeter.

3)  Input:  Check that the input signal is within 0 – 100% of 

the full-scale.

4) Output:  Check that the load resistance meets the de-

scribed specifications.

ADJUSTMENT PROCEDURE

This unit is calibrated at the factory to meet the ordered 
specifications, therefore you usually do not need any cali-
bration.

For matching the signal to a receiving instrument or in case 
of regular calibration, adjust the output as explained in the 

following.

 HOW TO CALIBRATE THE OUTPUT SIGNAL

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for 
more than 10 minutes.

1)  ZERO:  Apply 0% input and adjust output to 0%.
2)  SPAN:  Apply 100% input and adjust output to 100%.
3)  Check ZERO adjustment again with 0% input.
4)  When  ZERO  value  is  changed,  repeat  the  above  proce

-

dure 1) – 3).

Note: Remove the sealing label for /VN option.

MAINTENANCE

Regular calibration procedure is explained below:

 CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%, 75% and 100% input signal.  Check that the output 
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of 
tolerance, recalibrate the unit according to the “ADJUST-

MENT PROCEDURE” explained earlier.

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Содержание M5VS Series

Страница 1: ...ECIFICATIONS Choose 01 for CE Power suffix code R only 02 Specify voltage See INPUT SPECIFICATIONS CE not available 2 OUTPUT Current A 4 20 mA DC Load resistance 550 Ω max D 0 20 mA DC Load resistance 550 Ω max Z Specify current See OUTPUT SPECIFICATIONS Voltage 1 0 10 mV DC Load resistance 100 kΩ min CE not available 2 0 100 mV DC Load resistance 100 kΩ min CE not available 3 0 1 V DC Load resist...

Страница 2: ...mum span 1 mA Offset Max 1 5 times span Load resistance Output drive 11 V max DC Voltage Output code 0 CE Voltage range 10 10 V DC Minimum span 1 V Offset Max 1 5 times span Load resistance Output drive 10 mA max at 1 V Max 1 25 mA output drive for negative voltage Output code 01 Not CE Voltage range 1 1 V DC Minimum span 10 mV Offset Max 1 5 times span Load resistance Min 100 kΩ Min 1 MΩ for nega...

Страница 3: ... 4 1 39 1 2 3 4 5 6 7 8 SCHEMATIC CIRCUITRY CONNECTION DIAGRAM Isolation S Z Low Drift Amplifier Output Driver INPUT 3 4 1 2 Input shunt resistor incorporated for current input OUTPUT 5 6 8 7 U V POWER POWER LED Specifications are subject to change without notice Rugghölzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 10 12 mailbox sentronic com www sentronic com Produkte Support und...

Страница 4: ...ature must be within 5 to 55 C 23 to 131 F with relative humidity within 0 to 90 RH in order to ensure adequate life span and operation WIRING Do not install cables power supply input and output close to noise sources relay drive cable high frequency line etc Do not bind these cables together with those in which noises are present Do not install them in the same duct Install lightning surge protec...

Страница 5: ... units DIN RAIL 35mm wide 8 M3 5 SCREW 7 3 29 1 2 3 4 5 6 7 8 OUTPUT 5 6 7 8 INPUT 3 4 U V POWER CHECKING 1 Terminal wiring Check that all cables are correctly con nected according to the connection diagram 2 Power input voltage Check voltage across the terminal 7 8 with a multimeter 3 Input Check that the input signal is within 0 100 of the full scale 4 Output Check that the load resistance meets...

Отзывы: